21-100247-Certificate of Water Availability-02-19-2021-V1,. - Lakehaven
WATER & SEWER DISTRICT
Lakehaven Water & Sewer District - Development Engineering Section
31623 - 1st Ave S 0 PO Box 4249 * Federal Way, WA 98063-4249
Email: DE@Lakehaven.org * Telephone: 253-945-1581 or 253-945-1580
This certificate is intended to provide the applicant, land use agencies &/or public health departments with
information necessary to evaluate development proposals. Lakehaven Water & Sewer District, at its sole
discretion, reserves the right to delay, or deny, water service based upon capacity &/or supply limitations
in Lakehaven's or Other Purveyor's system facilities.
Proposed Land Use: ® Building Permit-SFR (ADU) ❑ Building Permit-MFR () ❑ Building Permit -Other
❑ Subdivision () ❑ Short Subdivision () ❑ Binding Site Plan
❑ Boundary Line Adjustment ❑ Other (specify/describe)
211121 JVa
Tax Parcel Number(s): 0821049178 Site Address: 31106 - 6th Ave S LWSD GIS Grid: I-07
Ex. Bldg. Area to Remain: 2,558 sf New Bldg. Area Proposed: 795 sf (additional)
WATER SYSTEM INFORMATION
1. ® Water service can be provided by service connection to an existing 10' diameter water main that is on the site.
2. ❑ Water service for the site will require an improvement to LWSD's water distribution system of:
❑ a. feet of " diameter water main to reach the site; and/or
❑ b. The construction of a water distribution system on the site; and/or
❑ c. A major portion of LWSD's comprehensive water system plan would need to be implemented and/or
constructed; and/or
❑ d. Other (describe):
3. ® a. The existing water system is in conformance with LWSD's Comprehensive Water System Plan.
❑ b. The existing water system is not in conformance with LWSD's Comprehensive Water System Plan and an
Amendment to this Plan will be required. This may cause a delay in issuance of land use approvals or permits.
4. ® a. The subject property is within the corporate limits of Lakehaven Water & Sewer District, or has been granted
Boundary Review Board approval for extension of water service outside of LWSD's water service area.
❑ b. Annexation or Boundary Review Board approval will be necessary to provide service.
5. Water service is subject to:
® a. Payment of connection charges (to be determined by LWSD, for any new/modified service connection);
❑ b. Proof or reservation of easement(s) as required by LWSD;
® c. Other: The existing meter should be evaluated under UPC & LWSD standards, to determine if it's adequate for the
proposed use. LWSD Service Connection Application reouire, for any new/modified service connection.
Comments/special conditions:
The nearest fire hydrant is approximately 285+/-+/- feet from the Property (as marked on map on the back of this page).
Fire Flow at no less than 20 psi available within the water distribution system is a minimum 1,000 GPM for two (2) hours or more.
This flow figure depicts the theoretical performance of the water distribution system under high demand conditions. Fire flow rates
greater than this may be accommodated through water distribution system improvements, contact LWSD for additional information.
536 Pressure Zone Est. Meter Elevation(s)-GIS: 440+/- Est. Pressure Range at Meter(s) (psi): 33-42
I hereby certify that the above water system information is true. This certification shall be valid for one (1) year from the date of
signature.
Name: BRIAN ASBURY Title: DEVELOPMENT ENGINEERING SUPERVISOR
Signature: Xticw ffi#yW l e-s 1gd/ Date: 1128121
0821049178 wtr swr.docx (Form Update 3/13/20) Page 1 of 4
2413 00
.f
08210,
311
Ex.
H ydr.
2413300030
31112
2413300020
31116
2413300010
31120
i
io
26" 26" 364, 22" ;c
ID" Q
,r CO in
S 312YN S 7-
OTE: lakehaven Water and Sewer
District neither warrants nor guarantees
he accuracy of any facility information
provided. Facility locations and conditions
are subject tofieId verification.
[R
5547600090 II 5547600160
809 I
- 5547600180
0821049190
31104
...� Ex. W1rSvc 36797
V Meter
N
0821049178
31106
to
0821049204
31110
0821040203
3111e
Y6'
832
082104923�1
e2e
Water Certificate of Availability
Parcel 0821049178
o 100
Feet 1/28/21
0821049178 wtr swr.docx (Form Update 3/13/20)