The City has completed an administrative review of the proposal to install an emergency generator on an
existing concrete slab inside the existing fenced, compound. The proposal includes the installation of a
Sprint ATS, and a Sprint Conduit as well as the proposed diesel generator. The Process I application is
hereby approved by the City's Department of Community Development Services.
Due to the nature of the proposal, a building permit will not be required. However, an electrical permit will
be required for the installation of the generator, issued by the City's Building Division prior to beginning
any work.
This Process I decision shall not waive compliance with future City of Federal Way codes, policies, and
standards relating to this site. The effective date of this decision is July 14, 2007 (three days from
issuance). Pursuant to Federal Way City Code (FWCC) Section 22-356, any person who received notice
of the administrative decision may appeal this decision to the Federal Way Hearing Examiner by July 30,
2007 (14 days after issuance). No work on the proposal can commence until the end of the appeal period.
However, in that you are the only party of record, you may waive your right to appeal this decision. If you
wish to waive your right to appeal, you must do so in writing or by email, to the attention of Laura Kim,
Associate Planner, laura.kim@cityoffederalway.com.
Work may begin on the proposal once the City verifies that an appeal waiver has been received and a
building permit has been issued by the City. If you have any questions regarding this letter, please contact
Laura Kim at laura.kim@cityoffederalway.com or 253-835-2641.
Sincerely,
-]� 11�
Kathy McClung
Director of Community Development
enc: Stamped Approved Plans
Doc 1 D 41510
s
Together with NEXTEL
N)�
ENCHANTED PARKWAY
PROJECT INFORMATION
PROJECT DESCRIPTION:
SPRINT-NEXTEL PROPOSES TO AMEND AN EXISTING UNSTAFFED
TELECOMMUNICATIONS FACILITY WITH THE ADDITION OF A 40KW
DIESEL GENERATOR AND FUEL TANK MOUNTED ON EXISTING
CONCRETE PAD
SITE ADDRESS:
1741 S 356TH STREET
FEDERAL WAY, WA 98003
PROPERTY OWNER:
LLOYD RUSSELL
174 S 356TH ST
FEDERAL WAY, WA 98003
APPLICANT:
SPRINT/NEXTEL
10545 WILLOWS RD NE
SUITE 100
REDMOND, WA 98052
PROJECT CONTACT:
MATT ENGLESBY
PHONE: (206) 310-2240
EMAIL- MENGLESI3Y@PTSWA.COM
LATITUDE:
47' 16' 57.16" N
LONGITUDE:
122' 18' 39.63" W
LAT/LONG TYPE:
NAD 83
ELEVATION:
0' AMSL
PARCEL NUMBER:
282104-9178-06
CURRENT USE:
TELECOMMUNICATIONS FACILITY
PROPOSED USE:
TELECOMMUNICATIONS FACILITY
POWER:
PSE
PHONE: 1-888-225-5773
TELCO:
QWEST
PHONE:
JURISDICTION:
CITY OF FEDERAL WAY
ZONING:
CB
APPLICABLE CODE:
2003 IBC
CONSTRUCTION TYPE:
II-B
OCCUPANCY TYPE:
UNOCCUPIED
PROJECT AREA:
APPROX. 40 S.F.
VALUATION:
$10,000
VICINTY MAP
WA0456
_ FedeYaflAlay
-fl s 350th_ St
T61
g 351st st = .
f $ 351ni�5t 1 sAt 1a2A
SITE
4Lp
ro
N
to
99
4 : a
�t
DRIVING DIRECTION
s 3Lkt st
Enchamad
aide
s
S-351-M SF
ts am pr
U3
a oa
m - UL-
N -
DEPART: 10545 WILLOWS RD NE, REDMOND, WA 98052
TURN RIGHT ONTO SR-908
TURN OFF ONTO RAMP TOWARDS 1-405 / RENTON
CONTINUE ON SR-518
TURN OFF ONTO RAMP TOWARDS 1-5 / PORTLAND
AT 1-5 EXIT 142E TURN OFF ONTO RAMP TOWARDS WA-161 S / PUYALLUP
MERGE ONTO SR-18
TURN LEFT ONTO SR-161 (ENCHANTED PKWY S)
TURN LEFT ONTO S 356TH ST
ARRIVE: 1741 S 356TH ST, FEDERAL WAY, WA 98003
DRAWING INDEX
CURRENT WtM
CONSTRUCTION DRAWINGS
AITIMA S. DATE:
SPRINT/NEXTEL:
LANDLORD:
CONST:
S/A: I
R.F.:
ZONING:
A&E:
T-1 TITLE SHEET AND GENERAL INFORMATION
G-1 GENERAL NOTES
A-1 SITE PLAN
A-2 ENLARGED SITE PLAN
A-3 GENERATOR AND ATS DETAILS
E-1 GROUNDING PLAN AND ELECTRICAL NOTES
E-2 MO POWER DIESEL GENERATOR AND ALARM
E-3 ATS CABLE SCHEDULE AND ATS ALARM iNN
E-4 ATS ALARM WIRING-CDMA ROVE D
E-5 ELECTRICAL DETAILS
PLANNING
City :of. Faders! Way
Dept. of Community Dewelc
Penft 0-+—[l /+7�0 3 - OF
PROJECT TEAM
DESIGN TEAM
THOMAS R. HOLLAND. ALA
PACIFIC TELECOM SERVICES, LLC
568 FIRST AVE S. SUITE 650
SEATTLE, WA 98104-2804
CONTACT: STEVE ISHIHARA
PHONE: (206) 342-9000 EXT. 412
FAX: (206) 903-8513
EMAIL: SISHIHARA®PTSWA.COM
ZONING CONTACT
PACIFIC TELECOM SERVICES, LLC
568 FIRST AVE S, SUITE 650
SEATTLE, WA 98104-2804
CONTACT: MATT ENGLESBY
PHONE: (206) 342-6391
E-MAIL: MENGLESBY®PTSWA.COM
PRIME CONTACT
SPRINT/NEXTEL
10545 WILLOWS RD NE
SUITE 100
REDMOND, WA 98052
CONTACT: BRYAN ADAMS
OFFICE: (425) 278-2109
PROJECT MANAGER RECEIVE[
PACIFIC TELECOM SERVICES, LLC
568 FIRST AVE S, SUITE 650
SEATTLE, WA 98104-2804 JUN 8 �OQ7
CONTACT: LORI CHASE
PHONE: (206) 342pj�-�63yy85
EMAIL: LCHASE f It�I ]F FEDERAL
BUILDING DEPT.
*rint- )00
Together with NEXTEL
PACIFIC TELECOM SERVICES,
LLC
Swft* WA. 66104
R—: (2N) 349i Fm (206) 909-6516
4072
THOMAS R. HOLLAND
STATE OF WASHINGTON '
1 �
Q
FI ~
U
N Vl
O N
m
L-2
Z
V)
O
U O
IY V
U. O
0 p
w
� �
is
S o
Ty-1
TITLE SHEET AND
GENERAL INFORMATION
JOB #
DRAWING #
WA04.96
T-1
REVISION 1 0
STRUCTURAL STEEL NOTES
1. ALL STEEL WORK SHALL BE PAINTED IN ACCORDANCE
WITH THE PROJECT SPECIFICATIONS AND IN ACCORDANCE
WITH ASTM A36 UNLESS OTHERWISE NOTED.
2. ALL WELDING SHALL BE PERFORMED USING E70XX
ELECTRODES AND WELDING SHALL CONFORM TO AISC AND
AWS D1.1. WHERE FILLET WELD SIZES ARE NOT SHOWN,
PROVIDE THE MINIMUM SIZE PER TABLE J2.4 IN THE AISC
"MANUAL OF STEEL CONSTRUCTION". PAINTED SURFACES
SHALL BE TOUCHED UP.
3. BOLTED CONNECTIONS SHALL BE ASTM A325 BEARING
TYPE (3/4"0) CONNECTIONS AND SHALL HAVE MINIMUM
OF TWO BOLTS UNLESS NOTED OTHERWISE.
4. NON-STRUCTURAL CONNECTIONS FOR STEEL GRATING MAY
USE 5/8" DIA. ASTM A 307 BOLTS UNLESS NOTED
OTHERWISE.
5. INSTALLATION OF CONCRETE EXPANSION/WEDGE ANCHOR,
SHALL BE PER MANUFACTURER'S WRITTEN RECOMMENDED
PROCEDURE. THE ANCHOR BOLT, DOWEL OR ROD SHALL
CONFORM TO MANUFACTURER'S RECOMMENDATION FOR
EMBEDMENT DEPTH OR AS SHOWN ON THE DRAWINGS. NO
REBAR SHALL BE CUT WITHOUT PRIOR ENGINEERING
APPROVAL WHEN DRILLING HOLES IN CONCRETE. SPECIAL
INSPECTIONS, REQUIRED BY GOVERNING CODES, SHALL BE
PERFORMED IN ORDER TO MAINTAIN MANUFACTURER'S
MAXIMUM ALLOWABLE LOADS.
6. INSTALLATIONS WHERE THE GENSET IS LOCATED NEAR
EXISTING CABLE TRAY SHALL HAVE A NOTE ON THE
DRAWINGS CALLING FOR GRIP STRUT INSTALLATION OVER
THE TRAY FOR TO PROVIDE FOR A WALKWAY FOR TECHS
AND SERVICE PERSONNEL
7. EXISTING PLATFORM INSTALLATIONS SHALL INCLUDE THE
INSTALLATION OF AN ANGLE UNDER THE STRUCTURAL
MEMBER OF THE PLATFORM TO SECURE THE GENSET TO
THE PLATFORM IN LIEU OF THE GATING.
8. SURFACE MOUNTING OF CONDUITS SHALL BE AVOIDED AT
ALL POSSIBLE LOCATIONS WHERE PEDESTRIAN TRAFFIC
CAN OCCUR. WHERE THIS IS UNAVOIDABLE, GRIP STRUT
BRIDGING SHALL BE CALLED OUT FOR INSTALLATION TO
PROTECT THE CONDUITS AND POTENTIAL FOR PERSONNEL
TRIPPING HAZARDS.
ELECTRICAL NOTt�:
1. ALL DETAILS ARE SHOWN IN GENERAL TERMS. ACTUAL
INSTALLATION AND CONSTRUCTION MAY VARY DUE TO SITE
SPECIFIC CONDITIONS.
2. GROUND ALL ANTENNA BASES, FRAMES, CABLE RUNS, AND
OTHER METALLIC COMPONENTS USING GROUND WIRES AND
CONNECT TO SURFACE MOUNTED BUS BARS. FOLLOW
ANTENNA AND BTS MANUFACTURERS PRACTICES FOR
GROUNDING REQUIREMENTS. GROUND COAX SHIELD AT
BOTH ENDS AND EXIT FROM TOWER OR POLE USING MFR'S
PRACTICES.
3. ALL GROUND CONNECTIONS SHALL BE CADWELD. ALL WIRES
SHALL BE COPPER THHN/THWN. ALL GROUND WIRE SHALL
BE GREEN INSULATED WIRE ABOVE GROUND.
4. REFER TO DIVISION 16 GENERAL ELECTRIC; GENERAL
ELECTRICAL PROVISION AND COMPLY WITH ALL
REQUIREMENTS OF GROUNDING STANDARDS.
5. RIGID CONDUIT SHALL BE USED WHERE DAMAGE CAN
OCCUR FROM VEHICULAR TRAFFIC OR EQUIPMENT DELIVERY
EXERCISES.
6. ATS AND GENSET LABELS ARE TO BE PROVIDED AND
INSTALLED WITH SERIAL AND CASCADE NUMBERS FOR THE
ATS AND GENSETS. LABELS SHALL BE ATTACHED VIA
ALUMINUM OR SS SCREWS - CONSTRUCTION MANAGER TO
PROVIDE TO SUBS FOR INSTALL AT SITE, DUE TO POSSIBLE
ASSET TRANSFER ACTIVITY, UPON RECEIPT OF LABEL
SPECIFICATION FROM SPRINT/NEXTEL.
7. NEW INSTALLATION SHALL BE PVC CONDUIT, USE SCH BO
ABOVE GROUND AND SCH 40 BELOW GROUND. ALSO REFER
TO CONSTRUCTION MANAGER DIRECTION FOR ANY CONDUIT
EXPOSED TO TRAFFIC (VEHICLE OR FOOT).
B. CONTRACTOR TO PROVIDE A NEW 66 BLOCK IF REQUIRED,
WITH FURTHER ROUTING TO THE RBS EQUIPMENT CABINET
AND LEFT WITH A 2' COIL OF WIRE. ALARM CABLING IN
THE TELCO CABINET SHALL BE INSTALLED IN A NEAT
FASHION WITH A 6" SERVICE COIL. CONTRACTOR SHALL
NOT MAKE PUNCH DOWNS ON THE TELCO BOARD 66
BLOCK
GENERAL NOTES:
THE SPRINT/NEXTEL METHOD OF PROCEDURE (MOP) MOPS
2061108 INSTALLATION OF PAD MOUNTED GENERATOR SETS
IS THE BASIS FOR ALL TECHNICAL INSTALLATION
SPECIFICATIONS; AND IN THE EVENT THERE IS A CONFLICT
BETWEEN THESE CONSTRUCTION DOCUMENTS OR THE
INSTALLATION CHECKLIST AND THE GENSET MOP, THE
CONTRACTOR SHALL FOLLOW THE DIRECTIVE DESCRIBED
WITHIN THE MOP AND CONTACT CONSTRUCTION MANAGER TO
APPRISE. EXCEPT NO PORTABLE GENERATOR S/0 CORD
STILL BE REMOVED
2. DRAWINGS ARE NOT TO BE SCALED, WRITTEN DIMENSIONS
TAKE PRECEDENCE, THIS SET OF DOCUMENTS IS INTENDED
TO BE USED FOR DIAGRAMMATIC PURPOSES ONLY, UNLESS
NOTED OTHERWISE. THE GENERAL CONTRACTOR'S SCOPE OF
WORK SHALL INCLUDE FURNISHING ALL MATERIALS,
EQUIPMENT, LABOR, AND ANY REQUIREMENTS DEEMED
NECESSARY TO COMPLETE INSTALLATION AS DESCRIBED IN
THE DRAWINGS AND OWNER'S PROJECT MANUAL.
3. THE PROPOSED FACILITY WILL BE UNMANNED AND DOES
NOT REQUIRE POTABLE WATER OR SEWER SERVICE.
4. THE PROPOSED FACILITY IS UNMANNED AND IS NOT FOR
HUMAN HABITAT. (NO HANDICAP ACCESS IS REQUIRED).
5. INFORMATION SHOWN ON THESE DRAWINGS WAS OBTAINED
FROM SITE VISITS AND DRAWINGS PROVIDED BY THE SITE
OWNER. DRAWINGS WERE PREPARED FROM SITE SPECIFIC
DETAILS AND STANDARDIZED DETAILS DEVELOPED BY PACIFIC
TELECOM SERVICES, LLC. STANDARDIZED DETAILS ARE TO BE
CONFIRMED AND CORRELATED AT THE SITE BY THE
CONTRACTOR. THE CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS. MODIFICATIONS DUE TO FIELD CONDITIONS
MUST BE SUBMITTED TO, AND APPROVED BY,
SPRINT/NEXTEL PRIOR TO ORDERING MATERIAL OR
PROCEEDING WITH CONSTRUCTION.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING ANY
DAMAGE CAUSED BY THE CONSTRUCTION OPERATION.
7. CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL
PERMITS AND INSPECTIONS REQUIRED FOR CONSTRUCTION.
8. CONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM
THE SITE ON A DAILY BASIS. ALL INSTALLATIONS SHALL BE
100% CLEAN OF ALL DEPRIS AND METAL FILINGS SHALL BE
REMOVED FROM ENCLOSURES, SITE AREA, FIXTURES,
PLATFORMS, ETC.
9. PRIOR TO THE SUBMISSION OF BIDS, CONTRACTORS
INVOLVED SHALL VISIT THE JOB SITE TO FAMILIARIZE
THEMSELVES WITH ALL CONDITIONS AFFECTING THE
PROPOSED PROJECT. CONTRACTORS SHALL VISIT THE
CONSTRUCTION SITE WITH THE CONSTRUCTION/CONTRACT
DOCUMENTS TO VERIFY FIELD CONDITIONS AND CONFIRM
THAT THE PROJECT WILL BE ACCOMPLISHED AS SHOWN.
PRIOR TO PROCEEDING WITH CONSTRUCTION, ANY ERRORS,
OMISSIONS, OR DISCREPANCIES SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT/ENGINEER VERBALLY AND IN
WRITING.
10. THE GENERAL CONTRACTOR SHALL RECEIVE WRITTEN
AUTHORIZATION TO PROCEED WITH CONSTRUCTION PRIOR TO
STARTING WORK ON ANY ITEM NOT CLEARLY DEFINED BY
THE CONSTRUCTION DRAWINGS/CONTRACT DOCUMENTS.
11. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE
PROJECT DESCRIBED IN THE CONTRACT DOCUMENTS. THE
CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL
CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES,
AND PROCEDURES FOR COORDINATING ALL PORTIONS OF
THE WORK UNDER THE CONTRACT.
GENERA NOTES (CONT.):
12. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND
MATERIALS ACCORDING TO MANUFACTURER'S/VENDOR'S Together with NEXTEL
SPECIFICATIONS UNLESS NOTED OTHERWISE OR WHERE 0"' E . NA"ee2
nm"e assysaWff
LOCAL CODES OR ORDINANCES TAKE PRECEDENCE.
13. ALL WORK PERFORMED ON THE PROJECT AND MATERIALS
INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL
APPLICABLE CODES, REGULATIONS, AND ORDINANCES.
PACIFIC TELECOM SERVICES,
CONTRACTOR SHALL GIVE ALL NOTICES AND COMPLY WITH
LLC
ALL LAWS, ORDINANCES, RULES, REGULATIONS AND
,,,,„ nM _, w =
e.Z wti
LAWFUL ORDERS OF ANY PUBLIC AUTHORITY, MUNICIPAL
- (2
AND UTILITY COMPANY SPECIFICATIONS, AND LOCAL AND
STATE JURISDICTIONAL CODES BEARING ON THE
PERFORMANCE OF THE WORK.
14. THE STRUCTURAL COMPONENTS OF ADJACENT
CONSTRUCTION OR FACILITIES ARE NOT TO BE ALTERED
A072 GISTEREP
BY THIS CONSTRUCTION PROJECT UNLESS NOTED
A CT
OTHERWISE.
15. SEAL ALL PENETRATIONS THROUGH FIRE -RATED AREAS
WITH U.L. LISTED OR FIRE MARSHALL APPROVED
THOMAS R. HOLLAND
MATERIALS IF APPLICABLE TO THIS FACILITY AND OR
STATE OF WASHINGTON 1
PROJECT SITE.
�
16. CONTRACTOR TO PROVIDE A PORTABLE FIRE EXTINGUISHER
WITH A RATING OF NOT LESS THAN 2-A OR 2-A1OBC
WITHIN 75 FEET TRAVEL DISTANCE TO ALL PORTIONS OF
PROJECT AREA DURING CONSTRUCTION.
17. CONTRACTOR SHALL MAKE NECESSARY PROVISIONS TO
PROTECT EXISTING IMPROVEMENTS, EASEMENTS, PAVING,
CURBING, ETC. DURING CONSTRUCTION. UPON COMPLETION
OF WORK, CONTRACTOR SHALL REPAIR ANY DAMAGE THAT
MAY HAVE OCCURRED DUE TO CONSTRUCTION ON OR
ABOUT THE PROPERTY.
18. THE ARCHITECTS/ENGINEERS HAVE MADE EVERY EFFORT
TO SET FORTH IN THE CONSTRUCTION AND CONTRACT
DOCUMENTS THE COMPLETE SCOPE OF WORK.
CONTRACTORS BIDDING THE JOB ARE NEVERTHELESS
CAUTIONED THAT MINOR OMISSIONS OR ERRORS IN THE
DRAWINGS AND OR SPECIFICATIONS SHALL NOT EXCUSE
SAID CONTRACTOR FROM COMPLETING THE PROJECT AND
IMPROVEMENTS IN ACCORDANCE WITH THE INTENT OF
THESE DOCUMENTS. THE BIDDER SHALL BEAR THE
RESPONSIBILITY OF NOTIFYING (IN WRITING) THE
ARCHITECT/ENGINEER OF ANY CONFLICTS, ERRORS. OR
OMISSIONS PRIOR TO SUBMISSION OF CONTRACTOR'S
PROPOSAL IN THE EVENT OF DISCREPANCIES THE
CONTRACTOR SHALL PRICE THE MORE COSTLY OR
EXTENSIVE WORK, UNLESS DIRECTED OTHERWISE.
19. THE CONTRACTOR SHALL PERFORM WORK DURING
OWNER'S PREFERRED HOURS TO AVOID DISTURBING
NORMAL BUSINESS.
20. CONTRACTOR SHALL CALL WASHINGTON UTILITY
COORDINATING COUNCIL SERVICE FOR UNDERGROUND
UTILITY MARKOUT PRIOR TO CONSTRUCTION
1-800-424-5555.
21. IN CASE OF CONFLICT BETWEEN THE AFORE REFERENCED
SPRINT/NEXTEL STANDARDS AND INSPECTION CHECK LIST,
THE GENERAL CONTRACTOR SHALL CONTACT
CONSTRUCTION MANAGERS' PROJECT MANAGER TO
RESOLVE, IN WRITING, ANY DEVIATIONS.
RECEIVED
JUN 1 8 2007
CITY OF FEDERAL WAY
BUILDING DEPT.
F-
Q
F-
m
0 0
O N
m -
CD 0
O O
Z
Z��
r
0U Z
O
>
W U
�
LLO
� O
w W
o
G-1
GENERAL NOTES
JOB #
DRAWING #
WA0456
G-1
REVISION 1 0
/EXISTING BUILDING
EXISTING NEXTEL 5'-0' X
9'-0" EQUIPMENT CONCRETE
PAD
EXISTING WAVEGUIDE
EXISTING SPRINT PPC
PROPOSED SPRINT ATS
4
A-3
PROPOSED SPRINT CONDUIT
(APPROX 35' RUN)
EXISTING SPRINT EQUIPMENT
ON CONCRETE PAD
PROPOSED NDM 40kw DIESEL
GENERATOR AND FUEL TANK ON
EXISTING CONCRETE PAD
xI
X —X—X— X—XJ
x—x—x--x—x—x7%—X—L
x
EXISTING (2) 6'-0" ACCESS
EXISTING TELCO RISER
EXISTING BOLLARD (TYP)
EXISTING 150'-0" LATTICE TC
ARRAYS NOT SHOWN FOR CL
EXISTING CINGULAR EQUIPMEI
EXISTING T—MOBILE EQUIPMEI
CONCRETE PAD
x — x — x — x — x — x — x — x x—x--x—x P
2 , 4
—3 A-3 A-4 A-4
U
x
is x
uj
N
4
PROPOSED NEXTEL ATS
I I
i 1
I
i
A-3
EXISTING ELECTRICAL VAULT
—' —J
x
X—X X—X—%—
x
I
—X—X—X—%—X—X—X—X—X—X—X—X—X—%—X—X—X—X—X—X—X—X—
—%—X—X—X—X
N X—X—X—X—
—X—X—X—X—X—X—X—%—X—
PROPOSED NDM CONDUIT
4'-6" 12'-7"
(APPROX 65' RUN)
EXISTING 6'-0" CHAIN LINK FENCE
WITU3� STRANDS RA.RELY[R�,. —
131'-0"t
FENCED AREA
LEXISTING BUILDING
SCALE. (24' X 367 3/16's1'-0'
SCALE (11- X 177 3/32'-1'-0' 6 5 4 3 2 1' 0 5'
RECEIVED
CITY OF FEDERAL WAY
BUILD
ENLARGED SITE PLAN I I
111�
e
Together with NEXTEL
+mz wam.i 1n x w+rc +m
hn+u, .3y31br+m
PACIFIC TELECOM SERVICES,
LLC
e ., W& —0.
p'— C..) 3a-9M Pm: ("S) W3-"13
4072
-_ , I
THOMAS R. HOLLAND
STATE OF WASHINGTON ,
1 �
�
r �
V
0 0
o ry
m
p O
3z
O
ZL�
0
Z
c-
U
O
>
Lu
Q�v
rvOw0
00
w w
L �Q
Qp
±LLL
A-2
ENLARGED SITE PLAN
JOB #
DRAWING #
WA0456
A-2
REVISION
I 0
ASCO 7000 SERIES AUTOMATIC
TRANSFER SWITCH (30-230 AMPS) (4) .43 DIA,
GENERAL NOTES MOUNTING HOLES-y
1. TYPE 3R/4/4X/12 WALL MOUNTED ENCLOSURE. L
2. FINISH TYPE 3R/4/12: ANSI 61 GREY.
TYPE 4X CONSTRUCTED OF 12 GAUGE 304
STAINLESS STEEL.
3. PLATED DOOR CLAMPS AND PADLOCK
HASP ON LEFT SIDE.
4. SINGLE DOOR HINGED ON RIGHT
5. TERMINALS - SCREW TYPE LUGS FOR
EXTERNAL POWER CONNECTIONS.
6. THREE POLE SWITCH WITH SOLID NEUTRAL
SHOWN FOR REFERENCE.
7. THREE POLE SWITCH WITH SOLID NEUTRAL
SHOWN FOR REFERENCE.
B. NEUTRAL CONFIGURATIONS:
AN OPTIONAL FULL RATED NEUTRAL CONFIGURATION
FOR EACH SOURCE AND THE LOAD MAY BE
PROVIDED. WHEN EQUIPPED IT IS IN ONE OF THE
FOLLOWING FORMATS AS SPECIFIED BY THE
CATALOG NUMBER NO. NEUTRAL TYPE:
(A) SOLID (COPPER BUS) NEUTRAL
(B) SWITCHED NEUTRAL POLE
(C) OVERLAPPING NEUTRAL POLE
CAM-LOK CONNECTOR
ENCLOSURE
EXISTING CONCRETE
FR 0 NT
GENERATOR VENT
FRONT VIEW
WITHOUT DOOR
1�W
000
00
rIc
D ® I I
TRAL
MAL
FRONT VIEW
WITH DOOR
KNOCKOUTS:
LEAVE INTACT FOR TYPE 12
REMOVE FOR TYPE 12 RIGHT SIDE
N NOT AVAILABLE ON TYPE 4,4X
2„ SWITCH RATING RANGE OF WIRE
BOTTOM VIEW (AMPS)
30-150 (1) #14 TO 4/0 AWG AL-CU WIRE
200-230 (1) #14 TO 4/0 AWG COPPER WIRE
E)
PROPOSED NEXTEL
40kw SINGLE SIDE
SERVICE GEN£RATO
PROPOSED NEXTEL
77 GALLON DIESEL
FUEL TANK
8.-o.
TOP
ATS CABINET OUTDOO
SCALE: (24"X36': NOT TO SCALE
SCALE (11'Xi 7): NOT TO SCALE
r
00
r
UG
STUDS
0
BACK
SCALE: (24WB-): 1/2"=1'-0"
SCALE: (11"X17): 1/4"=1'-O"
7"
-- —� - 75-.50 COMBINATION
n PILOT KNOCK -OUTS.
TOP AND BOTTOM
TOP VIEW
TYP TOP AND BOTTOM --(4) .37-DIA. EXTERNAL
ASCO 7000 SERIES AUTOMATIC
TRANSFER SWITCH (30-230 AMPS)
INTERIOR
WALL --
DIMPLED MOUNTING HOLES
q" �. 1'-1"
OLID
EUTRAL
NORMAL
1. 1'-3" L 1'-6"
FRONT VIEW FRONT VIEW
WITHOUT DOOR WITH DOOR
GENERAL NOTES
1. TYPE 1 WALL MOUNTED ENCLOSURE.
2. STANDARD FINISH - LIGHT GREY, ANSI 61.
3. KEY LOCKABLE HANDLE.
4. REMOVEABLE SINGLE DOOR.
5. TERMINALS - SCREW TYPE LUGS FOR
EXTERNAL POWER CONNECTIONS.
6. ® CENTER OF GRAVITY.
7. THREE POLE SWITCH WITH SOLID NEUTRAL
SHOWN FOR REFERENCE.
ATS CABINET INDOOR
SCALE: (24"X367:NOT TO SCALE
SCALE (11"X177: NOT TO SCALE
x V
a
m GROUND LUG
MOUNTING STUDS
7�.
SWITCH RATING RANGE OF WIRE
(AMPS)
30-150 (1) #14 TO 4/0 AWG AL-CU WIRE
200-230 (1) #14 TO 4/0 AWG COPPER WIRE
3
A _q GENERATOR HOUSING
!� TOP OF GENERATOR
IT11FUEL TANK
3/4"0 EPDXY SET ANCHOR
BOLTS, 4" MIN. EMBED (TYP)
1—TOTAL OF (4) BOLTS MIN.
VIBRATION ISOLATION TO BE
SUPPLIED BY GENERATOR
n CONy2�T��VgrBY
I . , I CITY OF FEDERAL WAY
FOUNDATION SECTION BUILDING DEP _ .
2 SCALE: (24"X36-):1-1/2"
SCALE: (11'X17'):3/4' = V-0"
■
Together with NEXTEL
nor. w.r+4.,m
PACIFIC TELECOM SERVICES,
LLC
ww
Phph_(mq 3a2 M00 i— (m!) 903-8513
- `" r / I
THOMAS R. HOLLAND
STATE OF WASHINGTON 1
1 �
O
a�
O
4
O
3o
Z
0
0
U
Z
w0�
Iv1LO
O
w
w
�
�
Q
o
A-3
GENERATOR AND
EQUIPMENT DETAILS
JOB il} DRAWING #
WA0456 A-3
REVISION I D
PROPOSED 4OKw DIESEL
GENERATOR ON CONCRETE PAD
i 2
x
TDETAIL
axx —x —x—x—x—
NERATOR FRAME BOND SEE
SAME SHEETNERATOR FENCE BOND SEE
DETAIL SAME SHEET
GENERATOR FRAME
TWO HOLE BOLTED
x—
iLl x
I
x
x—x—x—'L—=)L—�=J—�
PROPOSED #2
AWG ATS CASE I
BOND I 1
\SPROO
INT ATS
APPROX. LOCATION OF EXISTING
SPRINT GROUND RING (CONTRACTOR
TO FIELD VERIFY EXACT LOCATION)
—x—x—x—x—x—x—x—x—x—x—x—x—x—x—x—x--x—x—x
GROUND LUG, SS HDW
0 #2 AWG TINNED WIRE
0
NOTE:
PREP SURFACE BEFORE GROUNDING -
USE NO-OX BETWEEN LUG AND STEEL.
USE SAME COLOR TOUCH UP PAINT TO
PREVENT RUST.
GENERATOR FRAME BOND
NOT TO SCALE
SCALE: (24' X 387 1/4'-1'-0'
SCALE (11' X 177 1/B'-7' v
NOTES:
1. POWER INTERRUPTION IS ALLOWED ONLY UNDER
THE FOLLOWING CONDITIONS; OUTSIDE OF THE
MORNING AND AFTERNOON DRfVE TIMES. CUT
DURATION MUST BE GUARANTEED TO BE LESS
THAN 2 HOURS MAX. IF THIS CAN NOT BE
GUARANTEED STAND-8Y POWER MUST BE
CONNECTED OR INTERRUPTION MUST BE
PERFORMED DURING THE MAINTENANCE WINDOW.
2.EXISTING DUPLEX Gn ON THE GENERATORS SHALL
BE CHANGED OUT TO A NON -GF1 OUTLET TO
AVOID LOSS OF POWER TO THE BATTERY CHARGER
AND BLOCK HEATERS. NON-Gn OUTLET SHALL BE
SERVICED BY ONE 20AMP CIRCUIT IN FLEX
CONDUIT.
EXOTHERMIC WELD
COLD GALVANIZED
AFTER COOLING —
12" M
GLN .aL GROL]NDING OTES:
TO BURIED GROUND RING WITH
1. EXOTHERMIC WELD ALL CONNECTIONS
PARRALLEL TAP WELDS, USE SHORT RODS WHERE STANDARD GROUND RODS ARE
Tpgetherwith NEXTEL
NOT USED, SEE CABLE TO CABLE DETAIL.
0!4 MUIM 0 xc sum im
WA 99D52
2. MAKE ALL GROUNDING CONNECTIONS AS SHORT AS POSSIBLE, MINIMUM
=m D.
FlIDNC 4T5$7!.]ADO
BENDING RADIUS IS B".
3. CLEAN ALL SURFACES AND BRUSH WITH BRONZE BRUSH PRIOR TO MAKING
GROUND CONNECTIONS, PAINT ALL EXOTHERMIC WELDS TO GALVANIZED OBJECTS
WITH GALVANIZE PAINT, USE NO-OX COMPOUND WITH METAL TO METAL
PACIFIC TELECOM SERVICES,
CONNECTIONS.
LLC
4. INSTALL 5/8" X 10' COPPER CLAD GROUND RODS IN LOCATIONS SHOWN,
W. nm Awn.. S. SuN. M
S.�, WA. NIM
�Mns (M) 3.2 Nc Fs (M) 9W] 15
DISTANCE 10'-0" MINIMUM TO 15'-0" MAXIMUM BETWEEN RODS.
5. GROUND SYSTEM MUST BE INSPECTED BY CONSTRUCTION MANAGER PRIOR TO
C) BACKFILL, PROVIDE 24 HOURS NOTICE.
6. ALL BONDS SHALL BE #2 AWG BARE, THINNED, SOLID COPPER UNLESS
OTHERWISE NOTED.
THE GENSET SHALL BE GROUNDED TWICE IN DIAGONAL CORNERS. ONEGROUND
TO THE TANK FRAME AND THE SECON❑ TO THE GENERATOR ENCLOSURE
x — x — x — x — X—x—FRAME. IT IS ACCEPTABLE TO GROUND THE TANK AT BOTH LOCATIONS WITH A
rA-0721s7.
JUMPER FROM THE TANK TO THE GENSET ENCLOSURE. THESE GROUNDS SHALL
BE ON THE OUTSIDE OF TH£ UNIT TO BE VISIBLE BY ALL.
'
PROPOSED
NEXT \ ATS
PROPOSED #2 AWG
ATS CASE BOND
I I
APPROX. LOCATION OF
EXISTING NEXTEL GROUND
RING (CONTRACTOR TO FIELD
VERIFY EXACT LOCATION)
X —X —
FENCE POST
FINISHED GRADE
FENCE BONDING CONCRETE FOOTING
CONDUCTOR
FENCE BONDING DETAIL
NOT TO SCALE
GROUNDING PLAN 12
GRCUNDING PLAN NOTES -
CDPROVIDE AND INSTALL #2 AWG BARE, TINNED SOLID COPPER CONDUCTOR FROM
THE GENERATOR FRAME TO THE GENERATOR GROUND ROD.
�2 PROVIDE AND INSTALL A 5/8" X 10'-0" COPPER CLAD STEEL GROUND ROD
APPROXIMATLEY 24" FROM GENERATOR PAD, FOR CASE BOND.
O3 PROVIDE AND INSTALL A #2 AWG BARE, TINNED SOLID COPPER CONDUCTOR
FROM THE GROUND ROD TO THE NEAREST POINT ON THE EXISTING GROUND
RING.
O4 PROVIDE AND INSTALL 02 AWG BARE, TINNED SOLID COPPER CONDUCTOR FROM
THE FUEL TANK FRAME TO THE FUEL TANK GROUND ROD.
ATS NOTES:
IF THE ATS IS INSIDE THE CELL SITE ENCLOSURE, THE ATS CASE SHALL BE
BONDED TO THE HALO GROUND RING INSIDE THE ENCLOSURE WITH A #& AWG
COPPER WIRE. IF THE ATS IS OUTSIDE THE ENCLOSURE, IT SHALL BE BONDED TO
THE EXTERNAL DROUND RING WITH A #2 AWG SOLID TINNED COPPER WIRE.
THE SURGE ARRESTORS DESCRIBED IN THIS MOP ARE TO BE MOUNTED ON THE
MOUNTING PLATE SOLD BY THE MANUFACTURER. THEY MAY BE GROUNDED IN ONE
OF THREE WAYS:
1. IF THE ARRESTOR MOUNTING PLATE IS MOUNTED ON THE TELCO BOARD AND
IF THE TELCO GROUND BAR IS BONDED TO THE EXTERNAL GROUND RING, THE
PLATE MAY BE BONDED TO THE TELCO GROUND BAR WFTH A #2 AWG INSULATED
STRANDED COPPER WIRE AND SUITABLE COMPRESSIONOTYPE 2-HOLE LUGS.
2. IF THE ARRESTOR PLATE IS NOT MOUNTED ON THE TELCO BOARD, BOND IT
DIRECTLY TO THE EXTERNAL GROUND RING WITH A #2 AWG SOLID TINNED
COPPER WIRE. USE A PVC CONDUIT THROUGH THE SHELTER WALL AT A 45
DEGREE ANGLE TO ALLOW THE GROUND LEAD TO EXIT THE SHELTER FOR
BONDING TO THE EXTERNAL GROUND RING.
3. IF AN EXISTING #2 AWG GROUND CONDUCTOR EXISTS THE SHELTER (TO THE
EXTERNAL GROUND RING) WITHIN 2FT OF THE MOUNTING PLATE LOCATION, THE
PLATE MAY BE BONDED USING A #2 AWG INSULATED STRANDED CONDUCTOR WITH
A COMPRESSION TYPE "C" TAP AND A SUITABLE COMPRESSION TYPE 2 HOLE LUG.
MAKE ALL CONNECTIONS TO THE ATS CASE, THE GENERATIOR FRAME, THE
EXTERNAL FUEL TANK (IF PRESENT AND IF SUPPORTED BY THE MANUFACTURER)
AND THE SURGE ARRESTOR MOUNTING PLATE WITH SUTABLE 2-HOLE
COPRESSION-TYPE LUG RAND STAINLESS -STEEL SCREWS, STAR -TYPE LOCK
WASHERS AND LUG CONTACTS THE MAiINGVE PAINT AT THE METAL SURFACE 1NOINT OUES710NET0 EE S�REQG" FI
METAL -TO -METAL CONTACT. APPLY ANTIOXIDANT TO THE MATING SURFACES.
ENSURE THAT ALL UNDERGROUND OR OUTDOOR CONNECTIONS TOAjffOjND8IG200�
SYSTEM ARE EXOTHERMICALLY WELDED (CAD -WELDED).
PERFORM ALL GROUNDING WORK IN ACCORDANCE WITH STDIbffV&,FEDERALV
CONSTRUCTION STANDARDS RI III ntNG DEPT
ELECTRICAL NOTES
Q
G
MF-
0
0 0
O
z��
0 Z
EL O
>
x U
,wL.LLO
U p
w w
0
Q O
E-1
GROUNDING PLAN AND
F ELECTRICAL NOTES
JOB #
I DRAWING !
WAO45fi
I E-1
REVISION o
MQ POWER DIESEL PADMOUNT GENERATOR SET
CONTROL PANEL
REMOTE
START
ALARM EXPANSION BOARD
' WEAK BATTERY 9 NC BLK
K5
10 C l
�I
+ LOW BATT VOLTAGE 11 INC
K6
12 C
HIGH BATT VOLTAGE 13 NC
K7
14 C
LOW ENGIN TEMP 15 NC
K8
I+ 16 I C hrWHT—
21 NC BRN—
FAULT #1
22 � C j-I-BLU—
LEAK DETECT 23 NC ` RED —
FAULT #2
l 241 C I GRNLLIT
—
ENGINE RUNNING 25 INC
FAULT #3
26
1 35% LOW FUEL 27 NC }
FAULT #4
i 28 F}-'
' 29 FNC
` FAULT #5
30 ❑C `
l
GENERATOR FAILURE 31 NC BILK,
FAULT OUT #5 I
j 32 C � �-f-WHT
L—_------�_�J
STRANDED
WIRE
2
ASCO
7000
ATS
STRANDED
WIRE
STRANDED
WIRE
NOTES:
O
G:D'V-) a GND
O
O
+/_ o +/--0
GND v) ii GND
0
O
GND V)) GND
0
O
O
0
GND v�i ii GND
0
GND ii GND
O
O
1 GND w a GND
fo
O
GND a GND
O
O
O
+/_ 0 o +/-
GNO V) Of GND
0
O
O
O
+/- CWD o
Of-
GND V GND
0
O
O
GND u0) a GND
O
O
O
+/_ o +/-
GND ' �a GND
0
O
O
oc
GND V) ii GND
O
O
O
O
+/_ : +/-
GND o) a GND
0
O
O
GND vV) d GND
O
O
+/_ Lo' o +/-
ct
GND V) a GND
0
O
O
O
+/_ wo o +/-
GND V) a GND
0
O
O
O
O
+/_ ' o +/-
GND N a GND
0
O
O
+/_ 5 o +/D�0
GND N a GN
O
1. SEE DETAIL 1, SHEET E-3 FOR ATS CABLE SCHEDULE
2. CONTRACTOR TO PROVIOE A NEW 66 BLOCK IF REQUIRED, Wn-H
FURTHER ROUTING TO THE RBS EQUIPMENT CABINET AND LEFT WITH
A 2' COIL OF WIRE. ALARM CABLING IN THE TELCO CABINET SHALL
BE INSTALLED tN A HEAT FASHION WITH A 6" SERVICE COIL
CONTRACTOR SHALL NOT MAKE PUNCH DOWNS ON THE TELCO
BOARD 66 BLOCK
WHT/BLU
(UTILITY
POWER)
BLU/WHT
WHT/ORG
(GENERATOR
POWER)
ORG/WHT
WHT/GRN
(TRANSFER SW
POSTION)
GRN/WHT
IHT/BLU
NERATOR
-AILURE)
LU/WHT
IHT/ORG
(ENGINE
UNNING)
)RG/WHT
VHT/GRN
35% FUEL
EMAINING)
;RN/WHT
9
SOLID
WIRE
7
SOLID
WIRE
WHT/BLU ------- 1� B
;ENERATOR SOLID
MINOR) WIRE
BLU/WHT
WHT
(LEAK
)ETECTED)
ORG/WHT
SYSTEM BLOCK
11 0 0 0 0 11
WHT/BLU 37 0 0 0 37
BLU/WHT 12 0 0 0 12
38 o a o 0 38
WHT/BLU
BLU/WHT
WHT/ORG
ORG/WHT
WHT/GRN
GRN/WHT
WHT/ORG
ORG/WHT
WHT/GRN
GRN/WHT
WHT/ORG
ORG/WHT
WHT/BLU
BLU/WHT
17 0 0 0 —17'
43 0 0 0 43
,a o 0 016
44 0 0 0 44
19 o 0 019
45 0 0 0 0 45
20 0 0 0 0 20
46 r o 0 0 46
21 o 0 0 21
477 o 0 0 47
22aoo-22
� o 0 0 4B
23� o 0 0 23
49 0 0 0 0 49
24 0 0 0 0 24
50 0 0 0 0 50
25 0 0 0 0 25
USER BLOCK
36 0 0 0 0 36
11 0 0 0 0 11
37 0 0 0 0 37
12 0 0 0 0 12
3B o 0 0 0 38
13 0 0 0 0 13
39 0 0 0 39
14 0 0 0 14
40 0 0 0 40
15 0 0 0 15
41 0 0 0 0 41
16 0 0 0 0 16
RECEIVE
JUN 18 2007
CITY OF
DEPT.
MQ POWER ALARM WIRING - IDEN
SCALE (24-X36': NOT TO SCALE (
SCALE (11'X17': NOT TO SCALE
*rint.
Together with NEXTEL
,m.s resa.s n ,c nm ,00
s[oweo, ■. noss
M.o,.r azxsrs�rm
PACIFIC TELECOM SERVICES,
LLC
see r,nn W. s, swi. eso
rbT (zae) arz-soon rea (me) eoe-es,a
4072
- J i
THOMAS R. HOLLAND
STATE OF WASHINGTON
i -, - :-_3
rY.
z
W
mc,
�z
w
0Ua
U
�)L0
c4
w 1v
V
o
E-2
MO POWER DIESEL GENERATOR
ALARM WIRING — IDEN
JOB #
DRAWING
WA0456
E-2
REVISION 0
ASCO 7000 SERIES
TRANSFER SWITCH
g
BLK
UTILITY POWER
Ei
WHT
[OPTION 18G]
(CLOSED WHEN
POWER ON)
7
BLK
4
WHT
3
GRN
GENERATOR POWER
9
RED
[OPTION 18B] (OPEN
WHEN POWER ON)
1
GRN
7
RED
31
BLU
32
BRN
TRANSFER SWITCH
POSITION (CLOSED FOR
UTILITY)
12
BLU —
13
BRN
aAE
IX-6^4 r
BLK
WHT
RED
GRN
BRN
5 BLU
STRANDED
WIRE
BLK
WHT
RED
GRN
BRN
6 BLU
STRANDED
WIRE
aD GND
N
Q
O
mGD ND
O
o
1n D_
O
O
t w t
0
GND MD it GND
O
O
O
V) D_
O
t w t
GND � w GND
O
O
O
V) D_
0
t w t
E aE GND
Q
0
GND
V) D_
O
O
t w t
GND z) . GND
O
O
Q
1n o
NOTES:
1. SECOND POLYPHASER IS PROVIDED FOR ENVIRONMENTAL CONTROL SYSTEM (TO BE
CONNECTED BY OTHERS).
2 POLYPHASERSALL SUFFIC ENT ROOM TO DO TH S THE CABINET. THE EXISTING TELCO RE
POLYPHASER(S) SHOULD BE MOUNTED
IS NOT
W/IN A NEW 18"X18"X32" NEMA RATED ENLCOSURE MOUNTED ON THE EXISTING
H-FRAME.
3. POLYPHASERS HAVE SPECIFIC WIRE IN/WIRE OUT ROUTING. THIS MUST BE FOLLOWED
BY INSTALLATION PERSONNEL.
4_ POLYPHASER QUANTITY REQUIREMENTS.
-COMA SITES RECEIVE 2, ONE MOUNTING PLANE FOR GENERATOR ALARMS ONLY.
NO POLYPHASERS BETWEEN ATS AND BTS.
-IDEN SITES RECEIVE 4, ONE MOUNTING PLANES, TWO FOR GENERATOR ALARMS,
ONE FOR ATS ALARMS.
-CO-HAB (IDEN AND COMA) RECEIVE 4, ONE MOUNTING PLANE, ALL GENERATOR
ALARMS 00 TO THE IDEN SHELTER/CABINET, AND THE ATS ALARMS (FOR COMA
ONLY) DO NOT REQUIRE POLYPHASERS - STRAIGHT THROUGH TO BTS (RADIO
CABINET). -- IN CO-HAB INSTANCES 2 ATS WILL BE USED. THE IDEN ATS
USES POLYPHASERS BETWEEN IT AND FINAL PUNCHDOWN.
5. ALL ALARMS GO TO THE IDEN SIDE ON COHAB SITES. ATS ALARMS ALSO GO TO THE
COMA SIDE. NO POLYPHASERS ARE REQUIRED FOR HE ATS ALARMS FOR COMA.
ATS ALARM WIRING - IDEN
SCALE (24'X36'): NOT TO SCALE 2
SCALE: (11'X17': NOT TO SCALE
WHT/BLU
(UTILITY
POWER)
BLU/WHT
WHT/ORG
(GENERATOR
POWER)
ORG/WHT
WHT/GRN
GRN/WHT
(TRANSFER
SWITCH
POSITION)
9 WHT/BLU
SOLID BLU/WHT
WIRE
WHT/ORG
ORG/WHT
WHT/GRN
GRN/WHT
SYSTEM BLOCK
11 o O O o 11
37 0 0 0 37
12 o a o 12
38 0 0 0 0 38
21 0 0 0 0 21
47 o 0 0 47
22 2�=m 0 0 022
48 o 0 048
233 23
49 0 0 0 0 49
24 o I== 0 0 24
50 0 0 0 0 50
25 0 0 0 0 25
CABLE FROM
TO
MANUFACTURER
PART
NUMBER
CONDUCTOR COUNT
AND GAUGE
USE
NUMBER
2 (UNSHIELDED)
ATS GENERATOR START
GENERATOR
1
ATS
BELDEN
8442
22 AWG
SIGNAL TO GENERATOR
TERMINAL STRIP
GENERATOR
SURGE
8 (UNSHIELDED)
GENERATOR ALARMS TO SYSTEM
2 TERMINAL STRIP
ARRESTORS
BELDEN
g421
22 AWG
BLOCK SURGE ARRESTOR
GENERATOR
SURGE
BELDEN
8442
2 (UNSHIELDED)
FUSED 12 VDC TO SYSTEM
BLOCK SURGE ARRESTOR
3 TERMINAL STRIP
ARRESTORS
22 AWG
GENERATOR
SURGE
8 (UN2SHAIWGDED)
ENERA O TO SYSTEM
GENERATOR
4 TERMINAL STRIP
ARRESTORS
BELDEN
9421
SURGELARMS
BLOCK ARRESTOR
SURGE
8 (UNSHIELDED)
ATS ALARMS TO SYSTEM BLOCK
5 ATS
ARRESTORS
BELDEN
9421
22 AWG
SURGE ARRESTOR
SURGE
TELCO
SUPERIOR
12-204-37
8 (SOLID CONDUCTOR)
GENERATOR ALARM OUTPUTS FROM SYSTEM
BLOCK SURGE ARRESTOR TO SYSTEM BLOCK
7 ARRESTORS
BOARD
/ ESSEX
22 AWG
TELCO
S (SOLID
GENERBLOCKATOR ALARM TS
UTO IVGM
E
8 ARSURGE
RESTORS
BOARD
/ ESSIOR EX
12-204-37
22CAWGUCTOR)
SURGE ARRESTOR
SURGE
TELCO
SUPERIOR
12-204-37
8 (SOLID CONDUCTOR)
ATS ALARM OUTPUTS FROM SYSTEM BLOCK
TO SYSTEM BLb-N
O
9 ARRESTORS
BOARD
/ ESSEX
22 AWG
SURGE ARRESTOR {j
ATS CABLE SCHED
SCALE: (247(36'): NOT TO SCALE
SCALE (I I'X17': NOT TO SCALE
I
CITY OF FEDERAL WA
BUILDING PSP:�.Y
Together with NEX[TEL
neoxo +zs-2��.r.00
PACIFIC TELECOM SERVICES,
LLC
3N FIM ev.w. 5., s,ul. e5o
S . WA. W104
P,_ (2M) 342-9000 Fez (205) 903-5513
4072
THOMAS R. HOLLAND
STATE OF WASHINGTON '
W
4
r
Va
a
O N
O C]
z
ZaD
O
0 V
a
� Ll
Q
70
wUJ
W 0
Q o
E-3
ATS CABLE SCHEDULE AND
ATS ALARM WIRING — IDEN
JOB #
DRAWING 1
WA0456
E-3
REVISION 1 0
NOTES:
1.
2.
3.
4.
5.
POLYPHASER SURGE PROTECTORS SHALL BE MOUNTED NEAR THE ATS AND CONNECTED
TO NEAREST GROUND WIRE EXITING THE SHELTER WITH A #6 WIRE WITH A TWO HOLE
LUG CONNECTION.
ALL POLYPHASERS SHALL BE MOUNTED W/IN THE EXISTING TELCO CABINET. IF THERE
IS NOT SUFFICIENT ROOM TO DO THIS, THE POLYPHASER(S) SHOULD BE MOUNTED W/IN
A NEW 18"X1B"X12' NEMA RATED ENLCOSURE MOUNTED ON THE EXISTING H-FRAME
POLYPHASERS HAVE SPECIFIC WIRE IN/WIRE OUT ROUTING. THIS MUST BE FOLLOWED
BY INSTALLATION PERSONNEL
POLYPHASER QUANTITY REQUIREMENTS;
-CDMA SITES RECEIVE 2, ONE MOUNTING PLANE FOR GENERATOR ALARMS ONLY.
NO POLYPHASERS BETWEEN ATS AND BTS.
-IDEN SITES RECEIVE 4. ONE MOUNTING PLANES. TWO FOR GENERATOR ALARMS,
ONE FOR ATS ALARMS.
-CO-HAB ($DEN AND COMA) RECEIVE 4. ONE MOUNTING PLANE, ALL GENERATOR
ALARMS GO TO THE IDEN SHELTER/CABINET, AND THE ATS ALARMS (FOR COMA
ONLY) DO NOT REQUIRE POLYPHASERS -- STRAIGHT THROUGH TO BTS (RADIO
CABINET). -- IN CO-HAB INSTANCES 2 ATS WILL BE USED. THE IDEN ATS USES
POLYPHASERS BETWEEN IT AND FINAL PUNCHDOWN.
ALL ALARMS GO TO THE IDEN SIDE ON COHAS SITES. ATS ALARMS ALSO GO TO THE
COMA SIDE. NO POLYPHASERS ARE REQUIRED FOR THE ATS ALARMS FOR
UTILITY CO. DISCONNECT
L1 /L2
✓GENERATOR ELECTRICAL GROUND II
✓EXOTHERMIC BOND TO EXTERIOR GROUND RING
! SHELTER DISCONNECT
I
I
1 F_71
N N I
I
I
"CHASSISD H-FRAME) BOND
CHASSIS BOND
i
✓UTILITY ELECTRICAL GROUND ROD*
✓3 INCHES ABOVE SURFACE FOR INSPECTION
✓EXOTHERIC BOND TO EXTERIOR GROUND RING
N
ATS/MTS
NORMAL
CHASSIS BOND TO
HALO (INTERIOR OR
EXTERIOR (EXTERIOR)
✓SHELTER ELECTRICAL GROUND ROD*
✓3 INCHES ABOVE SURFACE FOR INSPECTION
✓EXOTHERMIC BOND TO EXTERIOR GROUND RING
*IF UTILITY DISCONNECT 15FT OR LESS FROM SHELTER, COMMON ROD PERMITTED,
OTHERWISE, TWO DISTINCT RODS.
**BOND UTTUTTY DISCONNECT NEUTRAL/GROUND TO SHELTER GROUND IF UTILITY
DISCONNECT IS WITHIN SHELTER PERIMETER, OTHERWISE, NOT BOND.
NEUTRAL GROUND BOND
SCALE (24"X36':NOT TO SCALE
SCALE (11'X17-):NOT TO SCALE
UTI LITY
DISCONNECT
EMERGENCY POWER INPUT
FROM PADMOUNT GENERATOR
I
,
I
I
I
I
I
I
I
I
GENERATOR CHARGE CONNECTION
l
E
I
ALARM /CONTROL CONNECTION I
I
I
I
I
I
I
I
I
I
I
I
GENERATOR
APPLETON------_-----
CONNECTOR
ATS LOAD CENTER TO SITE
LOADS
I '
I
I
I I POWER
I SURGE
I .' ROTECTOR
I k
I
I I TO FACILITY
I ALARM ALARM BLOCK
SURGE (PROVIDED
PROTECTORS WITH SHELTER)
I I�
I
I
I
I
I
I
I
I
r----� NOTES:
I ! I
1.IF PORTABLE IS REQUIRED IN ADDITION TO
-�- I PADMOUNT GENERATOR, ADD PLANNING AS
I I REQUIRED TO ADD MANUAL TRANSFER SWITCH
I I AND APPLETON CONNECTOR IN EMERGENCY
1 # I BUS FROM ATS (SHOWN IN DOTTED LINES).
I i
L----J
GENSE SINGLE -LINE DIAGRAM
SCALE: (24"X36"): NOT TO SCALE 2
SCALE: (11"X17"): NOT TO SCALE
ALL GENSET CONNECTIONS VIA STUB -UP AREA
LOAD CENTER 1%
�CHARGER HEATERS POWER
L1 /L2
N I I I GENERATOR I GENSE-r POWER OUT
CHASSIS BOND ALARM/STATUS/CONTROL
TO HALO
3
TO C
RING
GENSET/TANK
GROUND ROD
SURGE
SUPPRESSOR
SITE
LOAD CENTER
SITE POWER
UTILITY POWER IN
ATS* I� UTILITY MAINS
� ` DISCONNECT
TO IMU
MULTI -PAIR ALARM CABLE ALARM 66
BLOCK
t CEIVE
CONDUIT SINGLE -LINE
SCALE: (24"X36"):NOT TO SCALE
SCALE (11"X17': NOT TO SCALE
JUN 18 2007
OF FFDEFtAL
1
*rint. )00
Together with NECra-
lose WNOWS W NE SUITE IN
IIEDWND. WA MOM
PNONL' .'x+W IN
PACIFIC TELECOM SERVICES,
LLC
screw WA. sell
flimNr. (Doe) 312-sNN rs (DOS) sorest]
THOMAS R. HOLLAND
STATE OF WASHINGTON 1
1 �
z
Q
1
C✓
� :e
�o 0
�O N
o�
3z
0
0 Z
>
� O
cv
L O
C] Cl
w w
Q o
E-5
ELECTRICAL
DETAILS
JOB 4
DRAWING jl
WA0456
E-5
REVISION 0
o.
Federal Way
41k
�pjG MASTER LAND USE APPLICATION
'Sly 1 DEPARTiVTENT QF CQMMiFNi7'S` DEVELOPMENT SERVICES
- 33325 8s' Avenue South
2�07 PO Box 9718
3ut4 I S Federal Way WA 98063-9718
1�Y OF
253-835-2607;Fax 253-835-2609
c.F a1=1�AL WAS www.cityoffederalway.com
BUlLD1NG p�,P
APPLICATION No(s) G Date 6 l 1--0%
Project Name
Property Address/Location 174
Parcel Number(s)
2,92-16q'-979.-66 `
Project Description �Pr:,_ I to -s-Or c�-r �%m -ry e i/ �i t -h r �� r Wn
J
PLEASE PRINT
Type of Permit Required
Annexation
Binding Site Plan
Boundary Line Adjustment
Comp Plan/Rezone
Land Surface Modification
Lot Line Elimination
Preapplication Conference
Process I (Director-s Approval)
Process II (Site Plan Review)
Process III (Project Approval)
Process IV (Hearing Examiner's Decision)
Process V (Quasi -Judicial Rezone)
Process VI
SEPA w/Project
SEPA Only
Shoreline: Variance/Conditional Use
Short Subdivision
Subdivision
Variance: Commercial/Residential
Required Information
9C_ Zoning Designation
Comprehensive Plan Designation
_Value of Existing Improvements
Value of Proposed Improvements
International Building Code (IBC):
Js� C1 C_ vP `L c` Occupancy Type
1 Construction Type
-14A
Applicant }} 4
Name: M,
Address: 56 9 f S ` A,.,
City/State: Su- l c lr✓Q
zip: "f91& 1 ,
Phone: 2 o G- 31 ❑ _Z 21 z;
Fax: 24,6 �o"j_ ,SS 13 t.✓o� . G cJ l�r-1
Email: r)-1 er-3 i z-5 L /
Signature: ��
Agent (if different than Appli
Name:
Address:
City/State:
Zip:
Phone:
Fax:
Email:
Signature:
Owner
Name: l l t>i d I- E, 5!, 11 4-
Address: l L4 ( S. 'zl5G _,
City/State: F,�cr.t � �an 7
zip: 1&ba3
Phone: oG Ve- Z 2
Fax:
Email:
Signature:
Bulletin #003 -August 18, 2004 Page 1 of 1 k:\Handouts\Ivlaster Land Use Application
CITY OF FEDERAL WAY
DEPARTMENT OF COMMUNITY DEVELOPMENT SERVICES
DEVELOPMENT REVIEW COMMITTEE TRANSMITTAL
DATE: June 22, 2007
TO: Will Appleton, Development Services Manager
Scott Sproul, Assistant Building Official
Brian Asbury, Lakehaven Utility District
Chris Ingham, Federal Way Fire Department
FROM: Laura Kim
FOR DRC MTG. ON:
FILE NUMBER(S): 07-103303-00-UP
RELATED FILE NOS.: None
PROJECT NAME: SPRINT/NEXTEL @ ENCHANTED PKWY
PROJECT ADDRESS: 1741 S 356TH ST
ZONING DISTRICT: BC
PROJECT DESCRIPTION: Sprint to install an emergency generator on an
existing concrete slab inside an existing fenced
compound
LAND USE PERMITS: Use Process I
PROJECT CONTACT: PACIFIC TELECOM SERVICES
MATT ENGLESBY
568 1ST AVE S Suite 650
2067191639 (Work)
MATERIALS SUBMITTED: Plan Sheets T-1 thru E-5
Project Description
Master Land Use Application
Pacific Telecom Services, LLC
June 18, 2007
Department of Community Development
33325 8th Ave S.
Federal Way, WA 98063-9718
SUBJECT: City of Federal Way Land Use Process I permit of the installation of an emergency
generator
Dear Planning Department,
This letter is to describe the Sprint Nextel emergency generator proposal. Sprint Nextel proposes to install an
emergency generator inside of an existing fenced wireless communication compound. The site address is 1741
S. 356b St, Federal Way, WA 98003, parcel # 282104-9178-06. The project consists of placing a 40kw desiel
powered generator on an existing concrete slab inside of an existing fenced area. The property is owned by
Lloyd Russell and the current use is a wireless communication facility.
If you have any questions or need additional information please contact me.