21-102066-UP-Water Availability-2021-05-24-V1926480-0060-0070 wtr.docx (Form Update 3/13/20)Page 1 of 2
WATER CERTIFICATE OF AVAILABILITY
Lakehaven Water & Sewer District – Development Engineering Section
31623 – 1st Ave S PO Box 4249 Federal Way, WA 98063-4249
Email: DE@Lakehaven.org Telephone: 253-945-1581 or 253-945-1580
This certificate is intended to provide the applicant, land use agencies &/or public health departments with
information necessary to evaluate development proposals. Lakehaven Water & Sewer District, at its sole
discretion, reserves the right to delay, or deny, water service based upon capacity &/or supply limitations
in Lakehaven’s or Other Purveyor’s system facilities.
Proposed Land Use: Building Permit-SFR () Building Permit-MFR () Building Permit-Other
Subdivision () Short Subdivision () Binding Site Plan
Boundary Line Adjustment Other (specify/describe) SEPA, Process III Land Use Approval
Tax Parcel Number(s): 926480-0060,-0070 Site Address: 34520 9
th Avenue S LWSD GIS Grid: J-12
Ex. Bldg. Area to Remain: 0 sf New Bldg. Area Proposed: 55,000 sf
WATER SYSTEM INFORMATION
1.Water service can be provided by service connection to an existing 12” diameter water main that is approximately 15 feet
from the site.
2.Water service for the site will require an improvement to LWSD’s water distribution system of:
a. 25 feet of 12” diameter water main to reach the site; and/or
b. The construction of a water distribution system on the site;
c. A major portion of LWSD’s comprehensive water system plan would need to be implemented and/or
constructed; and/or
d. Other (describe): New water main and Developer Extension agreement required with any new hydrants onsite.
3.a. The existing water system is in conformance with LWSD’s Comprehensive Water System Plan.
b. The existing water system is not in conformance with LWSD’s Comprehensive Water System Plan and an
Amendment to this Plan will be required. This may cause a delay in issuance of land use approvals or permits.
4.a. The subject property is within the corporate limits of Lakehaven Water & Sewer District, or has been granted
Boundary Review Board approval for extension of water service outside of LWSD’s water service area.
b. Annexation or Boundary Review Board approval will be necessary to provide service.
5.Water service is subject to:
a. Payment of connection charges (to be determined by LWSD);
b. Proof or reservation of easement(s) as required by LWSD;
c. Other: Water Service Connection Application required.
Comments/special conditions: .
The nearest fire hydrant is approximately 20+/- feet from the Property (as marked on map on the back of this page).
System hydraulic model results (FF #419), at no less than 20 psi, indicate that LWSD’s standard maximum allowable liquid velocity
of 10 ft/s is exceeded at a fire flow rate above 11,600 GPM for two (2) hours or more. This flow figure depicts the theoretical
performance of the water distribution system under high demand conditions. Fire flow rates greater than this may be accommodated
through water distribution system improvements, contact LWSD for additional information.
538 Pressure Zone Est. Meter Elevation(s)-GIS: High 290+/-, Low 250+/- Est. Pressure Range at Meter(s) (psi): 107-116
I hereby certify that the above water system information is true. This certification shall be valid for one (1) year from the date of
signature.
Name: BILL NELSON Title: ENGINEERING TECHNICIAN III
Signature: Bill Nelson (Signed Electronically)Date: 5/24/21
926480-0060-0070 wtr.docx (Form Update 3/13/20)Page 2 of 2