16-125697Bruce S—N acVeigh, P.E. Civil Engineer/Small Site Geotechnical 14245 59th Ave. S. Tukwila, WA 98168 Cell Ph: 206-571-8794 July 19, 2018 Subject: Storm Drainage Pump System New Arco/AM-PM Store 35505 Pacific Highway S. Federal Way, WA 98003 Reference: Separately provided Shop Drawings for Pump Installation. The following information provides a discussion and evaluation of required supplemental stormwater pumps. While the use of pumps for storm water removal is usually avoided, in this case it is necessary since the location and planned grade for the final storm line from the site into the adjacent street system is blocked by concrete encased major utility conduits which cannot be disturbed or altered. While a common solution to the situation would be to have a "submerged" line under the concrete encasement, it is not feasible since the existing Type 1 catch basin in the street is not deep enough to accept a lower line. (The original connection line was very flat, and the depth of the concrete encasement is approximately 30", making any sort of lowered gravity line infeasible.) The design is based on field information obtained by this office and direct field survey of the exposed catch basins and conduit concrete encasement block. Drainage. The site construction including paving and underground utilities is at about 90 percent. The professionally designed storm system has major detention and water quality components which are in place. It is understood that the detention of storm runoff from the site is based on Level 2 evaluation, with only a tiny permitted release flow from the site into the adjacent street system. As noted, the site storm system is in place and cannot be altered. The only problem is getting the site storm water to the street system. Attached is a scale profile showing the field measured location and elevation of the concrete encased conduit block. Proposed is the use of a duplex pump installation in the last catch basin on the site, which is a 48" diameter Type 2. This catch basin has been installed on site per original plan and cannot be altered or re -located. Commercial Dayton 3/4 horsepower pumps are recommended, installed as a duplex system in the 48" catch basin. The pumps would elevate the flow, which would be shot into a regraded 12:�storm line connected to the street catch basin- uo Again, reference is made to the scale profile. rvlc,.Y\ c.�p4 Hum Evaluation for Ade uac . The referenced pumps have a Q rated at 80 gpm with a 5 foot head. The proposed layout has approximately a 5 foot static head. While there are several valves, bends and fittings, the short total run of pipe is only about 7 feet, the estimated Q of 80 gpm may be taken as a good estimate of flow for this installed system. A rough MGS Flood run was made of the site. Noting that the system is detained and released at a Level 2 rate, it is noted that the 100-year pre -developed "forest" condition would have a Q of Q.006_Q24__cfs or 2.97 gpm. Since the capacity of the pump is about 80 gpm, it is adequate with a high degree of safety factor. I Note that in the event of the electric power going out, the open 12" pipe to the street system will act as an overflow of the system. A review of the elevations of the catch basins and other components installed on the site indicates a temporary surcharge will have no adverse effect. The original design catch basin 12" outlet invert elevation was 197.13. The regraded overflow line 12 outlet will have an invert elevation of 200.5. The resulting approximate 3.3 feet of surcharge could back up into the system. The elevations of the "coalescing" separator, and noting its overflow feature for excess of design storms, will allow it to continue functioning with a temporary surcharge. Penn ja1 J C The surcharge will have adverse effect on the functioning of the detention system. Note that the unitive . tiny allowable release rate of a Level 2 designed system in effect creates a storage capacity requirement approaching a full storm runoff volume. (For Level 2 only 1 /2 of a 2-year forested runoff release is allowed, etc.) r9ju u_ r-tAu �.Tr �X v; 1 1 ,,,r -thrK. 5'p_ye For this reason, additional storage required for a surcharging situation would not greatly increase the amount of water storage. Thinking along this line, the possibility of an actual significant surcharging event, or unusual increase in water level in the site's systems, is remote. It would not likely not occur in the life time of the system. (Note that the FROP elevation differential computed for orifice release flow rates would be affected reducing released flow Q, however the resulting back up storage is as noted above not be seriously affected. Pump Installation_ Attached are shop drawings for the installation of the duplex pump system. Not specified in detail is electrical work, including make/model number of control/alarm box. However, operational settings required for the system setup are provided. The site owner/contractor will have the pumps and electrical related work done by a certified electrical contractor. The contractor will use components compatible with the pumps and specified system functions. The control box will be located on a permanent post adjacent to the catch basin with pumps. It will be in a non -traffic area. Functions for the control box will be.. - Emergency power shut off switch - Overload breaker - High water alarm - Switch component for alternating Pump A and Pump B operation - Timer for pump operations (optional) Provided plumbing for the duplex pump installation will be appropriate check valves, and shut off ball valves and accessible disconnect unions for each pump. Polyethylene pump lift lines will be provided. Conclusion. While unconventional, the installation of the duplex pump system for this site is appropriate. The pumps will be installed correctly and should have a long service life. The chosen pumps have a capacity vastly greater than the released detained flow rates. A physical overflow is provided should the pump's electrical systems fail during a major storm event. The surcharging of the site's drainage components, while not ideal, will have no real short or long term adverse effect on the site's systems. /�- �4) Bruce S. MacVeigh, P.E. Civil Engineer - #18657 fedwaystationstormpumps01 /1851 EXPIRES: 4/24/ /`7 - ass:•::;`; ;.::•:. my24, /.; ��!} car"". !• � 'r ®�.!� N IN R y �f �- TELEPHONE LINE P(UG) EXISTING UNDERGROUND POWER STORM DRAINAGE KEYNOTES EXXIIS LNG STORM DRAIN CATCH IN L' CONNECT TO EXISTING CATCH BASIN #1 26 CB # 11, TYPE 1 EX. RIM= 201.11 (OLDCASTLE OR APPROVED EQUAL) EX. IE= 196.95 12" IN W, NE) RIM= 203.72 EX. IE= 196.91 (18" OUT SE) IE= 201.00 12" IN SE) IE= 196.96 (12" IN NW) SEE DETAIL ON SHEET C6,2. CONTRACTOR TO FIELD VERIFY EXACT HORIZONTAL/VERTICAL LOCATION OF 27 13 LF 6" PVC SDR-35 SD ®0.50%. EXISTING STORM DRAIN PRIOR TO CONSTRUCTION. CONTACT ENGINEER IF 2$ CONNECT TO PROPOSED CB FOR LEVEL CONFLICT EXISTS.. 2 35 LF 12" ADS N-12 SD . ® 0.50%. 29 CONNECT TO ROOF DRAIN LINE. 3 CB #2, TYPE 2-48" CONNECT TO ROOF DRAINS. (OLDCASTLE OR APPROVED EQUAL) 30 'RiM = 2.04.65 IE= 201.33 (6-) . IE= 197.13 12 iN W SEE PLUMBING PLANS FOR DETAILS IE= 202.12 1�,.TIN W ti N 31 4 LF 6" PVC SDR-35 SD 0.50%. JE= 1*7:43 12" OUT SEE DETAIL N�fE C .2. 39 LF 12" ADS N-12 SD ® 0.50%. 32 (O CAS#12, TYPE 1 APPROVED EQUAL) RIM= 205.45 I MODULAR WETLAND WEST: 4'X6' INTERNAL BYPASS UNIT SEE IE= 201.00 {12" IN SE DETAIL SHEET C6.3 FOR STRUCTURE DETAILS SEE DETAIL ON SHEET f.2. GRATE INLET ELEVATION= 204.97 33 LEVEL SPREADER. SEE DETAIL ON SHE[ IE=197.85 (12" IN W) IE=197.33 (12" OUT E) 34 CB #12, TYPE 1 (OLDCASTLE OR APPROVED EQUAL) 0 20 LF 20 12" ADS N-12 SD 0 0.50%. RIM= 205.89 IE= 200.89 6" IN SE) SEE DETAIL ON SHEET C6.2. CB #3 PROPOSED 54" FLOW CONTROL STRUCTURE 35 35 LF 6" PVC SDR-35 SD ® 2.00S. RIM= 204.46 IE= 198.45 12" IN N) 36 PROPOSED CLEANOUT. IE= 202.70 12" OUT NE) (EMERGENCY OVERFLOW) � RIM= 206.03 IE= 198.45 12" OUT E IE= 201.59 SEE SHEET C6.5 FOR DETAILS. SEE DETAIL ON SHEET C6.0. (D 49 LF 12" ADS N-12 SD ® 1.00%. 37 25 LF 6" PVC SDR-35 SD 02.00%. 9 CB #4, TYPE 1 (OLDCASTLE OR APPROVED EQUAL) 38 PROPOSED CLEANOUT. IM= 204.67 RIM= 206.70 IE= 202.61 (12" IN SW) IE= 202;09 SEE DETAIL SHEET C6.2. SEE CLTAIL ON SHEET C6.0. 1 O 18 LF 12" ADS N-12 SD ® 0.50%. 39 8 LF 6" PVC SDR-35 SD 0 1.00 MIN. CANOPY ROOF DRAIN TIG.H UNE. 11 24 LF 12" ADS N-12 SD ® 4.507a. 40 25 LF 6" PVC SDR-35 SD ® 1.00% MIN. CANOPY ROOF DRAIN TIGHTLINE. 12 (O #5, TYPE 2-P" 41 14 LF 6" PVC SD ® 1.00% MIN. (OLDCASTLE OR APPROVED EQUAL} IM= 204,65 CANOPY ROOF DRAIN TIGHTLINE. IE= 198.52 (12" OUT S) SEE DETAIL ON SHEET CC6.2. 42 32 LF 6" PVC SD 0 1.00% MIN - CANOPY ROOF DRAIN TIGHTLINE. 13 PROPOSED STORMTECH MC--3500 DETENTION FACILITY. TOP OF FACILITY EL= 203.52 43 16 LF 6" PVC SD o' 1.00% MIN. BOTTOM OF CHAMBERS EL= 198.52 CANOPY ROOF DRAIN TIGHTLINE. BOTTOM OF GRAVEL EL=197.77 SEE SHEET C6.5 FOR DETAILS. 44 16 LF 6" PVC SD ® 1.00% MIN. (14) CB #6, TYPE 2-48" CANOPY ROOF DRAIN TIGHTLINE. SUMMER SEASON SAVINUS! UP TO 20% OFF ALL CATEGORIES • ENTER CODE: SUMSVR • JULY 17-19 SEE DETAILS 0 (/COUPONS -PROMO -CODES/) 9� (//www.zoro caw (//www.zoro.com),- Get your search on... Home (/) > Pipes, Valves & Fittings (/pipes-valves-fittings/c/33/) > Sump Pump & Utility Pumps (/sump-pump-utility- pumps/c/10661/) > Submersible Sump Pumps (/submersible-sump-pumps/c/10426/) > 314 HP 1-1/2" Submersible Sump Pump 115V Vertical 3/4 HP 1-1/2" SUBMERSIBLE SUMP PUMP 115V VERTICAL DAYTON (/B/DAYTON/) I ZORO #: G0998776 I MFR #: 3BB72 No Reviews I Write the First Review (/review? pr_page_id=G0998776&pr_merchant id=297763&pr_api key=9Od7l773-2bl9-45c6-a4ec- 053f308ea2cd&pr_m ercha nt-group_id=48555) In stock 8 253.92 /EA Item ships from Zoro in 1 business day. r -- - i qty 1 Add to Cart This item ships FREE. Details. Standard ground shipping. Max. Dia. Solids: 1/2" Voltage: 115 Country of Origin (subject to change): China DESCRIPTION Submersible Sump Pump, Pump HP 3/4, Voltage - Pumps 120VAC, Discharge NPT 1-1/2 In. F, Max. Head - Pumps 32 ft., Pump Body Material Cast Iron, Base Material Cast Iron, Impeller Material - Pumps Cast Iron, Shaft Seal Material - Pumps Carbon Ceramic, Cord Length - Pumps 10 ft., Switch Type - Pumps Vertical, Max. Diameter Solids 1/2 In., Amps - Pumps 9.80, Diameter 9-1/8 In., Height 12-1/4 In., GPM of Water @ 5 Ft. of Head 80, Max. Liquid Temp. 104 Degrees F, Off Point 3 In., On Point 7-3/4 In. RESTRICTIONS AND COMPLIANCE *1 : California Proposition 65 : This product contains a chemical known to the State of California to cause birth defects or other reproductive harm. *2 : California Proposition 65 : This product contains a chemical known to the State of California to cause cancer. REVIEWS Write the First Review (/review? pr_page_id=G0998776&pr_merchant_id=297763&pr_a p i_key=9Od7l 773-2b 19-45c6-a4ec- 053f308ea2cd&pr_merchanteroup_id=48555) ZORO'S FAVORITE PRODUCTS A, Pump, Sump, 0.33 1-1/2" Male 1-1/2" Female 1" NPT Bronze 1/2" NPT Bi HP Adapter x MNPT Coupler x MNPT Spring Check Valve Spring Che( (Mayton-pump-sump- (/banjo-adapter-1-12- (/banjo-coupler-1-12- (/zoro-select-spring- (/zoro-select 033-hp- in-male-adapter-x- in-125-psi- check-valve-bronze-1- check-vaive- 4ku64/i/G1402633/) mnpt- polypropylene- in-npt- 12-in-npt- DAYTON 150f/i/G2218002/) 150b/i/G0687766/) 6ajy3/i/G0689823/) 6ajy1 /i/G231 $93.59 BANJO BANJO ZORO SELECT ZORO SELE( $3.54 $7.54 $20.53 $10.45 Zoro #: G0998776 I Mfr #: 3BB/2 Mechanical Seal: SiC Features: - GPM of Water @ 20 Ft. of Head: 50 Duty: Continuous Includes: - Housing Material: Cast iron GPM of Water @ 30 Ft. of Head: 20 Max. Head: 32 ft. Discharge NPT: 1-1 /2" F Off Point: 3" Max. Temp.: 104 Degrees F Gauge/Conductor: 18/3 GPM of Water @ 10 Ft. of Head: 70 Switch Type: Vertical IOU -Air - - ------ - 4. 5� Shaft Seal: Silicon Carbide GPM of Water @ 5 Ft. of Head: 80 Alarm: No GPM of Water @ 25 Ft. of Head: 40 Max. Liquid Temp.: 104 Degrees F Base Material: Cast Iron GPM of Water @ 15 Ft. of Head: 62 HP: 3/4 Cord Length: 10 ft. Thermal Protection: - Motor Type: Oil -Cooled Amps: 9.8 Bearing Type: Upper and Lower Ball Item: Submersible Sump Pump Diameter: 9-1 /8" Height: 12-1 /4" Hz: 60 On Point: 7-3/4" Impeller Material: Cast Iron NEC Cord Designation: SJTOW / ..mod-{L-S�•r7 e 61sle-;, �P oK��B 6F:7s 6 6 z, 77 ti. I MGS FLOOD PROJECT REPORT Program Version: MGSFlood 4.43 Program License Number: 201710009 Project Simulation Performed on: 07/18/2018 6:22 PM Report Generation Date: 07/18/2018 6:25 PM Input File Name: Project Name: Analysis Title: Comments: Hwy99station.fld Highway 99 Gas Station Level 2 Release Estimate Approximate. To check storm pump capacity. PRECIPITATION INPUT Computational Time Step (Minutes): 60 Extended Precipitation Time Series Selected Climatic Region Number: 16 Fuli Period of Record Available used for Routing Precipitation Station: 96004405 Puget East 44 in_5min 10/01/1939-10/01/2097 Evaporation Station 961044 Puget East 44 in MAP Evaporation Scale Factor 0.750 HSPF Parameter Region Number: 1 HSPF Parameter Region Name : USGS Default ********** Default HSPF Parameters Used (Not Modified by User) ********************** WATERSHED DEFINITION *********************** Predevelopment/Post Development Tributary Area Summary Predeveloped Post Developed Total Subbasin Area (acres) 1.200 1.200 Area of Links that Include Precip/Evap (acres) 0.000 0.000 Total (acres) 1.200 1.200 ----------------------SCENARIO: PREDEVELOPED Number of Subbasins: 1 ---------- Subbasin : Subbasin 1 -------Area (Acres) Outwash Forest 1.200 Subbasin Total 1.200 ----------------------SCENARIO: POSTDEVELOPED Number of Subbasins: 1 ---------- Subbasin: Subbasin 1 ----Area (Acres) Impervious 1.200 Subbasin Total 1.200 ************************* LINK DATA ##i}k#k yFkAk■* k* f*kkkN�i*# ----------------------SCENARIO: PREDEVELOPED N umhor of 1 Wee- 1 Link Name: New Channel Lnk1 Link Type: Open Channel Downstream Link: None ---------Left Overbank Upper Sideslope (z) 0.500 Upper Width (ft) 3.000 Middle Sideslope (z) 10.000 Middle Width (ft) 10.000 Mannings n 0.040 ----------Main Channel Lower Sideslope Left (z) : 0.500 Lower Width Left (ft) : 3.000 Lower Sideslope Right (z) : 0.500 Lower Width Right (ft) : 3.000 Mannings n : 0.024 Base Width (ft) : 10.0 Elevation (ft) : 100.00 Channel Slope (ft/ft) : 0.020 Channel Length (ft) : 1000.0 ----------Right Overbank Upper Sideslope (z) 0.500 Upper Width (ft) 3.000 Middle Sideslope (z) 10.000 Middle Width (ft) 10.000 Mannings n : 0.040 Massmann Infiltration Option Used Hydraulic Conductivity (in/hr) : 0.0 Depth to Water Table (ft) : 100.0 Bio-Fouling Potential : Low Maintenance : Average or Better LINK DATA ----------------------SCENARIO: POSTDEVELOPED Number of Links: 1 Link Name: New Channel Lnk1 Link Type: Open Channel Downstream Link: None ----------Left Overbank Upper Sideslope (z) 0.500 Upper Width (ft) : 3.000 Middle Sideslope (z) 10.000 Middle Width (ft) Mannings n 0.040 ----------Main Channel Lower Sideslope Left (z) 0.500 Lower Width Left (ft) 3.000 Lower Sideslope Right (z) 0.500 Lower Width Right (ft) 3.000 Mannings n 0.024 Base Width (ft) 10.0 Elevation (ft) 100.00 Channel Slope (ft/ft) 0.020 Channel Length (ft) 1000.0 10.000 z ----------Rinht n%inrhnnk Upper Sideslope (z) 0.50i1-,.� Upper Width (ft) 3.00t. Middle Sideslope (z) : 10.000 Middle Width (ft) : 10.000 Mannings n . 0.040 Massmann Infiltration Option Used Hydraulic Conductivity (in/hr) : 0.0 Depth to Water Table (ft) : 100.0 Bio-Fouling Potential : Low Maintenance : Average or Better **********************FLOOD FREQUENCY AND DURATION STATISTICS******************* ----------------------SCENARIO: PREDEVELOPED Number of Subbasins: 1 Number of Links: 1 ----------------------SCENARIO: POSTDEVELOPED Number of Subbasins: 1 Number of Links: 1 ***********Groundwater Recharge Summary ************* Recharge is computed as input to Perind Groundwater Plus Infiltration in Structures Total Predeveloped Recharge During Simulation Model Element Recharge Amount (ac-ft) Subbasin: Subbasin 1 375.813 Link: New Channel Lnk1 Not Computed Total 375.813 Total Post Developed Recharge During Simulation Model Element Recharge Amount (ac-ft) Subbasin: Subbasin 1 0.000 Link: New Channel Lnk1 Not Computed Total: aM Total Predevelopment Recharge is Greater than Post Developed Average Recharge Per Year, (Number of Years= 158) Predeveloped: 2.379 ac-ft/year, Post Developed: 0.000 ac-ft/year ***********Water Quality Facility Data ************* ----------------------SCENARIO: PREDEVELOPED Number of Links: 1 ----------------------SCENARIO: POSTDEVELOPED Number of Links: 1 ***********Compliance Point Results ************* Scenario Predeveloped Compliance Subbasin: Subbasin 1 Scenario Postdeveloped Compliance Subbasin: Subbasin 1 Recurrence Interval Computed Usir" pringorten Plotting Position �Predejjpment Runoff Postdevelopment Runoff Tr (Ye Discharge (cfs) Tr (Years) Discharge (cfs) ---------_ - --------- —------------------------------ --------- —--- ---------- C 2-Year 2.384E-04 5-Year 2.417E-04 2-Year 0.346�%i0. 5-Year 0.435 10-Year 6.470E-04 10-Year 0.514 25-Year 2.504E-03 25-Year 0.578 5.84 -03 10 -Y 6.624E-03 50-Year 0�.62266 100-Year 0-Year 1.2 -02 200-Year 0.774 ** Record too Short to Comp to Peak Discharge for These Recurrence Intervals 0 -VIK Recording Requested By: Triple B Pac Hwy, Inc. When Recorded Mail To: City of Federal Way I llllllll llll � 11111111111111�11I 1111133325 8th Ave S illy iilll lllllll llll 111 llll n Federal Way, WA 98003 20180817000303 ATTN: Ann Dower, Public Works COVENANT Reo: $102.00 8/17/201a 10:47 AM KING COUNTY, WA DECLARATION OF COVENANT Grantor (s): TRIPLE B PAC HWY, INC., a Washington corporation Grantee (s): CITY OF FEDERAL WAY, a Washington municipal corporation Property Legal Description (abbreviated): A ptn of NW 1/ , NE %, Sec 29, Twp 21N, R. 4E, W.M. Additional Legal(s) on Exhibit A Assessor's Tax Parcel ID#(s): 292104-9127 IN CONSIDERATION OF the approved City of Federal Way ("City") building permit for application No. 16-105697-000-CO relating to real property legally described as: Legal description of property attached hereto as Exhibit "A" and incorporated herein by reference.), in King County, Washington, and portions of vacated streets adjoining ("Property") the undersigned as Grantor(s) declares that the above -described Property is hereby subject to a perpetual easement for a natural or constructed storm water conveyance system ("System") and hereby dedicates, covenants, and agrees as follows: City shall have the right to ingress and egress over the Property to access such easement area for inspection of and to reasonably monitor the System for performance, operational flows or defects in accordance with the City's Surface Water Management Division procedures. 2. If City determines that maintenance or repair work is required to be done to the System, the Manager of the Surface Water Management Division of the Department of Public Works ("Manager") shall give notice of the specific maintenance and/or repair required. The Manager shall also set a reasonable time in which such work must be completed by the Grantor, its heirs, successors or assigns. If the above required maintenance and/or 4 repair is not completed within the time set by the Manager, the City may perform the required maintenance and/or repair. Written notice will be sent to the Grantor stating the City's intention to perform such maintenance. Maintenance work will not commence until at least seven (7) days after such notice is mailed. If, within the sole discretion of the Manager, there exists an imminent or present danger, said seven (7) day notice period will be waived and maintenance and/or repair work will begin immediately. 3. If at any time the City reasonably determines that any existing retention/detention system creates any conditions detrimental to the receiving surface water system, public and/or private property, the Manager may take any measures pursuant to Federal Way Revised Code. 4. The Grantor shall assume all responsibility for the cost of any maintenance and for repairs to the System. Such responsibility shall include reimbursement to the City within thirty (30) days of the receipt of the invoice for any such work performed. Overdue payments will require payment of interest at the current legal rate as liquidated damages. If legal action ensues, the prevailing party is entitled to costs and/or fees. 5. The Grantor is hereby required to obtain written approval from the Manager prior to filling, piping, cutting, or removing vegetation (except in routine landscape maintenance) in open vegetated drainage facilities (such as swales, channels, ditches, ponds, etc.), or performing any alterations or modifications to the drainage facilities contained within Property as described previously. Any notice or consent required to be given or otherwise provided for by the provisions of this Declaration of Covenant shall be effective upon personal delivery, or three (3) days after mailing by Certified Mail, return receipt requested. 6. Grantor agrees to indemnify, defend, and hold City, its elected officials, officers, employees, agents, and volunteers harmless from any and all claims, demands, losses, actions and liabilities (including costs and all attorney fees) to or by any and all persons or entities, including, without limitation, their respective agents, licensees, or representatives, arising from, resulting from, or connected with this Declaration of Covenant except to the extent caused by the sole negligence of the City. This covenant is intended to protect the value and desirability of the Property, and shall inure to benefit all of the citizens of the City of Federal Way, and shall run with the land, and shall touch and concern the land, and shall be binding on all heirs, successors, and assigns. [signature page follows] GRANTOR: TRIPLE B PAC HWY, INC. By: / i�, Biriir'a`ndeqKSingh, President STATE OF WASHINGTON ) ss. COUNTY OF KING ) On this day personally appeared before me Birkirandeep- Singh, to me known to be the President of Triple B Pac Hwy, Inc., the corporation that executed the foregoing instrument, and acknowledged the said instrument to be the free and voluntary act and deed of said corporation, for the uses and purposes therein mentioned, and on oath stated that he was authorized to execute said instrument and that the seal affixed, if any, is the corporate seal of said corporation. GIVEN my h Aq..i Rev. 10/17 this qAV\ day of 20L. (tVC, rt to name of notary) Nut? ' n and for the State f Washington. My commission expires `1 7- EXHIBIT A LEGAL DESCRIPTION THAT PORTION OF THE SOUTHERLY 415.00 FEET OF THE NORTHWEST QUARTER OF THE NORTHEAST QUARTER OF SECTION 29, TOWNSHIP 21 NORTH, RANGE 4 EAST, W.M., IN KING COUNTY, WASHINGTON; EXCEPT THE NORTH 30 FEET THEREOF, AS CONTAINED IN FULFILLMENT DEEDS UNDER RECORDING NUMBERS 8905181096 AND 8905181102; AND EXCEPT THAT PORTION LYING SOUTHERLY AND SOUTHEASTERLY OF THE NORTHERLY LINE OF SOUTH 356TH STREET AND EAST OF THE WEST LINE OF PACIFIC HIGHWAY SOUTH (SR 99), AS DESCRIBED IN DEEDS RECORDED UNDER RECORDING NUMBERS 669248 AND 1778238, RESPECTIVELY; AND EXCEPT THAT PORTION CONDEMNED FOR HIGHWAY PURPOSES IN SUPERIOR COURT CAUSE NUMBER 81-2-05952-0; AND EXCEPT THAT PORTION CONVEYED TO KING COUNTY FOR ROAD PURPOSES BY DEEDS RECORDED UNDER RECORDING NUMBERS 9104051109, 9104051110, 9104051111, 9104051112 AND 9104051113; AND EXCEPT THAT PORTION CONVEYED TO THE CITY OF FEDERAL WAY FOR RIGHT OF WAY, BY DEED RECORDED UNDER RECORDING NUMBER 20070705000558 AND RE -RECORDED UNDER RECORDING NUMBER 20070712002432, LYING SOUTHEASTERLY OF THE FOLLOWING DESCRIBED LINE: COMMENCING AT THE NORTHEAST CORNER OF SAID SECTION 29; THENCE ALONG THE NORTH LINE OF SAID SUBDIVISION, NORTH 88-32-26" WEST 1581.01 FEET TO THE MONUMENTED CENTERLINE OF PACIFIC HIGHWAY SOUTH (SR99); THENCE ALONG SAID CENTERLINE, SOUTH 22°47'51" WEST, 963.50 FEET TO A MONUMENT IN A STEEL CASING, BEING A NAIL SET IN CONCRETE AT THE CENTERLINE OF SAID PACIFIC HIGHWAY SOUTH; THENCE CONTINUING ALONG SAID CENTERLINE, SOUTH 22°48'31" WEST, 48.33 FEET TO THE SOUTH LINE OF THE NORTH 30 FEET OF SAID SOUTHERLY 415 FEET; THENCE ALONG SAID SOUTH LINE, NORTH 88°32'11" WEST, 53.68 FEET TO THE WESTERLY MARGIN OF SAID PACIFIC HIGHWAY SOUTH AND THE TRUE POINT OF BEGINNING OF THIS LINE DESCRIPTION; THENCE CONTINUING ALONG SAID SOUTH LINE, NORTH 88°32'06" WEST, 12.88 FEET TO A POINT 62.00 FEET WESTERLY, AS MEASURED AT RIGHT ANGLES, TO THE CENTERLINE OF SAID PACIFIC HIGHWAY SOUTH; THENCE PARALLEL WITH SAID CENTERLINE, SOUTH 22°48'31" WEST, 186.92 FEET TO A POINT ON THE WESTERLY LINE OF THAT DEED RECORDED UNDER KING COUNTY RECORDING NUMBER 20070712002432 AND THE TERMINUS OF THIS LINE DESCRIPTION. TOGETHER WITH THE RIGHT OF ENTRY OVER A PORTION OF THE ADJOINING PROPERTY, SUBJECT TO THE TERMS AND CONDITIONS THEREOF CONTAINED IN INSTRUMENT RECORDED UNDER KING COUNTY RECORDING NUMBER 20070925001770. AND EXCEPT THAT PORTION CONVEYED TO THE CITY OF FEDERAL WAY FOR RIGHT OF WAY, BY DEED RECORDED UNDER RECORDING NUMBER, 20170517000568, LYING SOUTH OF A LINE 53.00 NORTH OF AND PARALLEL WITH THE CENTERLINE OF SOUTH 356TH. Project Name: Arco Federal Way August 1, 2018 BDG / JSE 16777 L.002 TESL Sediment Trap_Sizing Surface area = 2,080 square feet per cfs of inflow for the 2-year runoff event Per KCSWMM Appendix D - D.3.5.2 SA = 2,080 x Q2 Q2 = 0.217 cfs (developed detention basin 2 year peak) SA = 451 sf required SA = 1,865 sf provided Flow Frequency Analysis Time series File:dev detention.tsf Project Location:Sea-Tac ---Annual Peak Flow Rates--- -----Flow Frequency Analysis ------- Flow Rate Rank Time of Peak - - Peaks - - Rank Return Prob (CFS) (CFS) Period 0.213 7 2/09/01 2:00 0.417 1 100.00 0.990 0.187 8 1/05/02 16:00 0.316 2 25.00 0.960 0.260 3 12/08/02 18:00 0.260 3 10.00 0.90,0 0.217 6 8/26/04 2:00 0.258 4 5.00 0.800 0.258 4 10/28/04 16:00 0.228 5 3.00 0.667 0.228 5 1/18/06 16:00 0.217 6 2.GO 0.500 0.316 2 10/26/06 0:00 0.213 7 1.30 0.231 0.417 1 1/09/08 6:00 0.187 8 1.10 0.091 Computed Peaks 0.383 50.00 0.980 Pond Volume for Q10 required = 2,888 cf KCRTS output Type of Facility: Detention Pond Side Slope: 3.00 H:lV Pond Bottom Length: 36.57 ft Pond Bottom Width: 18.28 ft Pond Bottom Area: 669. sq. ft Top Area at 1 ft. FB: 2261. sq. ft 0.052 acres Effective Storage Depth: 2.50 ft Stage 0 Elevation: 0.00 ft Storage Volume: 2888. cu. ft 0.066 ac-ft Pond Volume = 3,308 cf provided Return Address: City of Federal Way Attn: Ann Dower 11114 11111 11111 IJ111 qHi 33325 8th Avenue South 201705170@0568 Federal Way, WA 98003-6325 TRIPLE 8 PAC H uo 77.00 PAGE-001 OF 005 "5/1KING TCOUNTY, UP E2864899 05/17/2017 12:21 KTNNG COUNTY, GA $10.00 SALE $0.00 PAGE-001 OF 001 STATUTORY WARRANTY DEED Grantor (s): TRIPLE B PAC HWY, INC., a Washington Corporation Grantee (s): CITY OF FEDERAL WAY, a Washington municipal corporation Property Legal Description (abbreviated): A ptn of NW '/4 , NE '/4, Sec 29, Twp 21N, R. 4E, W.M. Additional Legal(s) on Exhibit A Assessor's Tax Parcel ID#(s): 292104-9127 THE GRANTOR(S) TRIPLE B PAC HWY INC. Washington corporation, for and in consideration of the City of Federal Way's approval of a building permit No. 16-105697-000-CO for construction of a gas station, convenience store, and car wash and other good and valuable consideration, conveys and warrants to the CITY OF FEDERAL WAY, a Washington municipal corporation, all of their right, title and interest, and any after -acquired interest therein, in and to the real property described in Exhibit A and depicted in Exhibit A-1 herewith attached and made a part hereof, and any after -acquired interest therein, situated in King County in the State of Washington. DATED THIS 7 day of 20L7 J [Signature Page Follows] GRANTOR: TRIPLE B PAC HWY, INC. By.��,��1� Birkirandeep Singh, President STATE OF WASHINGTON ) ) ss. COUNTY OF KING ) On this day personally appeared before me Birkimndeep Sigh, to me known to be the President of Triple B. EqLHyfy. Inc., the corporation that executed the foregoing instrument, and acknowledged the said instrument to be the free and voluntary act and deed of said corporation, for the uses and purposes therein mentioned, and on oath stated that he was authorized to execute said instrument and that the seal affixed, if any, is the corporate seal of said corporation. GIVEN my hand and official seal this _ day of MA V . 204. (no si na re) p�R 5IFWQOV still (typed! rinted name of nota `ry) r -�g�� +++' 3 •r� Notary Public in and for the State of Washington. N q ` V My commission expires 1 p j� i �':, �a%. +� s �h,,,..}.,•�•` ,I'/t�oit ` p WA5H*�.��� G:U awformsWeeddev. doc Ol/l5 LEGAL DESCRIPTION RIGHT-OF-WAY DEDICATION Exhibit A That portion of the following described parcel in the Northwest quarter of the Northeast quarter of Section 29, Township 21 North, Range 4 East, Willamette Meridian, lying South of a line 53.00 feet North of, and parallel with the centerline of South 356th: THAT PORTION OF THE SOUTHERLY 415.00 FEET OF THE NORTHWEST QUARTER OF THE NORTHEAST QUARTER OF SECTION 29, TOWNSHIP 21 NORTH, RANGE 4 EAST, W.M., IN KING COUNTY, WASHINGTON; EXCEPT THE NORTH 30 FEET THEREOF, AS CONTAINED IN FULFILLMENT DEEDS UNDER RECORDING NUMBERS 8905181096 AND 8905181102; AND EXCEPT THAT PORTION LYING SOUTHERLY AND SOUTHEASTERLY OF THE NORTHERLY LINE OF SOUTH 356TH STREET AND EAST OF THE WEST LINE OF PACIFIC HIGHWAY SOUTH (SR 99), AS DESCRIBED IN DEEDS RECORDED UNDER RECORDING NUMBERS 669248 AND 1778238, RESPECTIVELY; AND EXCEPT THAT PORTION CONDEMNED FOR HIGHWAY PURPOSES IN SUPERIOR COURT CAUSE NUMBER 81-2-05952-0; AND EXCEPT THAT PORTION CONVEYED TO KING COUNTY FOR ROAD PURPOSES BY DEEDS RECORDED UNDER RECORDING NUMBERS 9104051109, 9104051110, 9104051111, 9104051112 AND 9104051113; AND EXCEPT THAT PORTION CONVEYED TO THE CITY OF FEDERAL WAY FOR RIGHT OF WAY, BY DEED RECORDED UNDER RECORDING NUMBER 20070705000558 AND RE- RECORDED UNDER RECORDING NUMBER 20070712002432, LYING SOUTHEASTERLY OF THE FOLLOWING DESCRIBED LINE: COMMENCING AT THE NORTHEAST CORNER OF SAID SECTION 29; THENCE ALONG THE NORTH LINE OF SAID SUBDIVISION, NORTH 88-32-26" WEST 1581.01 FEET TO THE MONUMENTED CENTERLINE OF PACIFIC HIGHWAY SOUTH (SR99); THENCE ALONG SAID CENTERLINE, SOUTH 22°47'51" WEST, 963.50 FEET TO A MONUMENT IN A STEEL CASING, BEING A NAIL SET IN CONCRETE AT THE CENTERLINE OF SAID PACIFIC HIGHWAY SOUTH; THENCE CONTINUING ALONG SAID CENTERLINE, SOUTH 22°48-31" WEST, 48.33 FEET TO THE SOUTH LINE OF THE NORTH 30 FEET OF SAID SOUTHERLY 415 FEET; THENCE ALONG SAID SOUTH LINE, NORTH 88°32'11" WEST, 53.68 FEET TO THE WESTERLY MARGIN OF SAID PACIFIC HIGHWAY SOUTH AND THE TRUE POINT OF BEGINNING OF THIS LINE DESCRIPTION; THENCE CONTINUING ALONG SAID SOUTH LINE, NORTH 88°32'06" WEST, 12.88 FEET TO A POINT 62.00 FEET WESTERLY, AS MEASURED AT RIGHT ANGLES, TO THE CENTERLINE OF SAID PACIFIC HIGHWAY SOUTH; Project Name: FEDERAL WAY ARCO March 18, 2017 BDG/stm 16777L.001.doc Page 1 THENCE PARALLEL WITH SAID CENTERLINE, SOUTH 22°48'31" WEST, 186.92 FEET TO A POINT ON THE WESTERLY LINE OF THAT DEED RECORDED UNDER KING COUNTY RECORDING NUMBER 20070712002432 AND THE TERMINUS OF THIS LINE DESCRIPTION. TOGETHER WITH THE RIGHT OF ENTRY OVER A PORTION OF THE ADJOINING PROPERTY, SUBJECT TO THE TERMS AND CONDITIONS THEREOF CONTAINED IN INSTRUMENT RECORDED UNDER KING COUNTY RECORDING NUMBER 20070925001770. (Containing 4,505 square feet, more or less) Project Name: FEDERAL WAY ARCO March 18, 2017 Page 2 BDG/stm 16777L.001.doc Exhibit A-1 r 11' RIGHT-OF-WAY DEDICATION � I cV 1 Ir Ii S. 356TH ST SCALE. For: HORIZONTAL 1 "=100' VERTICAL N/A &9Akj 18215 72ND AVENUE SOUTH KENT WA 98032 2 (425)251-6222 (425)251-8782 FAX Title: CIVIL ENGINEERING, LAND `�■ 9 PLANNING, SURVEYING, ENVIRONMENTAL SERVICES r J 0 GRAPHIC SCALE o J_ t� CD 0 50 — 100 200 1 " 100 FEET °n ui a� a --t- �0I Q _ x w CL T N zi cn 0 0 0 1 = L` JOB NUMBER ARCO 16777 FEDERAL WAY 16777L.001.UOC SHEEP DEDICATION Ri N v w 3 a_ V ...i ce o m %S D LO m C) f+i e r L C a 7S `gyp _ V m U a 1 Oj 2 'nCN 33.INV21'JCD MAOR , N � T m' �t 0 y Co r- r- co °' ❑ c g Ln uj c 3 m Q e Q Y 2 a m t 8 to yu�y� a m 6L m U ca m C � � E •� T C O 7iO1Nvt10 C z i v �13'ITdS u � C C O E C N C N m u c � u o ' V u�i .r 3 � � 0 0. o Q cn Q X O 6 a L' L O O � 0 U v O R y O 00. A P -� a U i.I h m _a V Q R 3 0. e C ar e0i u �o W R C G oN 'a o R T Y � u R � O � }❑ o �Mz vs lu , ❑ 0 0 8 O O G VI H V/ VI VI fA ••C�OII To 1 �L o 'W w •� K7 e» �% L x x W O _ C 7 R c R V 0 to C p Lr� V � T vl o — Q