Water, Sewer, & Fireflow letter from LakehavenLakehaven WATER & SEWER DISTRICT Lakehauen Water &Sewer District -Development Engineering Section 31623 - 1st Ave S PO Box 4249 Federal Way, WA 98063-4249 Email: DE@Lakehaven.org * Telephone: 253-945-1581 or 253-945-1580 This certificate is intended to provide the applicant, land use agencies &/or public health departments with information necessary to evaluate development proposals. Lakehaven Water & Sewer District, at its sole discretion, reserves the right to delay, or deny, water service based upon capacity &/or supply limitations in Lakehaven's or Other Purveyor's system facilities. Proposed Land Use: El Building Permit -SFR Q ®Building Permit -MFR (345) 171 Building Permit -Other ❑ Subdivision () ❑ Short Subdivision () ❑ Binding Site Plan ® Boundary Line Adjustment ❑ Other (specify/describe) Tax Parcel Number(s): 172_1.04=9019, -9028, -9030, -9031, -9033, -9034, -9035, -9046, -9051, -9057, -9059, -9064, -9074, 9090 Site Address: 330XX - 13th Ave S LWSD GIS Grid: J-10 Ex. Bldg. Area to Remain: N/A sf New Bldg. Area Proposed: 593,700 sf (total, 2 MFR bldgs) + Rec. Bldg. WATER SYSTEM INFORMATION 1. ❑ Water service can be provided by service connection to an existing " diameter water main that is approximately feet from the site. 2. ® Water service for the site will require an improvement to LWSD's water distribution system of: ® a. 5+/- feet of 8" & 12" diameter water main to reach the site; and/or ® b. The construction of a water distribution system on the site; and/or ❑ c. A major portion of LWSD's comprehensive water system plan would need to be implemented and/or constructed; and/or ® d. Other (describe): LWSD Developer Extension (DE) Agreement required. Upsizing of existing water mains <8" diameter will likely be required. 3. ® a. The existing water system is in conformance with LWSD's Comprehensive Water System Plan. ❑ b. The existing water system is not in conformance with LWSD's Comprehensive Water System Plan and an Amendment to this Plan will be required. This may cause a delay in issuance of land use approvals or permits. 4. ® a. The subject property is within the corporate limits of Lakehaven Water & Sewer District, or has been granted Boundary Review Board approval for extension of water service outside of LWSD's water service area. ❑ b. Annexation or Boundary Review Board approval will be necessary to provide service. S. Water service is subject to: ® a. Payment of connection charges (to be determined by LWSD); ® b. Proof or reservation of easement(s) as required by LWSD; ® c. Other: LWSD DE Agreement (#2 above) must be accepted by LWSD, prior to service connection activation(s). Comments/special conditions: The nearest fire hydrant will be on the Property (number & location TBD by fire marshal). Fire Flow at no less than 20 psi available within the water distribution system is a minimum 2.500 GPM for two (2) hours or more. This flow figure depicts the theoretical performance of the water distribution system under high demand conditions. Fire flow rates greater than this may be accommodated through water distribution system improvements, contact LWSD for additional information. 537 Pressure Zone Est. Meter Elevation(s)-GIS: 395+/- Est. Pressure Range at Meter(s) (psi): 53-61 I hereby certify that the above water system information is true. This certification shall be valid for one (1) year from the date of signature. Name: BRIAN ASBURY Title: DEVELOPMENT ENGINEERING SUPERVISOR Signature:JDate: �0r 1C Celebration Apts wtr.docx (Form Update 4/2/19) Page 1 of 2 Celebration Apts wtr.docx (Form Update 4/2/19) Page 2 of 2 Lakehaven WATER & SEWER DISTRICT Lakehaven Water &Sewer District -Development Engineering Section 31623 - 1st Ave S * PO Box 4249 Federal Way, WA 98063-4249 Telephone: 253-945-1581 or 253-945-1580 * Email: DE@Lakehaven.org This certificate is intended to provide the applicant, land use agencies &/or public health departments with information necessary to evaluate development proposals. Lakehaven Water & Sewer District, at its sole discretion, reserves the right to delay, or deny, sewer service based upon capacity &/or supply limitations in Lakehaven's or Other Purveyor's system facilities. Proposed Land Use: ❑Building Permit -SFR () ®Building Permit -MFR (345) ❑Building Permit -Other ❑ Subdivision () ❑ Short Subdivision () ❑ Binding Site Plan ® Boundary Line Adjustment ❑ Other (specify/describe) Tax Parcel Number(s): 172104-9019 -9028 -9030, -9031, -9033, -9034, -9035, -9046, -9051, -9057. -9059, -9064, -9074, 9090 Site Address: 330XX - 13th Ave S LWSD GIS Grid: 3 SEWER SYSTEM INFORMATION 1. ❑ Sewer service can be provided by service connection to an existing " diameter sewer main that is approximately feet from the site and the sewer system has the capacity to serve the proposed land use. 2. ® Sewer service for the site will require an improvement to LWSD's sanitary sewer system of: ® a. 5+/- feet of 8" diameter sewer main or trunk to reach the site; and/or ® b. The construction of a sanitary sewer collection system on the site; and/or ❑ c. A major portion of LWSD's comprehensive wastewater system plan would need to be implemented and/or constructed; and/or ® d. Other (describe): LWSD Developer Extension (DE) Agreement required. 3. ® a. The existing sewer system is in conformance with LWSD's Comprehensive Wastewater System Plan. ❑ b. The existing sewer system is not in conformance with LWSD's Comprehensive Wastewater System Plan and an Amendment to this Plan will be required. This may cause a delay in issuance of land use approvals or permits. 4. ® a. The proposed site land use is within the corporate limits of Lakehaven Water & Sewer District, or has been granted Boundary Review Board approval for extension of sewer service outside of LWSD's sewer service area. ❑ b. Annexation or Boundary Review Board approval will be necessary to provide service. S. Sewer service is subject to: ® a. Payment of connection charges (to be determined by LWSD); ® b. Proof or reservation of easement(s) as required by LWSD; ® c. Other: LWSD DE Agreement (#2 above) must be accepted by LWSD, prior to service connection activation(s). Comments/special conditions: I hereby certify that the above sewer system information is true. This certification shall be valid for one (1) year from the date of signature. Name: BRIAN ASBURY Title: DEVELOPMENT ENGINEERING SUPERVISOR Signature: Date: J5-� Celebration Apts swr.docx (Form Update 4/2/19) Page 1 of 2 -10 Ex. Bldg. Area to Remain: N/A sf New Bldg. Area Proposed: 593,700 sf (total, 2 MFR bldgs) + Rec. Bldg. SEWER SYSTEM INFORMATION 1. ❑ Sewer service can be provided by service connection to an existing " diameter sewer main that is approximately feet from the site and the sewer system has the capacity to serve the proposed land use. 2. ® Sewer service for the site will require an improvement to LWSD's sanitary sewer system of: ® a. 5+/- feet of 8" diameter sewer main or trunk to reach the site; and/or ® b. The construction of a sanitary sewer collection system on the site; and/or ❑ c. A major portion of LWSD's comprehensive wastewater system plan would need to be implemented and/or constructed; and/or ® d. Other (describe): LWSD Developer Extension (DE) Agreement required. 3. ® a. The existing sewer system is in conformance with LWSD's Comprehensive Wastewater System Plan. ❑ b. The existing sewer system is not in conformance with LWSD's Comprehensive Wastewater System Plan and an Amendment to this Plan will be required. This may cause a delay in issuance of land use approvals or permits. 4. ® a. The proposed site land use is within the corporate limits of Lakehaven Water & Sewer District, or has been granted Boundary Review Board approval for extension of sewer service outside of LWSD's sewer service area. ❑ b. Annexation or Boundary Review Board approval will be necessary to provide service. S. Sewer service is subject to: ® a. Payment of connection charges (to be determined by LWSD); ® b. Proof or reservation of easement(s) as required by LWSD; ® c. Other: LWSD DE Agreement (#2 above) must be accepted by LWSD, prior to service connection activation(s). Comments/special conditions: I hereby certify that the above sewer system information is true. This certification shall be valid for one (1) year from the date of signature. Name: BRIAN ASBURY Title: DEVELOPMENT ENGINEERING SUPERVISOR Signature: Date: J5-� Celebration Apts swr.docx (Form Update 4/2/19) Page 1 of 2 Celebration Apts swr.docx (Form Update 4/2/19) Page 2 of 2 Lakehaven WATER & SEWER DISTRICT Hydraulic Model Fire Flow Estimate Request/Reporting Form NOTES: Lakehaven's adopted level of service goals for fire flow rates are 1000 gpm within single family residential areas (including duplexes) and 2500 gpm for multi -family, commercial, industrial areas. Model results depict the theoretical performance of the water system under high demand conditions and are not guaranteed to represent actual system performance. A design professional should be consulted for site specific design purposes. The calculated fire flow capacity in the above table is based on a currently available residual system pressure of 20 psi at the location modeled. The model indicates that Lakehaven's standard maximum allowable velocity of 10 ft/s is exceeded at a fire flow rate above 1600 gpm. Fire flow capacities greater than 1600 gpm may be accommodated through water system improvements. 052819FF 360 - 3 3 0 0 5 15th AV2 S (Form Update 1/6!17) Requested By: Date: DaNkm Zern 5/22/19 Location to be Modeled: Existing Hydrant near Parcel # 1721049046 Results By: John Bowmall;: Lakehaven'/a Section Grid: J/10 intersection: S 330th St & 15th Ave S Add. Description: See attached map Pressure Zone: 538 Flow (gpm) Static 43 0 NOTES: Lakehaven's adopted level of service goals for fire flow rates are 1000 gpm within single family residential areas (including duplexes) and 2500 gpm for multi -family, commercial, industrial areas. Model results depict the theoretical performance of the water system under high demand conditions and are not guaranteed to represent actual system performance. A design professional should be consulted for site specific design purposes. The calculated fire flow capacity in the above table is based on a currently available residual system pressure of 20 psi at the location modeled. The model indicates that Lakehaven's standard maximum allowable velocity of 10 ft/s is exceeded at a fire flow rate above 1600 gpm. Fire flow capacities greater than 1600 gpm may be accommodated through water system improvements. 052819FF 360 - 3 3 0 0 5 15th AV2 S (Form Update 1/6!17) Results By: John Bowmall;: Date: 5/28/19 Model Run No.: Master Water System Model 2007.net FF #360 Condition Pressure (psi) Flow (gpm) Static 43 0 Fire Flow 20 3500 NOTES: Lakehaven's adopted level of service goals for fire flow rates are 1000 gpm within single family residential areas (including duplexes) and 2500 gpm for multi -family, commercial, industrial areas. Model results depict the theoretical performance of the water system under high demand conditions and are not guaranteed to represent actual system performance. A design professional should be consulted for site specific design purposes. The calculated fire flow capacity in the above table is based on a currently available residual system pressure of 20 psi at the location modeled. The model indicates that Lakehaven's standard maximum allowable velocity of 10 ft/s is exceeded at a fire flow rate above 1600 gpm. Fire flow capacities greater than 1600 gpm may be accommodated through water system improvements. 052819FF 360 - 3 3 0 0 5 15th AV2 S (Form Update 1/6!17) W Z ©w co $g� °ii _�Y 7 a s § 30 N019NIHSVM A VAi A.F 9PO6 b01 ZLI 79021 Vd NV7d 311S 7b771d33NOD !VO/1b2fS3733 A1171191 S V33 ri 4 I I IF IF IF I IL I q i CJ J II l 1 ii li I I I 1 t 1 1 I i I I I I I tl l F b IF srlavK3\s.alerxr\4#wl� ,a�a�a venni - �r9�11 lut'[0 M --i I IF IF IF I IL I q i IF srlavK3\s.alerxr\4#wl� ,a�a�a venni - �r9�11 lut'[0 M Lakehaven WATER & SEWER DISTRICT To: Lakehauen Water &Sewer District Attn: Development Engineering 31623 - 1st Ave S PO Box 4249 Federal Way WA 98063-4249 REQUEST FOR WATER HYDRAULIC MODEL ANALYSIS REPORT FOR LAKEHAVEN USE ONLY Fee: 230.00 Paid Date: 512=1 1 in Receipt No. 0 6011 I would like to request a water hydraulic model (aka fire flow') analysis &report for the following location: Parcel Number 1721049046 Site Address 33005 15th Ave S. Federal Way 98003 * * INCLUDE A MAP OF, OR INDICATE, HYDRANTS) DESIRED TO BE MODELED * * Jake Drake Name of Authorized Representative/Contact Permitting Technician Title/Position 425-250-7232 Contact Telephone Number jdrake@thebluelinegroup.com Contact Email 05/20/2019 Date Hydra Model RequestApp-2019.docx (Form Update 7/13/18) r' N SEC 1 77 TWP Z 7 N, RGE 4E7 W.M. \\J \\\\\\ \\\ \\ \\\ \\ITT. I I IIII { \\\ \ \\\ \\ \v� I 1 III I fill I 'ti \ \ \\\ �/ \\\ TIN, it, III! I NII II I IH h l Z l'if .ITT I` ITT Ila '00p tot x ITT tot 6 00 am -- - -- ll to RE CREAT10N (25' HT) 1`411 j / T 111 Y' 111I / /� / vl so' 1 mal IT to to If v r� 1 I i I — - — I: Is as of 2 pIt. . / / 4 I /lit ;// too _ IIto — — IITTt I yW��� — 7 = — �-1 IN 44 BUILDING�(, REs(65 NT(A,l,f1FNIT8 I / / v f65' "Ti ! / of too 6 / I �--T-W — J ,. — l I Ir I 1 _ r II L---� — �r—� 7 uIr it II I L---------- / r / s I I; UEOERAL O r PUBLICSCHOOLS SERW E - I I xUlwnoNsmacEs %/° I IT Z U ¢ L d,< I 11 � n- -----7 cJ l llI er l - -� l I I r--- j--------� IT I j I II I I I I I r j; ii Ci I i —iJ F y I Jill I 1 I I I I I I ( I I I I I IIII JI III C L------� �> II — — — — — -- — i 1 I J I I I eG I I IIII I I I L, ,�o. I I r------- I I I If111 I I I I II U----- --� F=.J L =LT l I 11 IIII I u u V� H 1 I r� ,:I I i U III I I I I I II I I nn rill) �—'-i L J L JJ S 33DTH .SST _cT7_ss-- Islas ,G G III I ` Clot 6 I Qra + I ' 5 1n24oaG I ,y G 3joW p1. y4 — j rorLGr — — — dd ho'�t�BL!lLO�/NG B ' a 235 RESIDENTIAL UNITS i .- f65 HT1 NINO 7.J U U U U L it � II I n r I El L --J L I L_ --J —� L --- r----- r---1 I I U bG U LJ k�a ®2019 INE OLUEUNE CROUP i TOT LOT 60' 0 30 60 120 i!i I y! II; Ijh II ij I I I G I.I o:G I I L-------- I r— L-- J I J IIII � ISI Ilii � i IIII I I I I11 � I I�JI 3 T— LJ II J I G I '�o, G jp? IL ----J I ISI 1 5TH AVE S (NOT TO SCALEJ BLU 'E LIN JS CENTRAL WAY, W11E100. KTRIQNN(0,WA 99033 P-<}52T9.W9I F:4Li2I$N4 3 WWM.IHEBLUELlwmWpL SCALE: AS NOTID PROJECT MANAGER: C1fM5ilA°HEA H AlUER, PE PROJECT ENGINEER: �A'.iV L KOFPF[YT; PE DESIGNER: OOM/NgJE GABALOpV ISSUf DA7E.• N 2 0 N W C m 0 O 2 2 '0 V Z asto ® J r 3 ` WVast O JQ m almost Ul N NVast Q Q J W W � V, aLd� 0 1 LqQ U JO8 NUMSER: 19— 719 SHEET NAME: SP -D 1 sFlr 1 CIF—3 SEC 17, '1 2 1 N, RGE 4E, W.M. III i ---- I I APPLICANT WISHES TO I DISCUSS U77LI27Nc \ ! CITY PROPERTY TO 1 11 /i' / / / CONNECT OPEN SPACE iso TO CELEBRATION PARK I11/�IF ot ' ilj i� iIi 1 I I --- i/ : I II I III I I I N / �:. I I I I I I04 *60 /7a -- -- --I IF 111 1 r—� i 1 --------- SCALE: 1" = 30'I i IF v I I'F/� ' 1 I II I i I --- — 0 15 30 6D1 o //11 / P / 1 1REERE7ENTION OPEN 1 I I L—__-_-__- - --- -----_-----_J 1 - ;: SPACE AREA e 1 1 tl 3 I r--- -_-__----_---- 1 J L 0 // 1 ' III it I I I I --� I 4( I -- ,/ ' 1111'1'',---- , I / �� // / I JS ROW 11'11 1111IF1 It / Q / I I I 60' RECREATION/ I IFF , // o m BUFFER CLUBHOUSE / 5 t ! 1111, 1 I I I I i I I I I I / , O/ V a .)IF aha 111 1I I I I I I I I I I l IF lljll I I I I I I I I I J 1 I r� 1 1 < / // QP ' FIFO,sle j 1llt I U U �0y y �1 111 U I )TOOL = 1 1 EX 12' ,tWATER MAIN I I ---_ / yI 1 t :. ` 1 wIII Fl, ; w W g ; \Existing Hydrant foj _ q' �� ` i TER MAN I (� I Iii ydraulifVECT TO EX lo¢eling ' Lam= _J L— L� Lij6'S7DE SEWER X100.6 \ �1 \-� --- `_. 50 -------- / --_ - SD - SD-i7_-sD --- --- - _ W - _ TOB MAIN _ EX 8" WATER M�1/N - _ W _ - - -. - - - - - - - - - - - / 11'- -W -W-_ W _--W_ --y/ ---'S �- — 1 ---I— ---- —li-- -- � ----_ ----- _—' — N�.�� S 330TH ST r y y wDETENR i*IF, i \ y STORMWATER -FFF VAULT IF w ' - EXTEND B' SEWER � EX B WATER MAID`-&,� W — 1 MAN IN TJ7H PL S I I -~ Aja- SD— • ` 'jam\ .- W it, ;•rb.- ---- y A _ -,- .�_ A _ - _ - _ _ _ _ •, N CONNECT Ta EX I t i T JJ ROW ..:'... �I� I __..... FIRE HPDR NT WATER MAIN -1t` -_.... I�_I j I �,'- EXISPNG WETLAND IIF _ '., :`r IFF v _ - -- r I .II 'i' i I FIRE HYDRANT _ _ : ____ I ! Ii FIRE HYDRANT 1 GARAGE ENTRY £L' y w w t' II 4I i I.-. 1?It 'WATER MAIN rC ! .' s ,.. IN LITH PLS _ It W i 1 -- — -- — / I IF IF am Fz FIFO— _—_ ___F. I — - — _ I FIFO w FIJI 1loom I, I w I I IB W 7 0 6 I: I e "' . I w AI IF W w '10I — ------- / / Lul 14 „ yFIFIF --FootI II IF - W — -- lFIFIF III — 1 ILL I 6° y _ 7,p IF / l! .est .'I Z I y / /,/'///i /�/1 �'_ _- j� I FIRE HYDRANT �� 'V II i B WATER MAIN 1 '// STOFMWATER UALITYLOOP FIRE HYDRANT / / / /- ii TREATMENT FACILITY BUS/AROA ND / II I I J I 1 '/ I I w... DETENTION VAULT i 4 I I I IQ h 70 WETLAND BUFFER PYRE HYDRANT 1 l Ii I % GARAGE 8UlLOING A / li 1 ,� I I 1I PRD ENTRY rro wcsroeNnac uNrrs j 1. - k _ �I c rss r,n j I I r II — /_?`L = 1_ ii !.I I, - I I I EX4"WATER MAIN BUILDING A I A I I TO !iE REPLACED /�/// SDE SEWER/ o It - --- ___ / ENTRYI m! ItE _ _ _ __ �._ �' / / ' I I CONNECT BUILDING I / I I I I I MAIN N 15TH AYES CE EX 4 WA R __ u, -- TH 8 0/ WATER c — - EX MAIN zzs a uHrrs `, — / I� :I '' s BW� D/NG B .q HER C -- ----------I II �I TIFF sa`n �at IF go Ft --- — — 1�c 1 --Il 1 yamIF a" 'IF LI ` l JB1.7 - - - - -II IF r_ w j �j ----- SOME, U / RE HYDRANT _ / - - i I 00 - / 1j. `1 FIRE HYDRANT -- _- I - -- -- - TIRE HYDRANT w FIRE HYDRANT I -- I I j � o i----------------- CONNECT TO FX -.: i� i� TOT LOT 1 I - m °i / SEWER MANHOLE I - _ ` _ I: IFFI! Till `a MATCHLINE - SEE SHEET SP -OZ E w (I 774E BLUELINE CROUP BLUELINE 25 CEMRAL WAY, SI)ITEA00. K81KI.w�Io A 58033 P:423216.4051 F. 425.216.4052 WNW.THEBLUELINEO OOPI SCALE. - AS N07ID PROJECT MANAGER: CI1R15T17PHFJ7 H MILLET; PE PROJECT ENGINEER: :K1N L KOIPPGEh; PE DESIGNER: DOM/NOUE CABALDON ISSUE DA Mo J%/�20l9 N 2 O N Lu r } 0 Q D 0 2 2 2 2� Q z 1 EL O Lu IFF Q W � � Q W Ll 14 k o Uuj Q LL V O U JOH NUMBER: T 9— 2 7 9 SHEET NAME: S�JP-O Z BHT SEC 1 77 TWP 2 T N, R13E 4E, W.M. MATCHL/NE -SEE SHEET SP -01 _ BUILDING B ZZ5 MCSIDkNr "M(r 77777777 f L r Y 1 I I -_ , GARAGE �,;�� •� J ENTRY At i3v¢�1 TOT LOT N SCALE: 1" = 30' 0 16 30 60 III I ili I ili I I'' I ili I I.I I 1 I 111 11i I I' I 1�1 1 I j I 11r 1 i I !1{ I I I PGtr li I I i III I I t it i t I I I cc ool I' a3B5T5 I 1 I I I CONNECT NEW 8' WATER MAIN TO I EX B' WATER MAIN III I I I EX H' WATER MAW TO REMAIN 311 I I I BLUELINE 25 CENTRAL WAY, 9UITE460, KiRICLW0, WA WM P:425.216.466I F:426.216.AIM W 1NN.TNEBLl1ELINEOROIIP.COM SCALE. AS NOIID PROJECT MANAGER: CHRISTOPHER H M/LL£R, PE PROJECT ENGINEER.• ,A7/J L KOEPFGEN, PE DESIGNER: Omll/NpIE CABALDON ISSUE DA 1F• --� 3/7/2019 ul 2 O N W m 0 0 i 2 2 2 Z EL m � t a Q 4.1 s' a� b� W a � 00 s� N u N o k�4 02019 THE BLUMNE GROUP IL Lu W W LdQ �za4 oLLM U JOB NU MSER: 19-019 SHEET NAME: S P -O 3 SHT 3 OF 3