Towne Place Hotel 2021049044 jointLakehaven
WATER & SEWER DISTRICT
Lakehauen Water &Sewer District —Development Engineering Section
31623 — 1st Ave S * PO Box 4249 Federal Way, WA 98063-4249
Email: DE@Lakehaven.org * Telephone: 253-945-1581 or 253-945-1580
This certificate is intended to provide the applicant, land use agencies &/or public health departments with
information necessary to evaluate development proposals. Lakehaven Water & Sewer District, at its sole
discretion, reserves the right to delay, or deny, water service based upon capacity &/or supply limitations
in Lakehaven's or Other Purveyor's system facilities.
Proposed Land Use: ❑ Building Permit-SFR () ❑ Building Permit-MFR () ® Building Permit -Other
❑ Subdivision () ❑ Short Subdivision () ❑ Binding Site Plan
❑ Boundary Line Adjustment ® Other (specify/describe) Hotel
Tax
Parcel Number(s): 2021049044
Site
Address: 34839 Pacific Hwy S LWSD GIS Grid: J-12
Ex.
Bldg. Area to Remain: N/A sf
New
Bldg. Area Proposed: 53,504 sf
WATER SYSTEM INFORMATION
1. ® Water service can be provided by service connection to an existing 8" diameter water main that is approximately 5+ - feet
from the site or by service connection to an existing 16" diameter water main that is approximately 25+ - feet from the
site.
2. ® If additional &/or onsite fire hydrant(s) required, water service for the site will require an improvement to LWSD's water
distribution system of:
® a. 5+/- feet of 8" &/or 12' diameter water main to reach the site; and/or
® b. The construction of a water distribution system on the site; and/or
❑ c. A major portion of LWSD's comprehensive water system plan would need to be implemented and/or
constructed; and/or
® d. Other (describe): LWSD Developer Extension (DE) Agreement required.
3. ® a. The existing water system is in conformance with LWSD's Comprehensive Water System Plan.
❑ b. The existing water system is not in conformance with LWSD's Comprehensive Water System Plan and an
Amendment to this Plan will be required. This may cause a delay in issuance of land use approvals or permits.
4. ® a. The subject property is within the corporate limits of Lakehaven Water & Sewer District, or has been granted
Boundary Review Board approval for extension of water service outside of LWSD's water service area.
❑ b. Annexation or Boundary Review Board approval will be necessary to provide service.
S. Water service is subject to:
® a. Payment of connection charges (to be determined by LWSD);
® b. Proof or reservation of easement(s) as required by LWSD;
® c. Other: Water Service Connection applications required. If applicable, LWSD DE Agreement (#2 above) project must
be accepted by LWSD, prior to service connection activation.
Comments/special
conditions: Service
pressure(s)
greater than
80 psi
indicated,
Pressure
Reducing
Valve(s)
indicated,
contact
local
building official for
reouirements &/or
additional
information.
The nearest fire hydrant is approximately 5+ -feet from the Property. (as marked on map on the back of this page).
Fire Flow at no less than 20 psi available within the water distribution system is a minimum 2,500 GPM for two (2) hours or more.
This flow figure depicts the theoretical performance of the water distribution system under high demand conditions. Fire flow rates
greater than this may be accommodated through water distribution system improvements, contact LWSD for additional information.
538 Pressure Zone Est. Meter Elevations)-GIS: 260+/- Est. Pressure Range at Meter(s) (psi): 111-120
I hereby certify that the above water system information is true. This certification shall be valid for one (1) year from the date of
signature.
Name: BRIAN ASBURY Title: DEVELOPMENT ENGINEERING SUPERVISOR
Signature: Date:
2021049044 wtr.docx (Form Update 4/2/19) Page 1 of 2
2021049044 wtr.docx (Form Update 4/2/19) Page 2 of 2
Lakehaven
WATER & SEWER DISTRICT
Lakehaven Water &Sewer District —Development Engineering Section
31623 — 1st Ave S * PO Box 4249 Federal Way, WA 98063-4249
Telephone: 253-945-1581 or 253-945-1580 * Email: DE@Lakehaven.org
This certificate is intended to provide the applicant, land use agencies &/or public health departments with
information necessary to evaluate development proposals. Lakehaven Water & Sewer District, at its sole
discretion, reserves the right to delay, or deny, sewer service based upon capacity &/or supply limitations
in Lakehaven's or Other Purveyor's system facilities.
Proposed Land Use: ❑Building Permit-SFR () ❑Building Permit-MFR () ®Building Permit -Other
❑ Subdivision () ❑ Short Subdivision () ❑ Binding Site Plan
❑ Boundary Line Adjustment ® Other (specify/describe) Hotel
Tax Parcel Number(s): 2021049044 Site Address: 34839 Pacific Hwy S LWSD GIS Grid: J-12
Ex. Bldg. Area to Remain: N/A sf
New Bldg. Area Proposed: 53,504 sf
SEWER SYSTEM INFORMATION
1. ® Sewer service can be provided by service connection to an existing 12" diameter sewer main that is on the site and the
sewer system has the capacity to serve the proposed land use.
2. ❑ Sewer service for the site will require an improvement to LWSD's sanitary sewer system of:
❑ a. feet of " diameter sewer main or trunk to reach the site; and/or
❑ b. The construction of a sanitary sewer collection system on the site; and/or
❑ c. A major portion of LWSD's comprehensive wastewater system plan would need to be implemented and/or
constructed; and/or
❑ d. Other (describe):
3. ® a. The existing sewer system is in conformance with LWSD's Comprehensive Wastewater System Plan.
❑ b. The existing sewer system is not in conformance with LWSD's Comprehensive Wastewater System Plan and an
Amendment to this Plan will be required. This may cause a delay in issuance of land use approvals or permits.
4. ® a. The proposed site land use is within the corporate limits of Lakehaven Water & Sewer District, or has been granted
Boundary Review Board approval for extension of sewer service outside of LWSD's sewer service area.
❑ b. Annexation or Boundary Review Board approval will be necessary to provide service.
S. Sewer service is subject to:
® a. Payment of connection charges (to be determined by LWSD);
® b, Proof or reservation of easement(s) as required by LWSD;
® c. Other: Sewer Service Connection Permit required.
Comments/special conditions:
I hereby certify that the above sewer system information is true. This certification shall be valid for one (1) year from the date of
signature.
Name: BRIAN ASBURY Title: DEVELOPMENT ENGINEERING SUPERVISOR
Signature: Mot Date: r
2021049044 swr.docx (Form Update 4/2/19) Page 1 of 2