12-1020340
j
8
AMER,..,ICA FEDERAL WAY
WA-TAC161M10.4-A
30911 PACIFIC HIGHWAY SOUTH
FEDERAL WAY, WA 98003
PROJECT INFORMATION
PROJECT DESCRIPTION:
CLEARWIRE PROPOSES TO ADD (1) 2'-0" MICROWAVE DISH TO SECTOR 13 ON EXISTING 154'-0"AGL STEEL MONOPOLE.
APPLICANT:
CLEARWIRE, LLC
1475 120TH AVE NE
BELLEVUE, WA 98005
CONTACT: FRANK WIGNER
PH: (206) 423-6685
CODE INFORMATION:
ZONING CLASSIFICATION: BC
BUILDING CODE: 2009 IBC
CONSTRUCTION TYPE: IIB
OCCUPANCY: S-2
JURISDICTION: CITY OF FEDERAL WAY
CURRENT USE: TELECOMMUNICATION
PROPOSED USE: MICROWAVE AUGMENT
TELCO COMPANY:
CENTURY LINK
PH: (800) 777-9594
POWER COMPANY:
PSE
PH: (425) 452-1234
SITE LOCATION: (BASED ON NAD 83
LATITUDE: 47• 19' 29.0" N
LONGITUDE: 122• 18' 48.0" W
TOP OF STRUCTURE AGL: 154'-0"
BASE OF STRUCTURE AMSL: 460' t
PARCEL NUMBER(S):
0821049064
ZONE: BC
AREA OF PARCEL:
31983 S.F. (0.73 ACRES)
PROJECT AREA:
42 S.F. EXISTING EQUIPMENT LEASE AREA
PROJECT TEAM
PROJECT ARCHITECT
RICHARD B. HALL, AIA
PACIFIC TELECOM SERVICES, LLC
111 SOUTH JACKSON, STE 200
SEATTLE, WA 98104
CONTACT: PAUL DANNEBERG
PH: (206) 464-4413
EMAIL: PDANNEBERG@PTSWA.COM
PROPERTY OWNER:
T"BD
TOWER OWNER:
AMERICAN TOWER CORPORATION
116 HUNTINGTON AVE, 11TH FLOOR
BOSTON, MA 02116
CONTACT: GEORGE GLINATSIS
PH: (303) 885-0501
PROJECT LEAD:.
CLEARWIRE, LLC
1475 120TH AVE NE
BELLEVUE, WA 98005
CONTACT: FRANK WIGNER
PH: (206) 423-6685
ITE ACQUISITION:
WESTOWER
7525 SE 24TH STREET #500
MERCER ISLAND, WA 98040
CONTACT: AMANDA NATIONS
PH: (206) 496-2294
PERMITTING:
WESTOWER
7525 SE 24TH STREET #500
MERCER ISLAND, WA 98040
CONTACT: JENNIFER TAYLOR
PH: (206) 228-2127
CONSTRUCTION MANAGER:
WESTOWER
7525 SE 24TH STREET #500
MERCER ISLAND, WA 98040
CONTACT: LEONARD MILLS
PH: (425) 508-0093
GENERAL INFORMATION:
1. PARKING REQUIREMENTS ARE UNCHANGED.
2. TRAFFIC IS UNAFFECTED.
3. SIGNAGE IS PROPOSED.
VICINITY MAP
w
a 30SRD ST
S 30 4TH 8T
�' 07
Co
-A
308TH LN
S 303TH PI
i
S��2TB 5'T
313TH ST
41 <
'
1:�; 1
I
30�Ni� ST
S 302N PL
S 302ND PL
Iv
S
a�
0 C1
S 3C411 ST
S30TH PL�eCN
Lake
..w . WH GT
S 30 TH ST
a �
-
w
{
r r,
r
SffH PL
r
IN
Felleral Way
DRIVING DIRECTIONS
FROM CLEARWIRE OFFICE (BELLEVUE. WA):
DEPART 120TH AVE NE TOWARD NE 12TH ST
0.4
MI
TURN RIGHT ONTO BEL-RED RD
0.1
MI
BEAR RIGHT ONTO NE 8TH ST
0.4
MI
TAKE RAMP RIGHT FOR 1-405 SOUTH TOWARD RENTON
13.9
MI
ROAD NAME CHANGES TO WA-518 WEST
0.1
MI
TAKE RAMP RIGHT FOR 1-5 SOUTH TOWARD PORTLAND
7.6
MI
AT EXIT 147, TAKE RAMP RIGHT AND FOLLOW SIGNS FOR S. 272ND
ST. 0.3
MI
TURN RIGHT ONTO S 272ND ST
0.6
MI
TURN LEFT ONTO WA-99 / PACIFIC HWY S
0.5
MI
KEEP STRAIGHT ONTO WA-99 / WA-509 / PACIFIC HWY S
1.1
MI
KEEP STRAIGHT ONTO WA-99 / PACIFIC HWY S
0.8
MI
ARRIVE AT 30911 PACIFIC HWY S, FEDERAL WAY, WA 98003
APPROVAL DATE
SIGNATURE
CLEARWIRE:
LANDLORD:
CONST:
S/A:
R. F.:
ZONING:
A& E:
B.H..
REVIEWERS SHALL CLEARLY PLACE INITIALS ADJACENT TO EACH
REDLINE NOTE AS
DRAWINGS ARE BEING REVIEWED
r'TAI"111 Mk/ AIATI If7f- AAI\/ I ICf" nD nicri nci IPF nTHP_R THAN THAT WHI(:H RFI ATFS TO CARRIER SERVICES IS STRICTLY PROHIBITED.
THE INFORMATION CONTAINED IN IRIS 5tl Ur UUIVJIKUUIIUiN UU�,uiviu141a iI) FIA
DRAWING INDEX
SHEET
ICONTENTS
T-1
TITLE SHEET
G-1
GENERAL NOTES
A-1
SITE PLAN
A-2
ENLARGED SITE PLAN
A-3
PROPOSED & EXISTING ANTENNA
LAYOUTS
PROPOSED & EXISTING SOUTH
A-4
ELEVATION
A-5
CONSTRUCTION DETAILS
RF-1
RF INFORMATION AND DETAILS
RF-2
SWEEP TEST
E-1
GROUNDING SCHEMATIC
E-2
GROUNDING DETAILS
E-3
ELECTRICAL DETAILS
PROPRIETARY INFORMATION
THE INFORMATION CONTAINED IN THIS SET OF
CONSTRUCTION DOCUMENTS IS PROPRIETARY BY NATURE.
ANY USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO CARRIER SERVICES IS STRICTLY PROHIBITED.
LEGAL DESCRIPTION
mm
NOTES
1. (2) RUNS OF FIBER CABLE TO BE INSTALLED WITHIN
INTERIOR OF THE EXISTING MONOPOLE
ABBREVIATIONS
A/C
AIR CONDITIONING
HORZ
HORIZONTAL
PLYWD
PLYWOOD
AGL
ABOVE GROUND LEVEL
HR
HOUR
PROJ
PROJECT
APPROX
APPROXIMATELY
HT
HEIGHT
PROP
PROPERTY
HVAC
HEATING
PT
PRESSURE TREATED
BLDG
BUILDING
VENTILATION
BLK
BLOCKING
AIR CONDITIONING
REQ
REQUIRED
RM
ROOM
CLG
CEILING
ID
INSIDE DIAMETER
RO
ROUGH OPENING
CLR
CLEAR
IN
INCH
CONC
CONCRETE
INFO
INFORMATION
SHT
SHEET
CONST
CONSTRUCTION
INSUL
INSULATION
SIM
SIMILAR
CONT
CONTINUOUS
INT
INTERIOR
SPEC
SPECIFICATION
IBC
INTERNATIONAL
SF
SQUARE FOOT
DBL
DOUBLE
BUILDING CODE
SS
STAINLESS STEEL
DIA
DIAMETER
STL
STEEL
DIAG
DIAGONAL
LBS
POUNDS
STRUCT
STRUCTURAL
DIN
DOWN
STD
STUD
DET
DETAIL
MAX
MAXIMUM
SUSP
SUSPENDED
DWG
DRAWING
MECH
MECHANICAL
MTL
METAL
THRU
THROUGH
EA
EACH
MFR
MANUFACTURE
TNNG
TINNED
ELEV
ELEVATION
MGR
MANAGER
TYP
TYPICAL
ELEC
ELECTRICAL
MIN
MINIMUM
EQ
EQUAL
MISC
MISCELLANEOUS
LINO
UNLESS NOTED OTHERWISE
EQUIP
EQUIPMENT
EXT
EXTERIOR
NA
NOT APPLICABLE
VERT
VERTICAL
NIC
NOT IN CONTRACT
VIF
VERIFY IN FIELD
FIN
FLUOR
FINISH
FLOURESCENT
NTS
NOT TO SCALE
W/
WITH r'*- E CtE- I I '`�
FLR
FLOOR
OC
ON CENTER
W/0
WITHOUT
FT
FOOT
OD
OUTSIDE DIAMETER
WP
WATER PROOF
MAY o s 2012
GA
GAUGE
GALV
GALVANIZED
CITY OF FEDERAL WAY
GC
GENERAL CONTRACTOR
GRIND
GROUND
CDS
GYP BD
GYPSUM WALL BOARD
clear
1475 120TH AVE NE
BELLEVUE, WA 98005
PACIFIC TELECOM SERVICES,
LLC
111 South Jackson, Suite 200
Seattle, WA. 98104
Phone: (206) 342-9000 Fax: (206) 903-8513
8828 REGISTERED
ARCHITECT
RICHARD HALL
STATE OF WASHINGTON
EXPIRATION DATE OF THE
LICENSE: 08/20113
h�
H-
w00
Q 0-)
Q
i U
Miy � LL
U w
Q Q
� w
Iw
0 LL
0
r�
h�
REVISIONS
NO.
DATE
DESCRIPTION
INITIAL
A
02/24/12
ISSUED FOR SITE PCD
BW
B
03/09/12
FINAL CONSTRUCTION DOCUMENTS
PHD
C
05/03/12
SUBMITTAL SET
PHD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
'AL
SHEET TITLE
TITLE SHEET
SHEET NUMBER
T-1
Pandit Number: 21 OZb
AwoveO`By:.,.
=fin
GENERAL NOTES:
1. ALL CONSTRUCTION AND MATERIALS SHALL COMPLY WITH
THE "INTERNATIONAL BUILDING CODE 2009" AND CITY
CODE, SHALL MEET OR EXCEED THE STRICTER OF
APPLICABLE COUNTY CODES AND REGULATIONS, LATEST
EDITIONS.
2. ANTENNAS, CABINETS AND COAXIAL CABLE SHALL BE
PROVIDED BY CLIENT. CONTRACTOR SHALL
COORDINATE SCHEDULE OF DELIVERY TO AVOID DELAYS.
3. DAMAGE TO ALL UTILITIES, LAND, DRIVEWAY AREAS, AND
PROPERTY OF OTHERS, DISTURBED DURING
CONSTRUCTION, SHALL BE RETURNED TO THE ORIGINAL
CONDITION AT THE COMPLETION OF WORK.
4. CONTRACTOR SHALL COORDINATE WITH THE LOCAL POWER,
TELEPHONE UTILITIES, AND THE CONSTRUCTION
MANAGER TO CONFIRM THE SOURCE OF SERVICE PRIOR
TO INSTALLATION OF CONDUITS.
5. NOT USED.
6. NOT USED.
7. ALL WORK SHALL BE DONE SATISFACTORY IN A
PROFESSIONAL WORKMANLIKE MANNER, SUBJECT TO
INSPECTION DURING THE CONSTRUCTION AND FINAL
APPROVAL BY THE CONSTRUCTION MANAGER.
8. ANY SUBSTITUTIONS OF MATERIALS, EQUIPMENT OR
ALTERATIONS FROM THE PLANS AND/OR SPECIFICATIONS
SHALL BE APPROVED BY THE CONSTRUCTION MANAGER.
9. COLOR SELECTION SHALL BE COORDINATED WITH
CONSTRUCTION MANAGER.
10. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS,
DIMENSIONS, AND BRING DISCREPANCIES TO THE
ATTENTION OF THE CONSTRUCTION MANAGER.
11. NOT USED.
12. CONTRACTOR SHALL SECURE THE NECESSARY PERMITS
FOR THIS PROJECT FROM ALL APPLICABLE
GOVERNMENT AGENCIES. CONTRACTOR SHALL BE
RESPONSIBLE FOR ABIDING BY ALL THE CONDITIONS
AND REQUIREMENTS OF THE PERMITS.
13. NOT USED.
14. CONTRACTOR SHALL VISIT THE PROJECT SITE TO VIEW ALL
CONDITIONS PRIOR TO SUBMITTING BID. ANY CHANGES
DURING CONSTRUCTION VISUALLY ASCERTAINABLE PRIOR
TO SUBMITTING BID, CANNOT BE THE BASIS FOR A
CHANGE ORDER.
15. COAT ALL SURFACES WITH NO-OX WHERE DISSIMILAR
METALS CONTACT.
16. CONTRACTOR SHALL REMOVE ALL DEBRIS AND EMPTY
COAX REELS FROM THE SITE UPON COMPLETION OF
THE PROJECT.
PROJECT NOTES:
REINFORCED CONCRETE:
R-1. NOT USED.
R-2. PREPARATION, TESTING, AND PLACING OF CONCRETE
AND REINFORCEMENT SHALL BE PER ACI-318
BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE, LATEST EDITION.
R-3. NOT USED.
R-4. NOT USED.
DESIGN:
D-1. DESIGN IS IN ACCORDANCE WITH THE INTERNATIONAL
BUILDING CODE 2009.
D-2. EQUIPMENT CABINET LOADING PER CLEARWIRE
STANDARD EQUIPMENT.
D-3. DESIGN LOADS: WASHINGTON STATE
SEE STRUCTURAL CALCULATIONS.
STRUCTURAL STEEL:
S-1. DETAIL, FABRICATE, AND ERECT ALL STRUCTURAL STEEL
IN ACCORDANCE WITH AISC, SPECIFICATION FOR
DESIGN, FABRICATION AND ERECTION OF
STRUCTURE STEEL FOR BUILDINGS.
S-2. ALL STRUCTURAL STEEL WORK SHALL CONFORM TO THE
AISC SPECIFICATION FOR STRUCTURAL STEEL FOR
BUILDINGS - ALLOWABLE STRESS DESIGN AND
PLASTIC DESIGN, 9th EDITION.
S-3. STRUCTURAL PIPE COLUMNS SHALL COMPLY WITH ASTM
A53. TYPE E OR S, GRADE B, Fy = 36KS1.
ALL WIDE FLANGE SHAPES SHALL BE ASTM A992.
GRADE 50. ALL STRUCTURAL SHAPES AND PLATE
SHALL COMPLY WITH ASTM A36.
S-4. WELDING: ALL WELDING IS TO BE DONE BY
PRE -QUALIFIED WELDERS HOLDING CURRENT
CERTIFICATE FROM A RECOGNIZED TESTING
LABORATORY. ALL WELDS SHALL BE 3/16"
MINIMUM FILLET WELDS U.O.N. ELECTRODES SHALL
BE E70XX.
S-5. THERE SHALL BE NO FIELD WELDING.
S-6. STRUCTURAL GROUT SHALL BE SHRINKAGE RESISTANCE
NON -EXPANSIVE, NONMETALLIC GROUT WITH A
MINIMUM 28 DAY COMPRESSIVE STRENGTH OF
5,000 PSI WHEN TESTED IN ACCORDANCE WITH
ASTM CODE C109. FORMS SHALL BE PLACED
AROUND BASE PLATE AND THE STRUCTURAL
GROUT SHALL BE POURED. NO DRY -DAMP
PACKING.
S-7. ANCHOR BOLTS AND ALL -THREAD RODS SHALL COMPLY
WITH ASTM A36, UNLESS OTHERWISE NOTED. ALL
OTHER BOLTS AND NUTS SHALL COMPLY WITH
ASTM A325. ALL BOLTS SHALL BE HOT -DIPPED
GALVANIZED.
S-8. ALL EXPOSED STEEL SHALL BE HOT -DIPPED
GALVANIZED AFTER FABRICATION PER ASTM A153
OR A123.
S-9. APPLY TWO COATS OF ZINC -RICH RUST-OLEUM #2185
PAINT TO ALL FIELD DRILLED HOLES AND CUTS.
GRID -GUARD EPDXY #5465 COATING SHALL BE
APPLIED TO ALL AREAS WHERE GALVANIZED
SURFACES NEED TO BE RECONDITIONED,
INCLUDING ALL WELD AREAS.
ELECTRICAL NOTES:
1. ALL ELECTRICAL WORK SHALL CONFORM TO THE
REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE
(NEC) AS WELL AS APPLICABLE STATE AND LOCAL
CODES.
2. ALL ELECTRICAL ITEMS SHALL BE UL APPROVED OR LISTED
AND PROCURED PER SPECIFICATION REQUIREMENTS.
3. THE ELECTRICAL WORK INCLUDES ALL LABOR AND MATERIAL
DESCRIBED BY DRAWINGS AND SPECIFICATIONS,
INCLUDING INCIDENTAL WORK TO PROVIDE COMPLETE,
OPERATING AND APPROVED ELECTRICAL SYSTEM.
4. GENERAL CONTRACTOR SHALL PAY FEES FOR PERMITS, AND
IS RESPONSIBLE FOR OBTAINING SAID PERMITS, AND
COORDINATION OF INSPECTIONS.
5. ELECTRICAL AND TELCO WIRING BETWEEN CABINETS SHALL
RUN IN EMT OR SCHEDULE 40 PVC (AS PERMITTED BY
CODE).
6. ELECTRICAL AND TELCO WIRING OUTSIDE A BUILDING AND
EXPOSED TO WEATHER SHALL BE IN WATER TIGHT
GALVANIZED RIGID STEEL CONDUITS AND WHERE
REQUIRED IN LIQUID TIGHT FLEXIBLE METAL OR PVC
WHERE LOCAL CODES AND SITE CONDITIONS PERMIT.
7. ELECTRICAL WORK SHALL BE COPPER WITH TYPE XHHW,
THWN, OR THIN INSULATION.
8. RUN ELECTRICAL CONDUIT BETWEEN ELECTRICAL UTILITY
DEMARCATION POINT AND EXISTING METER SOCKET AS
LOCATED ON THIS DRAWING IN PVC, PROVIDE FULL
LENGTH PULL ROPE. COORDINATE INSTALLATION WITH
UTILITY COMPANY.
9. RUN TELCO CONDUITS BETWEEN TELEPHONE UTILITY
DEMARCATION POINT AND EXISTING TELCO CABINET AND
CLEARWIRE CABINET AS INDICATED ON THIS DRAWING IN
PVC. PROVIDE FULL LENGTH PULL ROPE IN TELCO
CONDUIT.
10. ALL EQUIPMENT LOCATED OUTSIDE SHALL HAVE NEMA 3R
ENCLOSURE.
11. IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO
APPLY FOR COMMERCIAL POWER IMMEDIATELY UPON
RECEIVING AWARD OF BID. THE GENERAL CONTRACTOR
IS REQUIRED TO KEEP ALL RECEIPTS FROM THE POWER
COMPANY ACKNOWLEDGING APPLICATION FOR POWER
AND THOROUGH DOCUMENTATION OF ANY DISCUSSIONS
WITH THE POWER COMPANY THEREAFTER. ALSO, THE
GENERAL CONTRACTOR SHALL RECEIVE IN WRITING FROM
THE POWER COMPANY AS TO WHEN THE ANTICIPATED
POWER CONNECTION WILL BE COMPLETE. IF
COMMERCIAL POWER IS NOT AVAILABLE BY THE "POWER
COMPLETE" DATE AS CALLED OUT IN THE
SPECIFICATIONS, A GENERATOR SHALL BE SUPPLIED AND
MAINTAINED BY THE GENERAL CONTRACTOR UNTIL
COMMERCIAL IS OBTAINED, ALL COSTS ASSOCIATED WITH
THE GENERATOR WILL BE MUTUALLY AGREED UPON
BETWEEN THE OWNER AND GENERAL CONTRACTOR, IN
THE EVENT THAT THE GENERAL CONTRACTOR FAILS TO
TAKE THE NECESSARY MEASURES AS DESCRIBED HEREIN
TO SECURE POWER BY THE POWER COMPLETION DATE,
THEN ALL COSTS ASSOCIATED WITH THE GENERATOR
SHALL BE BORNE BY THE CONTRACTOR.
TPF INFnRnnATInN (:ONTAINFn IN THIS SFT OF CONSTRUCTION DOCUMENTS IS PROPRIFTARY RY NATURE ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RFI ATFS Tn CARRIER qFR\/IrF(-, IC CTRIrTI V PW)WIRITrm
GROUNDING NOTES:
1. AN ANTIOXIDANT COMPOUND SHALL BE APPLIED TO ALL
EXTERIOR, ABOVE GRADE, MECHANIC, GROUND
CONNECTIONS.
2. CONTRACTOR SHALL SUPPLY ALL MATERIAL, LABOR, AND
EQUIPMENT NECESSARY FOR A COMPLETE SYSTEM AS
INTENDED HEREIN UNLESS OTHERWISE NOTED.
3. ALL EXTERNAL GROUND CONDUCTORS SHALL BE #2
AWG, BARE, SOLID, TINNED COPPER UNLESS
OTHERWISE NOTED.
4. ALL GROUND CONNECTIONS SHALL BE MADE WITH
EXOTHERMIC WELD PROCESS UNLESS OTHERWISE
NOTED OR APPROVED. ALL CONNECTIONS SHALL BE
MADE AT DESIGNATED LOCATIONS ON THE
EQUIPMENT.
5. EXACT LOCATION OF GROUND RODS AND GROUND
CONNECTION POINTS SHALL BE DETERMINED IN THE
FIELD, ADJUST LOCATIONS AS REQUIRED TO KEEP
GROUND CONNECTIONS AS SHORT AS POSSIBLE (9"
MIN. BEND RADIUS AND 90 DEGREE MAX BEND
ANGLE). ALL BELOW GRADE GROUNDING SHALL BE
INSPECTED AND APPROVED BY CONSTRUCTION
MANAGER PRIOR TO BACKFILLING.
6. ALL GROUND COMPONENTS SHALL BE INSTALLED WITHIN
THE CONFINES OF THE FENCED AREA. ANY
METALLIC ITEMS WITHIN 6' OF THE GROUND RING
SHALL BE BONDED TO THE GROUND RING.
GROUNDING REQUIREMENT NOT SHOWN ON PLANS
ARE WAVEGUIDE HATCH COVER / PLATE, CABLE
TRAYS, SUPPORTS, SERVICE PANELS, DISCONNECT
SWITCHES, HVAC UNITS ETC. THESE ITEMS MUST BE
GROUNDED.
7. ALL EXTERIOR EXPOSED GROUND CONDUCTORS LONGER
THAN 18" SHALL BE PROTECTED AND SUPPORTED
BY A 3/4" PVC SCHEDULE 80 CONDUIT SLEEVE
MOUNTED WITH CLIC-STRAP SUPPORTS FROM 6"
BELOW FINISHED GRADE TO 6" FROM FINAL
CONNECTION.
8. ALL GROUND RODS SHALL BE DRIVEN STRAIGHT DOWN,
PERPENDICULAR TO FINISHED GRADE, SUITABLE
PROTECTION SHALL BE PROVIDED ON END OF RODS
TO PREVENT MUSHROOMING WITH GROUND DURING
INSTALLATION.
9. GROUND CONDUCTORS SHALL NOT COME IN CONTACT
WITH THE SLAB OR TOWER EXCEPT AS DESIGNATED.
10. THE UTILITY NEUTRAL / GROUND BOND IS TO BE MADE
IN THE METER OR MAIN DISCONNECT SWITCH, NOT IN
ATS.
11. ALL EQUIPMENT SURFACES TO BE BONDED TO
GROUNDING SYSTEM SHALL BE STRIPPED OF ALL
PAINT AND DIRT, CONNECTIONS TO VARIOUS METALS
SHALL BE A TYPE AS TO NOT CAUSE A GALVANIC
OR CORROSIVE REACTION AREA SHALL BE REPAINTED
FOLLOWING BONDING.
c I ear
1475 120TH AVE NE
BELLEVUE, WA 98005
PACIFIC TELECOM SERVICES,
LLC
111 South Jackson, Suite 200
Seattle, WA. 98104
Phone: (206) 342-9000 Fax: (206) 903-8513
8828 REGISTERED
ARCHITECT
kICHARD B. ALL
STATE OF WASHINGTON
EXPIRATION DATE OF THE
LICENSE: 08/20/13
I-
V• O W O o , 05
Q OF)
� Q
0
w _�
F"'r.y fi
U J
Q Q
w
W
O
REVISIONS
NO.
DATE
DESCRIPTION
INITIAL
A
02/24/12
ISSUED FOR SITE PCD
BW
B
03/09/12
FINAL CONSTRUCTION DOCUMENTS
PHD
C
05/03/12
SUBMITTAL SET
PHD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
SHEET TITLE
GENERAL NOTES
SHEET NUMBER
G-1
clear
1475 120TH AVE NE
BELLEVUE, WA 98005
�r
PACIFIC TELECOM SERVICES,
LLC
111 South Jackson, Suite 200
Seattle, WA. 98104
Phone: (206) 342-9000 Fax: (206) 903-8513
8828 REGISTERED
ARCHITECT
ICHARD6—Wk LI
STATE OF WASHINGTON
EXPIRATION DATE OF THE
LICENSE: 08/20/13
REVISIONS
NO.
DATE
DESCRIPTION
INITIAL
A
02/24/12
ISSUED FOR SITE PCD
BW
B
03/09/12
FINAL CONSTRUCTION DOCUMENTS
PHD
C
05/03/12
SUBMITTAL SET
PHD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
SHEET TITLE
SITE PLAN
SHEET NUMBER
A-1
EXISTING COMPOUND ACCESS GATE
EXISTING WATER METER
EXISTING CHAIN LINK FENCE
EXISTING GENERATOR
EXISTING 154'-0" HIGH MONOPOLE
EXISTING CONCRETE SLAB
PROPOSED 2'-0" MICROWAVE ANTENNA
MOUNTED TO EXISTING DAVIT ARM
EXISTING POWER PULL BOX
(SOURCE OF CLS POWER) -
X X X X X
PROPOSED (2) 1/2" RUNS WITHIN
EXISTING FLEX CONDUIT
EXISTING CLEARWIRE METER
AND TELCO BOX
EXISTING CLEARWIRE EQUIPMENT CABINET MOUNTED
ON EXISTING PRE —CAST CONCRETE PAD WITHIN
EXISTING CLEARWIRE 6'-0"x7'—O" LEASE AREA
—
X X X
\1"_—EXISTING GRAVEL
DRIVE
11 \
II �-
- x x x x x x x x x x x x x x x x
X X X X X X
X X X
NOTES:
1. (2) RUNS OF FIBER CABLE TO BE
INSTALLED WITHIN INTERIOR OF THE EXISTING
MONOPOLE
EXISTING ICE BRIDGE
North to be determined by
site survey (if possible).
24"x36" SCALE: 3/8" = 1'-0" �� I
1 1 "x 17" SCALE: 3/ 16" = 1'-0" 2' 1 ' 0" 2' ENLARGED SITE PLAN 1
FHE INFORMATION CONTAINED IN THIS SET OF CONS I KUC I IUN IJU(;uMtN I �5 IS HNUNKItIANY bT NAI UKt. AIN T UJt UM UIJULUJURC U I MLR 1 M MIN I 171/11 YYFM 1 RGLMI CJ 1 U U/1RRIGR JLRVIUGJ 10 0 1 RIU 1 LI rRUfIIDI I CU.
clear �a.r r
1475 120TH AVE NE
BELLEVUE, WA 98005
PACIFIC TELECOM SERVICES,
LLC
111 South Jackson, Suite 200
Seattle, WA. 98104
Phone: (206) 342-9000 Fax: (206) 903-8513
8828 REGISTERED
ARCHITECT
RICHARD B. HALL
STATE OF WASHINGTON
EXPIRATION DATE OF THE
LICENSE: 08/20113
I—
wo �00
.�
�Q
0�
w � =Q
U J
0 Q
I W
Q
0 LL
O
REVISIONS
NO.
DATE
DESCRIPTION
INITIAL
A
02/24/12
ISSUED FOR SITE PCD
BW
B
03/09/12
FINAL CONSTRUCTION DOCUMENTS
PHD
C
05/03/12
SUBMITTAL SET
PHD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
SHEET TITLE
EXISTING & PROPOSED
EQUIPMENT & ANTENNA PLAN
SHEET NUMBER
A-
NOTES:
1. (2) RUNS OF FIBER CABLE TO BE
INSTALLED WITHIN INTERIOR OF THE EXISTING
MONOPOLE
Q
a
00 00
W U
W
EXISTING CLEARWIRE 2'-0" 0
MICROWAVE ANTENNA (TO REMAIN) EXISTING CLEARWIRE 2'-0" 0MICROWAVE ANTENNA (TO REMAIN)
EXISTING CLEARWIRE QUAD PANEL EXISTING CLEARWIRE QUAD PANEL
ANTENNA WITH RRU EQUIPMENT ANTENNA WITH RRU EQUIPMENT
(TO REMAIN)
(TO REMAIN)
EXISTING MW
SECTOR A EXISTING MW
SECTOR A
.....................
..........._.___.
EXISTING 154'-0" HIGH
MONOPOLE EXISTING 154'-0" HIGH
MONOPOLE
0 0
� o
EXISTING CLEARWIRE DAVIT ARM EXISTING CLEARWIRE DAVIT ARM
ANTENNA MOUNT (TO REMAIN) ANTENNA MOUNT (TO REMAIN)
EXISTING CLEARWIRE QUAD
PANEL ANTENNA WITH RRU EXIS-I.ING CLEARWIRE QUAD
EQUIPMENT (TO REMAIN) ANTENNAPANEL U
EQUIPMENT(TO REMAIN)
EXISTING CLEARWIRE QUAD PANEL ANTENNA WITH RRU EXISTING CLEARWIRE QUAD
PANEL ANTENNA WITH RRU
EQUIPMENT (TO REMAIN) 0 O O 0 O
EQUIPMENT (TO REMAIN) 0 O
0
0
G
G�° p
-- �� 72o•R 9 SF-G�y�° S"
�20 R 6
EXISTING MW EXISTING MW
SECTOR C EXISTING CLEARWIRE 3'-0" 0 SECTOR C
X MICROWAVE ANTENNA (TO REMAIN) x EXISTING CLEARWIRE 3'-0" 0
MICROWAVE ANTENNA (TO REMAIN)
EXISTING CLEARWIRE oZ 0
EXISTING CLEARWIRE - c�
2 -0 MICROWAVE 2 -0 0 MICROWAVE
ANTENNA (TO REMAIN) G �G kp- ANTENNA (TO REMAIN) 032
PROPOSED 8'-0" 3" OD)
PIPE MOUNT AT EXISTING-5
DAVIT ARM 2
-5
PROPOSED CLEARWIRE 7
2'-0"0 MICROWAVE ANTENNA RF-1
North to be determined by
site survey (if possible). North to be determined by
site survey (if possible).
24"x36" SCALE: 1" = 1'-0" PROPOSED ANTENNA LAYOUT 2 24"x36" SCALE: 1"
1 1 "x 17" SCALE: 1 /2" = 1 '-0IS"" 1 ' " 0" 1 ' 1 1 "x 17" SCALE: 1 /2" - 1 '-O" 1, 6" 0" 11
EXISTING ANTENNA LAYOUT 1 THE INFORMATION CONTAINED IN THIS SET OF CONSTRUCTION DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO CARRIER SERVICES IS STRICTLY PROHIBITED.
clear ; ` I
1475 120TH AVE NE
BELLEVUE, WA 98005
PACIFIC TELECOM SERVICES,
LLC
111 South Jackson, Suite 200
Seattle, WA. 98104
Phone: (206) 342-9000 Fax: (206) 903-8513
8828 REGISTERED
/ ARCHITECT
ICHARD B. HALL
STATE OF WASHINGTON
EXPIRATION DATE OF THE
LICENSE: 08/20113
V• O OU
w o �00
Q 0-)
Q
w =Q
U J
Q Q
I n W
w
0 Li
0
REVISIONS
NO.
DATE
DESCRIPTION
INITIAL
A
02/24/12
ISSUED FOR SITE PCD
BW
B
03/09/12
FINAL CONSTRUCTION DOCUMENTS
PHD
C
05/03/12
SUBMITTAL SET
PHD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
SHEET TITLE
EXISTING & PROPOSED
NORTH ELEVATION
SHEET NUMBER
NOTES:
1. (2) RUNS OF FIBER CABLE TO BE
INSTALLED WITHIN INTERIOR OF THE EXISTING
MONOPOLE
TOP OF EXISTING MONOPOLE
>J, TOP OF EXISTING MONOPOLE
154 —0 f AGL
154'—O" f AGL
...............
PROPOSED 8'-0" (3" OD) PIPE 1 2
MOUNT AT EXISTING DAVIT ARM
EXISTING CLEARWIRE 2'-0"
II
I
MICROWAVE ANTENNA (TO REMAIN)
EXISTING CLEARWIRE 3'-0"0
EXISTING CLEARWIRE 2'-0"0
MICROWAVE ANTENNA (TO REMAIN)
MICROWAVE ANTENNA (TO REMAIN)
EXISTING CLEARWIRE 3'-0"0
MICROWAVE ANTENNA (TO REMAIN)
OL RAD CENTER OF EXISTING CLEARWIRE MICROWAVE ANTENNAS
— — — —
140> —0 f AGL
—
0
RAD CENTER OF EXISTING CLEARWIRECRNN
MICROWAVE ANTENNAS
—— —
140' —0"t AGL
i
—
0
RAD CENTER OF EXISTING CLEARWIRE PANEL ANTENNAS
136 >-0 "t AGL — — — —
—
®
__ RAD CENTER OF EXISTING_ CLEARWIRE PANEL ANTENNAS
:I
1367 0" f AGL
RAD CENTER OF PROPOSED CLEARWIRE MICROWAVE ANTENNA
136'-0"f AGL
EXISTING CLEARWIRE QUAD PANEL ANTENNA
I�
I
EXISTING CLEARWIRE QUAD
PANEL ANTENNA WITH RRU
EXISTING CLEARWIRE QUAD PANEL ANTENNA
EXISTING CLEARWIRE
QUADWITH
RRU EQUIPMENT (TO REMAIN)
I
EQUIPMENT (TO REMAIN)
WITH RRU EQUIPMENT (TO REMAIN)
PANE ANTENNAWITH
EQUIPMENT (TO REMAIN)
7 PROPOSED CLEARWIRE 2'-0" 0
I
RF-1 MICROWAVE ANTENNA
I
PROPOSED MICROWAVE RADIO
I;
PROPOSED (2) 1 /2" RUNS WITHIN
I
EXISTING FLEX CONDUIT
' E
-
s I
I
I
EXISTING 154'-0" HIGH MONOPOLE
it
I
I I
I i
I
I
EXISTING 154'-0" HIGH MONOPOLE
i
I
'
EXISTING GENERATOR
I
I
I
I
I
I�
I
I
i
'I
I
I
I
EXISTING GENERATOR
I
EXISTING CLEARWIRE METER
I
AND TELCO BOX
EXIS ING CLEARWIRE METER
EXISTING CHAIN
I
EXISTING CHAIN
AND TELCO BOX
LINK FENCE
I
I
LINK FENCE
EXISTING CLEARWIRE EQUIPMENT CABINET
l
I
MOUNTED ON EXISTING PRE —CAST
II
EXISTING CLEARWIRE EQUIPMENT CABINET
'
CONCRETE PAD WITHIN EXISTING
MOU TED ON EXISTING PRE —CAST
I
CLEARWIRE 6'-0"x7'-0" LEASE AREA
CON RETE PAD WITHIN EXISTING
CL RWIRE 6'-0"x7'-0" LEASE AREA
GRADE
OL
I
i
II
a a
II:
i
I
I
=
d
GRADE
I
—
0.-0.- AGL
a a °
a
a
�
0 —0 AGL
d
O
24"x36" SCALE: 3/16" = 1'-0"
d
d
24"x36" SCALE: 3/16" = 1'-0PROPOSED SOUTH ELEVATION
"x '-0"
2
1 1 17" SCALE: 3/32" = 1 4' 2' 0" 4'
1 1 "x 17" SCALE: 3/32" = 1 '-0" 4' 2' 0" 4
PROHIBITED.
EXISTING
SOUTH ELEVATION 1
THE INFORMATION CONTAINED IN THIS SET OF CONSTRUCTION DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO CARRIER SERVICES IS STRICTLY
1
I
clear . Ill
,
1475 120TH AVE NE
BELLEVUE, WA 98005
PACIFIC TELECOM SERVICES,
LLC
111 South Jackson, Suite 200
Seattle, WA. 98104
Phone: (206) 342-9000 Fax: (206) 903-8513
8828 REGISTERED
ARCHITECT
(CHARD B. HALL
STATE OF WASHINGTON
EXPIRATION DATE OF THE
LICENSE: 08/20/13
F—
V� O O
w o �00
� Q0-)
�Q
w _>
U Q
LL
Q U —1
Q Q
i a- W
W
0) Li
O
REVISIONS
NO.
DATE
DESCRIPTION
INITIAL
A
02/24/12
ISSUED FOR SITE PCD
BW
B
03/09/12
FINAL CONSTRUCTION DOCUMENTS
PHD
C
05/03/12
SUBMITTAL SET
PHD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
SHEET TITLE
EXISTING & PROPOSED
SOUTH ELEVATION
SHEET NUMBER
A-4
ANTENNA CABLING:
1) ACTUAL LENGTHS SHALL BE DETERMINED PER SITE CONDITION BY THE CONTRACTOR.
2) THE DESIGN IS BASED ON THE EMSS REPORT, SIGNED AND APPROVED BY ENGINEERING.
3) THE CONTRACTOR SHALL VERIFY THE ACTUAL LENGTHS OF CABLES BEFORE INSTALLATION.
4) ALL TIE WRAPS SHALL BE CUT FLUSH WITH THE APPROVED CUTTING TOOL FOR SAFETY AND PROTECTION.
5) THE ANTENNAS WILL BE FED BY RF CABLES WHICH MAY BE RUN OUTSIDE OR INSIDE THE TOWER DEPENDENT UPON SITE
CONDITIONS AND ENGINEERING DRAWINGS.
6) ALL SITE CABLING SHALL MAINTAIN MAXIMUM CABLE SEPARATION REQUIREMENTS AS TO THE TYPE OF CABLE AND
FUNCTION. THIS IS DONE TO PROTECT DAMAGE; AS WELL AS; TO PREVENT THE INDUCTION OF CURRENT INTO THE
CONDUCTORS FROM MAGNETIC LINES OF FLUX CREATED FROM POWER AND CURRENTS THROUGH THE CABLES.
7) CABLES SHALL BE PROTECTED FROM DAMAGE AND SHALL HAVE THE MINIMUM BEND RADIUS FOR THE SIZE AND
MANUFACTURER OF THAT CABLE. IN THIS CASE THE MINIMUM BEND RADIUS IS 100MM.
8) SLACK SHALL BE LEFT IN THE CABLES LEAVING THE EQUIPMENT TO THEIR TERMINATION POINTS. THIS IS DONE IN ORDER
TO PROVIDE STRESS RELIEF ON THE CABLES AND CONNECTIONS IN THE EVENT OF SEISMIC ACTIVITY.
9) ALL CABLES SHALL BE ROUTED AND INSTALLED IN A MANNER AS TO PROTECT THE CABLES FROM DAMAGE OF SHARP
EDGES OF HARDWARE AND WHERE CABLES ARE ROUTED DOWN THE TOWER.
10) CABLES SHALL BE SUPPORTED A MINIMUM OF EVERY THREE FEET EXCEPT FOR INSIDE MONOPOLES AND LATTICE TOWERS
WHERE CABLE AND CONNECTOR MANUFACTURERS RECOMMENDED FIBER SUPPORT ACCESSORIES SHALL BE USED IF REQUIRED.
1 1) CABLE BRIDGE SYSTEM SHALL BE USED AS AN ICE SHIELD TO SUPPORT AND PROTECT ANTENNA AND MICROWAVE
CABLES.
12) DRIP LOOPS SHALL BE REQUIRED ON ALL OUTSIDE CABLES. CABLES SHALL BE SLOPED AWAY FROM THE BUILDING OR
OUTDOOR CABINETS TO PREVENT WATER FROM ENTERING THROUGH THE CABLE PORT.
ANTENNA CABLING NOTES6
NOT USED
NOT USED
24"x36" SCALE: NOT TO SCALE
"x17"
24"x36" SCALE: NOT TO SCALE
"x17"
5
24"x36" SCALE: NOT TO SCALE 4
1 1 SCALE: NOT TO SCALE
1 1 SCALE: NOT TO SCALE
1 1 x17" SCALE: NOT TO SCALE
NOTES:
THE FIBER OPTIC CABLE COMES PRE —MANUFACTURED WITH HUBER—SUHNER CONNECTORS INSTALLED ON EACH END. THE
AVAILABLE LENGTHS ARE 20M, 40M, 60M, 80M, 100M.
THE POWER CABLE COMES PRE —MANUFACTURED WITH AN AMPHENOL CONNECTOR FOR USE AT THE DAP HEAD END ONLY. THE
OTHER END OF THE CABLE IS BARE. THE AVAILABLE LENGTHS ARE 20M, 40M, 60M, 80M, 100M.
BRACKET FLANGE
A UNIQUE COMBINED POWER & FIBER OPTIC CABLE (INTEGRATED CABLE 071903-1) HAS BEEN DEVELOPED TO MAKE RUNNING
CABLES EASIER AND MAY BE MADE AVAILABLE IN THE FUTURE. THE POWER CABLE IS LONGER THAN THE FIBER CABLE TO
PREVENT THE FIBER CABLE FROM BEING DAMAGED.
SUPPORT ARM SITE
PRO 1 18
INSTALL THE POWER AND FIBER OPTIC CABLE FROM EACH DAP HEAD TO THE EQUIPMENT CABINET ATTACH THE CABLE END TO
OR APPROVED EEQUAQUAL
THE CONNECTORIZED POWER AND FIBER DAP HEAD CONNECTORS. EACH CABLE SHALL HAVE A SERVICE/DRIP LOOP AT EACH
END OF AT LEASE ONE FULL LOOP NOT SMALLER THAN 6" IN DIAMETER. EXTRA CABLE SHALL BE LOOPED AT THE EQUIPMENT
CABINET.
EXISTING 154'-0" HIGH
CABLE SHALL BE ROUTED FROM EACH DAP HEAD UNIT, ALONG THE ANTENNA MOUNT IN ULTRA —TIGHT NON—METALLIC /LIQUID
MONOPOLE
NEW 8' (3" OD)
TIGHT / FLEXIBLE CONDUCT / SUB —DUCT STRUCTURE TO PROTECT THE CABLES FROM EACH INDIVIDUAL SECTOR.
e
e
MOUNTING PIPE
e
INSTALL TWO 2"0 FLEXIBLE CONDUITS. THE FIRST 2" CONDUIT IS USED TO RUN ALL FIBER AND POWER OPTIC CABLES. THE
EXISTING MICROWAVE
SECOND 2" CONDUIT IS INSTALLED DURING THE INITIAL INSTALLATION BUT IS RESERVED FOR FUTURE GROWTH / USE. THEN
�—ANTENNA
USE OF A KELLEM GRIP PROVIDES ACCEPTABLE CABLE SUPPORT
EXISTING MICROWAVE
THE RF CABLES SHALL BE RUN SEPARATELY OUTSIDE OF THE FLEXIBLE CONDUIT OTHER CABLE RUNNING OPTIONS MAY BE
U—BOLT CONNECTION
ANTENNA
USED BASED ON SITE SPECIFIC REQUIREMENTS. THE INSTALLER SHOULD CONSULT WITH THE CLEARWIRE PROJECT MANAGER
WHO WILL WORK WITH THE TOWER OWNER TO DEVELOP AN APPROPRIATE METHOD PER SITE. FOR CASES WHERE PROTECTIVE
CONDUIT IS NOT INSTALLED, THE USE OF VALMONT MICROFLECT CUSHION HANGER OR APPROVED EQUAL IS RECOMMENDED AS
A WAY TO PREVENT DAMAGE TO THE FIBER OPTIC CABLES.
NEW 8(3" OD)
MOUNTING PIPE
O
O
I'
O
!
O3/8" 0 SCREW
O
7/16"0 HOLE FOR
I
I
3/8"0 HARDWARE
CUSHION HANGER 3/4" 0 HOLE
ASSEMBLY
° (I
SNAP IN HANGER
°
EXISTING CLEARWIRE
PANEL ANTENNA MOUNTED
TO EXISTING PIPE
OO
EXISTING CLEARWIRE °
PANEL ANTENNA
MOUNTED TO
EXISTING PIPE
I
i
4 FIBER ODC PLUG 4 FIBER ODC PLUG
I
HUBER—SUHNER HUBER—SUHNER
EXISTING CLEARWIRE I'
84024249 84024249
BRACKET FLANGE
RRU 7-7
SUPPORT ARM SITE
PROPOSED CLEARWIRE !
t
PRO 1 P/N: SV197-18
2'-0"0 MICROWAVE 71
OR APPROVED EQUAL
ANTENNA
AMPHENOL THIS END NO
PROPOSED MICROWAVE
AL06F13-71 S CONNECTOR
RADIO
NEW 8' (3" OD)
4 FIBER ODC PLUG 4 FIBER ODC PLUG
MOUNTING PIPE
HUBER—SUHNER HUBER—SUHNER
84024249 84024249
0
0o
U—BOLT CONNECTION
AMPHENOL THIS END NO
0 AL06F13-71S CONNECTOR
0
RRU UNIT COAX
T-ARM MOUNT DETAIL
MOUNTING DETAIL
24"x36" SCALE: NOT TO SCALE 3
2
24"x36" SCALE: NOT TO SCALE
"x17"
24"x36" SCALE: NOT TO SCALE 1
1 1 %17" SCALE: NOT TO SCALE
11 SCALE: NOT TO SCALE
1 1 x17" SCALE: NOT TO SCALE
THE INFORMATION CONTAINED IN THIS SET OF CONSTRUCTION DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OI HER I HAN I HAI WHICH RELATES TO CARRIER SERVICES IS STRICTLY PROHIBITED.
�
clear v'� �I
1475 120TH AVE NE
BELLEVUE, WA 98005
PACIFIC TELECOM SERVICES,
LLC
111 South Jackson, Suite 200
Seattle, WA. 98104
Phone: (206) 342-9000 Fax: (206) 903-8513
8828 REGISTERED
ARCHITECT
� s
RICHARD . HALL
STATE OF WASHINGTON
EXPIRATION DATE OF THE
LICENSE: 08/20/13
V• O O
w o Do
Q OF)
Q
U <
Fes, L�
U J
Q Q
� W
W
0 W
r�
REVISIONS
NO.
DATE
DESCRIPTION
INITIAL
A
02/24/12
ISSUED FOR SITE PCD
BW
B
03/09/12
FINAL CONSTRUCTION DOCUMENTS
PHD
C
05/03/12
SUBMITTAL SET
PHD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
SHEET TITLE
CONSTRUCTION DETAILS
SHEET NUMBER
A-5
NOT USED NOT USED NOT USED NOT USED
24"x36" SCALE: NOT TO SCALE 11 24"x36" SCALE: NOT TO SCALE 10 24"x36" SCALE: NOT TO SCALE 9 24"x36" SCALE: NOT TO SCALE 8
1 1 "x17" SCALE: NOT TO SCALE 1 1 "x17" SCALE: NOT TO SCALE 1 1 %17" SCALE: NOT TO SCALE 1 1 "x17" SCALE: NOT TO SCALE
24.0"
OQ -
O
0�
N
tb
12.2"
NOT USED NOT USED NOT USED NOT USED
24"x36" SCALE: NOT TO SCALE 7 24"x36" SCALE: NOT TO SCALE 6 24%36" SCALE: NOT TO SCALE 5 24"x36" SCALE: NOT TO SCALE 4
1 1 "x17" SCALE: NOT TO SCALE 1 1 "x17" SCALE: NOT TO SCALE 1 1 "x17" SCALE: NOT TO SCALE 1 1 x17 SCALE: NOT TO SCALE
SIGNS AND PLACEMENT:
1. LOW LEVEL BLUE NOTICE SIGNS - PLACE AT SITE ENTRY / ACCESS
POINTS ONLY.
- ROOFTOPS: PLACE SIGNS ON THE INSIDE OF ROOF HATCH; PLACE ON 8
ACCESS DOOR UNLESS DOOR IS USED BY GENERAL PUBLIC OR BUILDING
TENANTS ON A REGULAR BASIS FOR ACCESS - IN THESE CASES CONSULT
CONSTRUCTION MANAGER.
- WATER TANKS: PLACE SIGNS ON COMPOUND GATE. NOTICE
- NETWORK CARRIER OWNED SITES: PLACE ONE SIGN ON COMPOUND
GATE; ALL SIGNS SHALL BE SECURED WITH EITHER STAINLESS STEEL ZIP
TIES OR STAINLESS TECH SCREWS. C LEARW R E ANTENNA INFORMATION
2. CONSTRUCTION COORDINATOR PARTICIPATION IN SIGN LOCATION:
NETWORK CARRIER CONSTRUCTION MANAGER SHALL MEET WITH ALL low
CONSTRUCTION COORDINATOR'S TO OUTLINE CRITERIA FOR SIGN PLACEMENT.
EMPHASIS SHALL BE PLACED ON "CHALLENGING" SITES, WHERE THE o
NETWORK CARRIER CONSTRUCTION MANAGERS SHALL GIVE CONSTRUCTION
COORDINATOR'S AS MUCH GUIDANCE ON EACH SPECIFIC SITUATION AS
POSSIBLE, HOWEVER, CONSTRUCTION COORDINATOR'S SHALL BE
SECTOR
ANTENNA
BAND #
AZIMUTH
MODEL
QTY.
DOWNTILT
RAD CENTER
FT. AGL
COAX
LENGTH (f)
B
BLUE
3
150'
-
1
0
136'-0"
160'-0"
GPS ANTENNA LOCATION OPTIONS: (1) EQUIPMENT CABINET; (2) ANTENNA MAST; (3) H-FRAME; FIELD VERIFY
ENCOURAGED TO PARTNER WITH NETWORK CARRIER CONSTRUCTION MANAGER Beyond this point you are entering an area
IN DECIDING PLACEMENT PERTAINING TO CHALLENGING SITES. A SITE VISIT where RF Emissions may exceed the FCC
General Population Exposure Limits
LABEL MARKING SHALL BE PLACED AT:
MAY BE REQUIRED TO FULFILL REQUIREMENTS. CONSTRUCTION COORDINATOR
SHALL IDENTIFY ALL SIGN LOCATIONS AT THE A&E WALK. PLEASE SEE SIGN
1. WITHIN 12" OF CABLE AT BOTH ENDS
DETAIL AND SIZE. Follow all posted signs and site guidelines
2. AT/NEAR TOWER MGB
for working in an RF environment
3. PRIOR TO ENTRY INTO THE CABINET FOR A CABLE SUPPORT BRIDGE
3. SIGN DISBURSEMENT FROM WAREHOUSE:
*COORDINATE BACKHAUL INSTALLATION WITH FINAL ENGS
SIGN INVENTORY SHALL BE ACCESSIBLE AT NETWORK CARRIER WAREHOUSE
TO BE DISBURSED AS PART OF THE GENERAL CONTRACTOR BOM AS CALLED
OUT IN A&E DRAWINGS FOR EACH SITE.
NOTICE SIGNAGE
ANTENNA SCHEDULE
NOT
USED
24"x36" SCALE: NOT TO SCALE 3
24"x36" SCALE: 2
1
NOT TO SCALE
"x17"
24%36" SCALE: NOT
TO SCALE
11 %17" SCALE: NOT TO SCALE
1 1 SCALE: NOT TO SCALE
1 1 "x17 SCALE: NOT
TO SCALE
THE INFORMATION CONTAINED IN THIS SET OF CONSTRUCTION DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO CARRIER SERVICES IS STRICTLY PROHIBITED.
clear w*re'l
1475 120TH AVE NE
BELLEVUE, WA 98005
PACIFIC TELECOM SERVICES,
LLC
111 South Jackson, Suite 200
Seattle, WA. 98104
Phone: (206) 342-9000 Fax: (206) 903-8513
8828 REGISTERED
ARCHITECT
RICHARD B. HALL
STATE OF WASHINGTON
EXPIRATION DATE OF THE
LICENSE: 08/20113
0 rf)
wo Ob
LL-
v �
U J
Q Q
Lli
0 LL
O
LLJ
REVISIONS
NO.
DATE
DESCRIPTION
INITIAL
A
02/24/12
ISSUED FOR SITE PCD
BW
B
03/09/12
FINAL CONSTRUCTION DOCUMENTS
PHD
C
05/03/12
SUBMITTAL SET
PHD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
SHEET TITLE
RF INFORMATION AND DETAILS
SHEET NUMBER
f F-1
EQUIPMENT SPECIFICATIONS:
1) BINOCULARS OR SPOTTING SCOPE, COMPASS, TELESCOPIC ANTENNA POINTING DEVICE, SURVEYOR'S MAP, INCLINOMETER
AND DECLINATION INFORMATION FROM MAGNETIC NORTH.
2) TRANSMISSION LINE TEST EQUIPMENT; MAY BE EITHER OF THE FOLLOWING TEST EQUIPMENT SUITES BUT MUST MATE WITH
BOTH N-TYPE AND DIN -TYPE CONNECTORS
3) PRECISION N-TYPE TERMINATIONS FOR TEST EQUIPMENT CALIBRATION
A) MATCHED LOAD (50 OHM TERMINATION AT PCS/ESMR FREQUENCIES)
B) SHORT LOAD
C) OPEN LOAD
4) PLOTTER/PRINTER OR LAPTOP PC WITH CABLING
5) PRECISION DIN -TYPE TERMINATIONS FOR SWEEP TESTS
A) 7/16 DIN PRECISION SHORT TERMINATION
B) 7/16 DIN PRECISION OPEN TERMINATION
C) 7/16 DIN PRECISION MATCHED LOAD TERMINATION
6) N TYPE PRECISION SHORT TERMINATION (AT GPS FREQUENCIES)
7) TORQUE WRENCH WITH INCREMENTS DOWN TO 5 IN-LBS (NOTE: WHEN USING THE ANRITSU SITE MASTER YOU MUST
BEWARE OF WHAT YOU HAVE THE SITE MASTER MODE SET-UP TO MEASURE. IF THE SITE MASTER MODE IS SET-UP TO
MEASURE RETURN LOSS YOU MUST DIVIDE THE PEAK AND VALLEY MEASUREMENTS BY (4) TO GET THE CORRECT INSERTION
LOSS. IF THE SITE MASTER MODE IS SET-UP TO MEASURE CABLE LOSS YOU MUST DIVIDE THE PEAK AND VALLEY
MEASUREMENTS BY (2) TO GET THE CORRECT INSERTION LOSS.
THE MATHEMATICAL MODEL FOR RL OF EACH CABLE ASSEMBLY (JUMPER, OR MAIN LINE) IS PROVIDED BELOW:
1) CONVERT ALL COMPONENTS VSWR'S TO REFLECTION COEFFICIENT:\
REFF COEFF = (VSWR-1)/(VSWR+1)
2) CALCULATE FEEDER ATTENUATION FACTOR:
ATT FACTOR = EXP(-(ATTENUATION (DB/10OFT)*LENGTH (FT)/434.3)
3) COLLECT CONTRIBUTING REFLECTIONS AT BOTTOM OF SYSTEM
4) MULTIPLY REFLECTION COEFFICIENTS OF TOP COMPONENTS BY ATTENUATION FACTOR FROM STEP 2
5) REFLECTION COEFFICIENTS OF BOTTOM COMPONENTS ARE UNCHANGED
6) DETERMINE RSS (ROOT SUM OF THE SQUARES) OF REFLECTIONS FROM STEP 3
RFF = (REF1-2+REF2-2+REF3-2...... )-.5
7) CALCULATE EXPECTED SYSTEM VSWR AND RETURN LOSS:
VSWR = (1 +RFF)/(1-RFF) RET LOSS = -20*LOG 10(RSS)
TEST EQUIPMENT SUITES
OPTION A OPTION B
WILTRON SITEMASTER S331 CABLE AND SPECTRUM ANALYZER WITH PLOT STORAGE CAPABILITY
ANTENNA ANALYZER OR EQUIVALENT EQUIPMENT (80OMHz-2.1 GHz RANGE) OR APPROVED EQUAL
SPECTRUM ANALYZER (FOR PORT -TO -PORT TESTING) SIGNAL GENERATOR (80OMHz-2.1 GHz RANGE)
SIGNAL GENERATOR (FOR PORT -TO -PORT TESTING) DIRECTIONAL COUPLER (40 dB DIRECTIVITY OR BETTER)
EITHER FFT CAPABILITY FOR THE
SPECTRUM ANALYZER OR TDR EQUIPMENT
EST PR
PRELIMINARY VISUAL INSPECTION
PRIOR TO TRANSMISSION LINE TESTING, A VISUAL INSPECTION IS TO BE PERFORMED TO VERIFY THAT THE CELL SITE IS
PROPERLY CONFIGURED AND READY FOR SWEEP TESTING. THIS INSPECTION VERIFIES THAT PROPER TRANSMISSION LINE
CABLES ARE INSTALLED, THAT ALL JUMPERS HAVE BEEN CONNECTED, AND THAT THE CABLES HAVE NO NOTICEABLE
STRUCTURAL PROBLEMS.
TEST PREPARATION
VERIFY THAT ALL TEST PERSONNEL AND EQUIPMENT ARE PRESENT, INCLUDING TOWER CREW FOR ANTENNA MAST ACCESS.
TESTING SEQUENCE
1) VERIFY THAT THE CORRECT BOTTOM JUMPER IS PRESENT (IF APPLICABLE) AND OF THE PROPER LENGTH AND NOTE IN
THE CHECK OFF SHEET
2) VERIFY THAT THE CORRECT TOP JUMPER IS PRESENT (IF APPLICABLE) AND OF THE PROPER LENGTH AND NOTE IN THE
CHECK -OFF SHEET.
3) VISUALLY CHECK FOR ANY EXCESSIVE JUMPER STRESS CAUSED BY THE BEND RADIUS AT EITHER TOP OR BOTTOM
JUMPER, AND NOTE ANY PROBLEMS IN THE CHECK -OFF SHEET.
4) VERIFY THAT THE CORRECT ANTENNA(S) ARE INSTALLED FOR EACH SECTOR.
5) VISUALLY VERIFY THAT CONNECTIONS BETWEEN JUMPERS AND MAIN FEED LINE ARE MATED.
6) VISUALLY CHECK FOR DENTS, KINKS, OR OTHER OBVIOUS STRUCTURAL PROBLEMS WITH THE FEED -LINE OR JUMPERS.
EXIT CRITERIA
VERIFY THAT THE CABLE AND ANTENNA ARE PROPERTY INSTALLED AND FREE FROM ANY OBVIOUS DEFECTS.
FEED LINE INSERTION LOSS TEST:
TEST
THE INSERTION LOSS VALUES ARE TO BE OBTAINED OVER THE ENTIRE BLOCK ASSIGNED FREQUENCY RANGE (TO AVOID
RE -CALIBRATION FOR DISTANCE -TO -FAULT TEST).
TEST PREPARATION
1) INSTALL A 7/16 DIN SHORTED LOAD INTO THE CONNECTOR AT THE ANTENNA END OF THE TRANSMISSION FEED LINE TOP
JUMPER.
2) VERIFY THE TORQUE SETTING OF THE FEED LINE CONNECTOR WITH THE SHORTED LOAD MATCHES THE MANUFACTURER'S
RECOMMENDATIONS.
3) SET THE TEST EQUIPMENT TO SWEEP THE FREQUENCY RANGE IN USE IN YOUR MARKET.
4) IF THE FIELD ENGINEER PREFERS, THE TOWER GROUNDING AND THE FEED -LINE GROUNDING CAN BE DONE AT THIS
POINT. THIS STEP IS THE FIELD ENGINEER'S PREROGATIVE.
5) SET TRANSMIT POWER TO TEST EQUIPMENT DEFAULT
6) CALIBRATE THE TEST EQUIPMENT ACCORDING TO TEST EQUIPMENT MANUFACTURER'S EQUIPMENT.
7) VERIFY THAT THE DISPLAY WILL SHOW INSERTION LOSS (CALLED CABLE LOSS ON THE SITE MASTER); OR MEASURE
RETURN LOSS THEN DIVIDE BY 2.
8) CONNECT THE TEST EQUIPMENT TO THE BOTTOM JUMPER'S CONNECTOR AND ADJUST TO THE PROPER TORQUE SETTING.
(SEE MANUFACTURER'S RECOMMENDATION)
9) PERFORM SETUP AND MEASUREMENTS FOR ALL REMAINING TRANSMISSION LINES.
EXIT CRITERIA
ALL TRANSMISSION LINES IN ALL SECTORS HAVE INSERTION LOSS LESS THAN OR EQUAL TO THE MAXIMUM ALLOWABLE
THRESHOLD.
BOTTOM JUMPER:
ILr_IIImaoils] II.I0
TOP JUMPER:
BOTTOM JUMPER
LOSS (dB)
CABLE ATTEN.
(dB/FT)
X
X
X
CABLE LENGTH
(FT)
# CONNECTOR
PAIRS
X
MAIN FEEDLINE TOP JUMPER
LOSS (dB) LOSS (dB)
IF TOP AND BOTTOM JUMPERS ARE NOT APPLICABLE TO YOUR
CABLE CONFIGURATION, ENTER (0) LOSS FOR THESE
INSERTION LOSS
(d B)
ATTEN. PER INSERTION LOSS
PAIR (dB) (dB)
0.14 =
CONNECTOR
LOSS (dB)
MAX. INSERTION
LOSS (dB)
F
ANY DISCONTINUITY (CONNECTOR CONTACT, KINKED CABLE, DAMAGED CABLE, OR OTHER ANOMALY) IN A TRANSMISSION CABLE
RESULTS IN THE REFLECTION OF SOME OF THE TRANSMITTED POWER. THIS REFLECTION IS A LOSS OF THE INTENDED TRANSMIT
POWER AND IS CALLED "THE RETURN LOSS" BY MEASURING THE TIME REQUIRED FOR THE SIGNAL TO TRAVEL TO THE POINT OF
ANOMALY AND BACK, ONE CAN DETERMINE THE ANOMALY'S DISTANCE FROM THE POINT OF ORIGINATION OF THE SIGNAL.
THE RETURN LOSS VALUES OF THE FEED LINE COMPONENTS ARE TO BE OBTAINED OVER THE ENTIRE BLOCK ASSIGNED
FREQUENCY BAND. THIS TEST USES DISTANCE TO FAULT MEASUREMENTS TO DETERMINE THE RETURN LOSS ASSOCIATED WITH
EACH CONNECTOR PAIR AND CABLE COMPONENT OF THE TRANSMISSION FEED LINE. THESE VALUES SHOULD BE REFERENCED TO
THE THRESHOLD VALUES LISTED BLOW. IF THE VALUE OF THE RETURN LOSS DOES NOT MEET THIS VALUE, THEN THE
APPLICABLE ANTENNA TRANSMISSION LINE SYSTEM FAILS. BY USING THIS TEST THE SUSPECT COMPONENT CAN BE LOCATED AND
CORRECTED. THE DTF MEASUREMENT CAN THEN BE REPEATED TO VERIFY ADHERENCE TO SPECIFICATIONS.
ENTRANCE CRITERIA
- PASSED PRELIMINARY VISUAL INSPECTION
- PASSED FEED LINE INSERTION LOSS TEST
TEST PREPARATION
1) INSTALL A 7/16 DIN 50-MATCHED LOAD INTO THE CONNECTOR AT THE ANTENNA END OF TRANSMISSION FEED LINE TOP
JUMPER
2) VERIFY THE TORQUE SETTING OF THE FEED LINE CONNECTOR WITH THE MATCHED LOAD MATCHES THE MANUFACTURER'S
RECOMMENDATIONS
3) SET THE TEST EQUIPMENT FREQUENCY SWEEP RANGE FOR THE ASSIGNED FREQUENCY BAND USED IN THE MARKET. ENSURE
THAT THE TRANSMITTED SWEEP FALLS WITHIN THE AUTHORIZED BAND FOR THE MARKET. FREQUENCIES USED ARE MHZ
OTHER FUTURE FREQUENCIES THAT REQUIRE SWEEPING ARE MHZ
4) CALIBRATE THE TEST EQUIPMENT ACCORDING TO TEST EQUIPMENT MANUFACTURER'S EQUIPMENT
5) VERIFY THAT THE TEST EQUIPMENT IS CONFIGURED TO MEASURE DISTANCE TO FAULT
6) CONNECT THE TEST EQUIPMENT TO THE BOTTOM JUMPER'S CONNECTOR AND ADJUST TO THE PROPER TORQUE SETTING
TESTING SEQUENCE
NOTE MEASUREMENTS OF THE RETURN LOSS AND THE DISTANCE CORRESPONDING TO EACH CONNECTOR PAIR. ALSO NOTE THE
LOWEST RETURN LOSS VALUE AND CORRESPONDING DISTANCE FOR EACH CABLE (WHERE PRACTICAL; USUALLY CABLES >=6'-O"
IN LENGTH). IF THE MEASURED RETURN LOSS FOR ANY COMPONENT IS LESS THAN THE APPROPRIATE VALUE FROM THE TABLE
BELOW, THE TEST HAS FAILED. REPLACE ANY FAILED COMPONENTS AND RE -TEST THE TRANSMISSION LINE FROM THE BEGINNING
OF THE ATP. PERFORM THE SETUP AND MEASUREMENTS FOR ALL REMAINING LINES
EXIT CRITERIA
ALL TRANSMISSION LINE COMPONENTS IN ALL SECTORS HAVE RETURN LOSS GREATER THAN OR EQUAL TO THE MINIMUM
ALLOWABLE THRESHOLD.
MINIMUM COMPONENT RETURN LOSS VALUES
COMPONENT
RETURN LOSS (dB)
CONNECTORS
> 30
CABLE
> 45
UBSYSTEM RETURN LOSS TEST:
THE RETURN LOSS VALUES OF THE ANTENNA SUBSYSTEM COMPONENT (NOT TO INCLUDE TRANSMISSION FEED LINE
CONTRIBUTIONS) ARE TO BE OBTAINED FOR THE COMPANY'S ASSIGNED FREQUENCIES IN YOUR MARKET. THESE VALUES SHOULD
BE REFERENCED TO THE THRESHOLD VALUES CALCULATED FOR YOUR SPECIFIC ANTENNA. IF THE VALUE OF THE RETURN LOSS
IS LESS THAN THE THRESHOLD VALUE, THEN THE ANTENNA FAILS AND NEEDS TO BE ANALYZED AND CORRECTED BEFORE
REPEATING THIS TEST. THIS TEST MUST BE REPEATED FOR EACH CARRIER FREQUENCY IN USE AT THE SITE.
ENTRANCE CRITERIA
VERIFY THAT THE FREQUENCY CHANNELS ARE CLEAR BY REFERENCING THE ANTENNA SWEEP ANALYSIS FOR YOUR MARKET BY
CONTACTING RF ENGINEERING.
- PASSED PRELIMINARY VISUAL INSPECTION
- PASSED FEED LINE INSERTION LOSS TEST
- PASSED FEED LINE DISTANCE -TO -FAULT TEST
TEST PREPARATION - BTS RECEIVE FREQUENCY TEST
CONNECT THE TEST EQUIPMENT TO THE BOTTOM JUMPER'S CONNECTOR AND ADJUST TO THE PROPER TORQUE SETTING. (SEE
MANUFACTURER'S RECOMMENDATION)
SET THE TEST EQUIPMENT FREQUENCY SWEEP RANGE TO THE BASE STATION RECEIVE FREQUENCIES USED IN YOUR MARKET.
1) CALIBRATE THE TEST EQUIPMENT WITH RESPECT TO THE END OF THE TOP JUMPER ACCORDING TO MANUFACTURER'S
INSTRUCTION. (CALIBRATE WITH AN OPEN, SHORT AND 50 OHM LOAD)
2) VERIFY THAT THE DISPLAY WILL SHOW RETURN LOSS VALUES.
3) REMOVE THE CALIBRATION LOAD FROM THE TOP JUMPER CONNECTOR AND CONNECT THE ANTENNA TO THE FEED LINE TOP
JUMPER.
4) VERIFY THE TORQUE SETTING OF THE FEED LINE CONNECTOR WITH THE ANTENNA MATCHES THE MANUFACTURER'S
RECOMMENDATIONS.
TEST EQUIPMENT CONNECTION
TESTING SEQUENCE - BTS RECEIVE FREQUENCY TESTS
TAKE MEASUREMENT OF THE LOWEST RETURN LOSS VALUE OVER
THE FREQUENCY BAND AND RECORD THE VALUE. IF THE
MEASURED RETURN LOSS FOR THE ANTENNA IS LESS THAN THE
THRESHOLD VALUE CALCULATED, THEN THE TEST HAS FAILED.
TEST PREPARATION - BTS TRANSMIT FREQUENCY TESTS
1) SET THE TEST EQUIPMENT FREQUENCY SWEEP RANGE TO THE
BASE STATION TRANSMIT FREQUENCIES USED IN YOUR MARKET.
2) SET TRANSMIT POWER TO TEST EQUIPMENT DEFAULT.
3) CALIBRATE THE TEST EQUIPMENT WITH RESPECT TO THE END
OF THE TOP JUMPER ACCORDING TO MANUFACTURER'S
INSTRUCTIONS. (CALIBRATE WITH AN OPEN, SHORT, AND 50 OHM
LOAD).
4) VERIFY THAT THE DISPLAY WILL SHOW RETURN LOSS.
TESTING SEQUENCE - BTS TRANSMIT FREQUENCY TESTS
TAKE MEASUREMENT OF THE LOWEST RETURN LOSS VALUE OVER
THE FREQUENCY BAND AND RECORD THE VALUE IN THE
PROVIDED WORKSHEET IF THE MEASURED RETURN LOSS FOR THE
ANTENNA IS LESS THAN THE THRESHOLD VALUE CALCULATED,
THEN THE TEST IS FAILED.
PERFORM THE ABOVE SETUP AND MEASUREMENTS FOR ALL REMAINING
TRANSMISSION LINES.
EXIT CRITERIA
ALL ANTENNAS IN ALL SECTORS HAVE RETURN LOSS GREATER THAN OR EQUAL TO THE MINIMUM ALLOWABLE THRESHOLD.
TRANSMISSION SYSTEM RETURN LOSS TEST:
THE RETURN LOSS VALUE FOR THE AGGREGATE TRANSMISSION LINE AND ANTENNA SYSTEM (INCLUDING WEATHER PROOFING) IS
TO BE OBTAINED FOR BOTH THE BASE STATION TRANSMIT AND RECEIVE FREQUENCIES ASSIGNED AND CLEARED IN YOUR
MARKET. THESE VALUES SHOULD BE REFERENCED TO THE THRESHOLD VALUE. IF THE VALUE OF THE RETURN LOSS IS LESS
THAN THE DESIGNED VALUE, THEN THE SYSTEM FAILS AND NEEDS TO BE ANALYZED AND CORRECTED BEFORE REPEATING THE
ATP.
ENTRANCE CRITERIA
- VERIFY THAT THE FREQUENCY CHANNELS ARE CLEAR BY CONTACTING RF ENGINEERING
- PASSED PRELIMINARY VISUAL INSPECTION
- PASSED FEED LINE INSERTION LOSS TEST
- PASSED FEED LINE DISTANCE -TO -FAULT TEST
TEST PREPARATION - BTS RECEIVE FREQUENCY TESTS
1) VERIFY THAT ANTENNAS ARE CONNECTED TO THE APPROPRIATE FEED LINE AS DESIGNATED IN THE COLOR CODING SCHEME
(SEE CONSTRUCTION SPECIFICATIONS)
2) DETERMINE THE RETURN LOSS VALUE OF THE ANTENNA
3) VERIFY THE TORQUE/CRIMPER SETTING OF THE FEED LINE CONNECTOR, MATCHES THE MANUFACTURER'S RECOMMENDATIONS.
4) APPLY WEATHER PROOFING TO EACH ANTENNA/CONNECTOR INTERFACE. AVOID BLOCKING ANY WEEP HOLES ON THE ANTENNA.
5) CONNECT THE TEST EQUIPMENT TO THE BOTTOM JUMPER'S CONNECTOR AND ADJUST TO THE PROPER TORQUE SETTING.
(SEE MANUFACTURER'S RECOMMENDATION).
6) SET THE TEST EQUIPMENT FREQUENCY SWEEP RANGE TO THE BASE STATION RECEIVE RF FREQUENCIES USED IN YOUR
MARKET.
7) CALIBRATE THE TEST EQUIPMENT ACCORDING TO TEST EQUIPMENT MANUFACTURER'S EQUIPMENT.
8) VERIFY THAT THE DISPLAY WILL SHOW RETURN LOSS.
THE INFORMATION CONTAINED IN THIS SET OF CONSTRUCTION DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO CARRIER SERVICES IS STRICTLY PROHIBITED.
THE SWEEP TESTS PROVIDE A MEANS OF DETERMINING THE CONDITION OF THE TRANSMISSION SYSTEM. IT IS IMPORTANT TO
MAINTAIN A VALUE OF RETURN LOSS THAT IS AS LOW AS POSSIBLE TO MAINTAIN THE SYSTEM INTEGRITY. IT IS ALSO VITALLY
IMPORTANT TO REALIZE THE PROPER TEST CONDITIONS WHEN ANALYZING THE SYSTEM. THE BEST RETURN LOSS FIGURES WILL
ALWAYS OCCUR WHEN THERE IS A 50 OHM LOAD PRESENT AT THE END OF THE TRANSMISSION LINE RATHER THAN AN
ANTENNA. IT IS ALSO IMPORTANT TO COMPARE SWEEP RESULTS USING THE SAME EXACT SETUP. THAT IS IF THE MEASUREMENT
WAS MADE WITH AN ANTENNA THE COMPARED RESULTS MUST BE MADE WITH THE SAME ANTENNA OR ONE WITH VERY SIMILAR
RETURN LOSS CHARACTERISTICS. IF THE RESULTS WERE OBTAINED WITH A 50 OHM LOAD THEY MUST BE COMPARED WITH A 50
OHM TERMINATION.
TESTING SEQUENCE - BTS RECEIVE FREQUENCY TESTS
TAKE MEASUREMENT OF THE LOWEST RETURN LOSS VALUE OVER THE FREQUENCY BAND AND RECORD THE VALUE. IF THE
MEASURED RETURN LOSS FOR THE TRANSMISSION SYSTEM IS LESS THAN THE THRESHOLD VALUE, THEN THE TEST HAS FAILED.
IF A FAILURE OCCURS, PERFORM A DISTANCE TO FAULT MEASUREMENT AND REPLACE THE SUSPECT COMPONENT. (NOTE: AT
THIS POINT, IF ALL OF THE PREVIOUS TESTS HAVE BEEN PERFORMED, THE ANTENNA CONNECTION IS MOST LIKELY FAULTY). IF
REPAIRS INVOLVE COMPONENTS OTHER THAN THE ANTENNA/ANTENNA CONNECTION RE -TEST THE TRANSMISSION LINE FROM THE
BEGINNING OF THE ATP.
TEST PREPARATION - BTS TRANSMIT FREQUENCY TESTS
- SET THE TEST EQUIPMENT FREQUENCY SWEEP RANGE TO THE BASE STATION TRANSMIT RF FREQUENCIES USED IN YOUR
MARKET.
- SET TRANSMIT POWER TO TEST EQUIPMENT DEFAULT
- CALIBRATE THE TEST EQUIPMENT ACCORDING TO TEST EQUIPMENT MANUFACTURER'S EQUIPMENT
- VERIFY THAT THE DISPLAY WILL SHOW RETURN LOSS
- VERIFY RETURN LOSS VALUES
TESTING SEQUENCE - BTS TRANSMIT FREQUENCY TESTS
- TAKE MEASUREMENT OF THE LOWEST RETURN LOSS VALUE OVER THE FREQUENCY BAND AND RECORD THE VALUE. IF THE
MEASURED RETURN LOSS FOR THE ANTENNA IS LESS THAN THE THRESHOLD VALUE, THEN THE TEST HAS FAILED. IF A FAILURE
OCCURS, PERFORM A DISTANCE TO FAULT MEASUREMENT AND REPLACE THE SUSPECT COMPONENT. (NOTE: AT THIS POINT, IF
ALL OF THE PREVIOUS TESTS HAVE BEEN PERFORMED, THE ANTENNA CONNECTION IS MOST LIKELY FAULTY). IF REPAIRS
INVOLVE COMPONENTS OTHER THAN THE ANTENNA/ANTENNA CONNECTION, RE -TEST THE TRANSMISSION LINE FROM THE
BEGINNING OF THE ATP
- PERFORM THE ABOVE SETUP AND MEASUREMENTS FOR ALL REMAINING TRANSMISSION LINES
EXIT CRITERIA
ALL ANTENNAS AND COMPONENTS IN ALL SECTORS HAVE RETURN LOSS GREATER THAN OR EQUAL TO THE MINIMUM ALLOWABLE
THRESHOLD VALUE.
- PASSED PRELIMINARY VISUAL INSPECTION
- PASSED FEED LINE INSERTION LOSS TEST
- PASSED FEED LINE DISTANCE -TO -FAULT TEST
- PASSED ANTENNA SUBSYSTEM RETURN LOSS TEST
VISUA
ENTRANCE CRITERIA
PASSED ALL ELECTRICAL TESTS.
TESTING SEQUENCE
1) VERIFY THAT THE RADOMES ON ALL ANTENNAS ARE SEALED AND DO NOT HAVE ANY CRACKS, INCLUDING GPS
2) CHECK THE ANTENNA MOUNTING
3) MEASURE ANTENNA ORIENTATION TO WITHIN 2 DEGREE RELATIVE TO MAGNETIC NORTH. MEASURE MECHANICAL DOWN -TILT TO
WITHIN 0.25 DEGREE FROM HORIZONTAL FOR EACH ANTENNA IN EACH SECTOR. RECORD DOWN -TILT AND ORIENTATION ON THE
VISUAL INSPECTION CHECK -OFF SHEET.
4) VERIFY THAT ANTENNA IS VERTICAL IN THE NON -TILT PLANE, I.E., NO SIDE TILT, (AZIMUTH PLANE IS HORIZONTAL) TO WITHIN
0.25 DEGREES AND RECORD AS PASS OR FAIL ON THE VISUAL INSPECTION CHECK -OFF SHEET.
5) VERIFY THE COAXIAL COLOR CODING MATCHES THE CORRECT ANTENNA AND SECTOR AND INDICATE AS PASS OR FAIL ON
THE VISUAL INSPECTION CHECK -OFF SHEET. (SEE CONSTRUCTION SPECIFICATION FOR ANTENNA CABLE COLOR CODING SCHEME).
6) VERIFY THAT APPROPRIATE TAGS ARE ATTACHED TO THE TOP AND BOTTOM OF THE FEED LINE SYSTEM AND INDICATE PASS
OR FAIL ON THE VISUAL INSPECTION CHECK -OFF SHEET.
7) VERIFY THAT CONNECTOR WEATHER PROOFING IS COMPLETE AND INDICATE ON THE VISUAL INSPECTION CHECK -OFF SHEET.
8) CAREFULLY CHECK ALL ANTENNA FEED LINES FOR DENTS AND KINKS AND OTHER ANOMALIES AND INDICATE OBSERVATIONS
ON THE VISUAL INSPECTION CHECK -OFF SHEET.
9) RECORD ALL INFORMATION IN THE SITE LOG BOOK AND THE SITE SPREADSHEET
EXIT CRITERIA
SUCCESSFUL COMPLETION OF THE ANTENNA SWEEPING ATP
CONNECTORS P/F
SECTOR #1
SECTOR #2
SECTOR #3
WEATHER PROOFING P/F
SECTOR #1 _
SECTOR #2-
SECTOR #3-
WEATHER PR
SECTOR #1
SECTOR #2
SECTOR #3
ANTENNA P/I
SECTOR #1
SECTOR #2-
SECTOR #3 -
BTS, DAP,
RRU UNIT
COLOR CC
ANTENNA DOWN TILT AND ORIENTATION
SECTOR
ANTENNA
DOWN -TILT
ORIENTATION
SIDE TILT
SECTOR 1
TXO RXO
RX1
SECTOR 2
TXO RXO
RX1
SECTOR 3
TXO RXO
RX1
11Z
DING
DING
STRAP
ION LINE
COAX COLOR CODE P/F
SECTOR #1
SECTOR #2
SECTOR #3
COAX CABLE P/F
SECTOR #1
SECTOR #2
SECTOR #3
GROUNDING
SECTOR #1
SECTOR #2
SECTOR #3
c I e a r . � .
1475 120TH AVE NE
BELLEVUE, WA 98005
PACIFIC TELECOM SERVICES,
LLC
111 South Jackson, Suite 200
Seattle, WA. 98104
Phone: (206) 342-9000 Fax: (206) 903-8513
8828 REGISTERED
ARCHITECT
RICHARD B. HALL
STATE OF WASHINGTON
EXPIRATION DATE OF THE
LICENSE: 08/20/13
I � �
w
O �
Q
� Q
�---� CD
U -_j
Q Q
LLJ
0 Li
O
REVISIONS
NO.
DATE
DESCRIPTION
INITIAL
A
02/24/12
ISSUED FOR SITE PCD
BW
B
03/09/12
FINAL CONSTRUCTION DOCUMENTS
PHD
C
05/03/12
SUBMITTAL SET
PHD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
SHEET TITLE
SWEEP TEST
SHEET NUMBER
RF-2
GROUNDING KEYED NOTES:
EXISTING ANTENNA GROUND BUS BAR AT ANTENNA LEVEL OF TOWER WITH COAX
O GROUND KIT. SEE DETAIL 5/E-2 FOR GROUND BAR CONSTRUCTION, 9/E-2 FOR
GROUND WIRE CONNECTIONS, AND 2/E-2 FOR COAX GROUNDING.
EXISTING TOWER GROUND BUS BAR AT BOTTOM OF TOWER WITH COAX GROUND KIT.
O2 SEE DETAIL 5/E-2 FOR GROUND BAR CONSTRUCTION, 9/E-2 FOR GROUND WIRE
CONNECTIONS, AND 2/E-2 FOR COAX GROUNDING.
O#6 AWG MICROWAVE ANTENNA GROUND TO ANTENNA GROUND BUS BAR (TYP). SEE
DETAIL 9/E-2.
O#2 AWG GROUND FROM EXISTING ANTENNA GROUND BUS BAR TO EXISTING TOWER
GROUND BUSS BAR (TYP OF (2) PLACES). SEE DETAIL 9/E-2.
O #2 AWG GROUND FROM TOWER GROUND BUS BAR TO EXISTING TOWER GROUND
RING (TYP OF (2) PLACES). SEE DETAIL 12/E-2.
ELECTRICAL SYMBOLS
AWG AMERICAN WIRE GAUGE
GROUND BAR
BCW
BARE COPPER WIRE
DWG
DRAWING
®
GROUND ROD WITH ACCESS
EMT
ELECTRICAL METALLIC TUBING
CHEMICAL GROUND ROD
GEN
GENERATOR
®
GROUND ROD
IGR
INTERIOR GROUND RING (HALO)
DISCONNECT SWITCH
IMC
INTERMEDIATE METALLIC CONDUIT
MGB
MASTER GROUND BAR
OM
METER
PCs
PERSONAL COMMUNICATION SYSTEM
b
CIRCUIT BREAKER
PTS
POWER TRANSFER SWITCH
PVC
RIGID (SCH. 40) POLYVINYL CHLORIDE CONDUIT
CADWELD TYPE CONNECTION
RGS
RIGID GALVANIZED STEEL
.
COMPRESSION TYPE CONNECTION
RWY
RACEWAY
GROUNDING WIRE
TYP
TYPICAL
1 ----REPRESENTS
DETAIL NUMBER
A-1
REFERENCE SHEET NUMBER
ROUNDING NOTES:
1. CONTRACTOR SHALL CAREFULLY REVIEW GROUNDING NOTES AND CONSULT WITH TOWER OWNER FOR SITE SPECIFIC
CONDITIONS IF THERE SHOULD BE ANY FURTHER CLARIFICATIONS NEEDED
2. CLEARWIRE GROUNDING LEADS COMING FROM BOTH ANTENNAS AND COAX GROUND KITS SHALL BE DIRECTED TO A
DEDICATED CLEARWIRE BUSS BARS AND SHALL BE LOCATED UP ON A GIVEN POLE OR TOWER NEAR THE BOTTOM OF
ANTENNAS BEING DIRECTLY FASTENED TO THE STEEL STRUCTURE WITH STAINLESS STEEL HARDWARE AND / OR ANGLE
ADAPTERS (E.G. PIROD / VALMONT GROUNDING BUSS BAR PART NUMBER B2981 [CLEARWIRE CONSTRUCTION MANAGER
SHALL CONFIRM BUSS BAR PART PRIOR TO CONTRACTOR PURCHASE OF PART] BEING ANCHORED TO A MOUNTING BRACKET
KIT FOR B2372 OR EQUIVALENT OR BEING MOUNTED WITH UNIVERSAL CLAMP NUMBER B1852 OR EQUIVALENT [W/O
CHERRY INSULATORS]).
3. ANCHORING OF CLEARWIRE UPPER BUSS BAR SHALL NOT EMPLOY THE USE OF DRILLING, WELDING OR CUTTING INTO THE
EXISTING POLE OR TOWER (ALL NEW ATTACHMENT BRACKETS SHALL BE CLAMPED OR MECHANICALLY FASTENED TO POLE
OR TOWER).
4. CLEARWIRE ANTENNA AND COAX GROUND LEADS SHALL TERMINATE AT UPPER BUSS BAR W/O INSULATORS AT THE NEAR
ANTENNA LOCATION WITH LEADS NOT CONTINUING DOWN THE POLE SHAFT OF TOWER LEG (TOWER STRUCTURE SHALL
SERVE AS GROUNDING MEDIUM IN ORDER TO ENSURE THAT ALL EQUIPMENT ON THE TOWER IS ON THE SAME GROUND
POTENTIAL MAINTAINING ONE COMMON GROUND PLANE).
5. A SECOND CLEARWIRE BUSS BARS WITH STAND OFF INSULATORS (E.G. PIROD / VALMONT GROUNDING BUSS BAR PART
NUMBER B2981 [CLEARWIRE CONSTRUCTION MANAGER SHALL CONFIRM BUSS BAR PART PRIOR TO CONTRACTOR PURCHASE
OF PART] BEING ANCHORED TO A MOUNTING BRACKET KIT FOR B2372 OR EQUIVALENT OR BEING MOUNTED WITH
UNIVERSAL CLAMP NUMBER B1852 OR EQUIVALENT [WITH STANDOFF CHERRY INSULATORS]) SHALL BE ADDED AT THE BASE
OF THE TOWER TO CAPTURE ANY ADDITIONAL TOWER SURFACE LIGHTNING RESIDUAL SHEETING WITH A DEDICATED
CLEARWIRE GROUND LEAD BEING DIRECTED TO GROUND AND ATTACHED TO THE EXISTING TOWER GROUND RING (FINAL
LOCATION OF BOTTOM OF TOWER GROUND BUSS BAR SHALL BE APPROVED BY TOWER REPRESENTATIVE PRIOR TO
INSTALLATION).
6. CLEARWIRE GROUND LEAD FROM LOWER CLEARWIRE BUSS BAR SHALL BE NO. 2 OR 2/0 AWG WIRE AND SHALL ATTACHED
TO EXISTING POLE / TOWER GROUND RING WITH PARALLEL THRU WIRE MOLD (E.G. PIROD / VALMONT PART NUMBER
171791 OR EQUIVALENT).
7. CLEARWIRE GROUND LEADS MAY NOT BE ATTACHED TO EXISTING GROUND RINGS WITH ANY CONFIGURATION OTHER THAN
THE "PARALLEL THRU WIRE MOLD" WITH THE LEAD SWEEPING INTO THE GROUND RING IN THE CONFIGURATION SHOWN ON
THE GROUNDING PLAN.
8. CLEARWIRE GROUND LEADS FROM BOTH ANTENNAS AND COAX GROUND KITS WHERE THERE IS AN ESTABLISHED GROUND
BUSS BAR POSITIONED AT THE TOP OF A NONCONDUCTIVE POLE OR STRUCTURE (E.G. WOOD UTILITY POLES, PRE —CAST
CONCRETE POLES, BUILDINGS, FIBERGLASS STRUCTURES, ETC.) SHALL EMPLOY THE USE OF SEPARATE GROUND LEAD
CONDUCTORS RUNNING DOWN THE POLE OR STRUCTURE TO A BUSS BAR AT THE BASE OF THE POLE OR STRUCTURE
AND FURTHER RUNNING INTO AN EXISTING GROUND RING.
North to be determined by
site survey (if possible).
24"x36" SCALE: 1 " = 1 '-0"
11"x17" SCALE: 1/2" = 1'-0" 1' 6" 0" 1SCHEMATIC GROUNDING PLAN
r+rT r�r I/`N-r I,I n/NrNl IAArAIT0 Ire Plf9rinM r Anv nV AIATI Inr AAIV I If^r /ln nl C/'�I (\�I If_]r /1T1.1ro TI_IAAI TLIAT 1A/LJ I/�Ll nrl ATrf" T/\ nAnnlrn C rrm I- !'__ /'err
IfIC IIVFVRIVI/A11V1N VVIVI/'111VLV IIV IIIIJ JL.I VI VVIYJII\ IIVI'I vvvvlrrr...Irly IJ 1 I\VI INIL 1%1 UI
clear
1475 120TH AVE NE
BELLEVUE, WA 98005
PACIFIC TELECOM SERVICES,
LLC
111 South Jackson, Suite 200
Seattle, WA. 98104
Phone: (206) 342-9000 Fax: (206) 903-8513
N8828]REGISTERE
ARCHITECT
RICHARD B. HALL
STATE OF WASHINGTON
EXPIRATION DATE OF THE
LICENSE: 08/20/13
E—
I �
O 0
W o 00
�Q
U J
EL Q
LLJ
LLJ
0 Li
O
REVISIONS
NO.
DATE
DESCRIPTION
INITIAL
A
02/24/12
ISSUED FOR SITE PCD
BW
B
03/09/12
FINAL CONSTRUCTION DOCUMENTS
PHD
C
05/03/12
SUBMITTAL SET
PHD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
SHEET TITLE
GROUNDING SCHEMATIC
SHEET NUMBER
E-1
#6 AWG FROM ANTENNA
CABLE GROUND KIT
GROUND BAR ON
WALL, ICE BRIDGE,
FLOOR OR ON
ANTENNA TOWER
(OD OOO OO O
nq
OOOO O OO '0' O
O O
*TWO HOLE LUG, OR EXOTHERMIC WELD TO
BE USED WITH #2 AWG BCW TO BUILDING
SERVICE GROUND OR GROUND RING
GROUND CONDUCTOR SHALL BE ELIMINATED
WHEN GROUND BAR IS ELECTRICALLY BONDED
T::::TO METAL TOWER/MONOPOLE STRUCTURE
NOTE:
GROUND BARS AT BOTTOM OF TOWERS/MONOPOLES
SHALL ONLY USE EXOTHERMIC WELDS.
NOT USED NOT USED NOT USED GROUND WIRE INSTALLATION
24"x36" SCALE: NOT TO SCALE 12 24"x36" SCALE: NOT TO SCALE 11 24"x36" SCALE: NOT TO SCALE 10 24"06" SCALE: NOT TO SCALE 9
1 1 "x17" SCALE: NOT TO SCALE 1 1 "x17" SCALE: NOT TO SCALE 1 1 "x17" SCALE: NOT TO SCALE 1 1 "x17" SCALE: NOT TO SCALE
2
4 5
7/16" 3/4 p 0 0
2" 0 0 0 ;
0 0
o p 0 p 0
0 Of 0 0
3 (DO 0 0 0 1
0 0 0
1"
NOTE:
1) COPPER GROUND BAR, 1/4"x 4% 20", NEWTON INSTRUMENT CO.
CAT. NO. B-6142 OR APPROVED EQUAL. HOLE CENTERS TO MATCH NEMA
DOUBLE LUG CONFIGURATION. (ACTUAL GROUND BAR SIZE WILL
VARY BASED ON NUMBER OF GROUND CONNECTIONS)
2) INSULATORS, NEWTON INSTRUMENT CAT. NO. 3061-4 OR APPROVED EQUAL
3) 5/8" LOCK WASHERS, NEWTON INSTRUMENT CO.
CAT. NO. 3015-8 OR APPROVED EQUAL
4) WALL MOUNTING BRACKET, NEWTON INSTRUMENT CO.
CAT NO. A-6056 OR APPROVED EQUAL
5) 5/8-11 X 1" HHCS BOLTS, NEWTON INSTRUMENT CO.
CAT NO. 3012-1 OR APPROVED EQUAL
6) INSULATORS SHALL BE ELIMINATED WHEN BONDING DIRECTLY TO
TOWER/MONOPOLE STRUCTURE. CONNECTION TO TOWER/MONOPOLE
STRUCTURE SHALL BE PER MANUFACTURERS RECOMMENDATIONS.
NOT USED NOT USED NOT USED TYPICAL GROUND BAR
24"x36" SCALE: NOT TO SCALEES 24"x36" SCALE: NOT TO SCALE 7 24"x36" NOT
NOT TO SCALE 6 5
1 1 "x17" SCALE: NOT TO SCALE 1 1 "x17" SCALE: NOT TO SCALE 1 1 %17" SCALE: NOT TO SCALE 24"x36" SCALE: NOT TO SCALE
1 1 "x17" SCALE: NOT TO SCALE
(TYPICALLY)COAX TO ANTENNA
MONOPOLE
TO ANTENNAS 12" TO 24,
04 120" MAX.
WEATHERPROOFING ��� STANDARD GROUND � KIT (TYP) ANTENNA GROUND BAR
RX2 TX1/RX1 ANTENNA CABLE No KIT (TYP) WITHOUT INSULATORS,
BONDED DIRECTLY TO
THE TOP OF MONOPOLE.
COAX JUMPER GROUND KIT (TYP) SEE NOTE
(TYP) TYPE TA TYPE VN TYPE NC TYPE SS #6 AWG (PROVIDED WITH
GROUND KIT TYP) ANTENNA GROUND BAR
WEATHERPROOFING KIT WITHOUT INSULATORS,
(SEE NOTE 3) BONDED DIRECTLY TO
COAX CABLE I BOTTOM OF MONOPOLE.
CONNECTOR #6 AWG CABLE GROUND KIT SEE NOTE
WEATHERPROOFING (TYP FOR ALL)
KIT (TYP) SEE NOTE 2
ANTENNA GROUND BAR, C6 t EXOTHERMIC WELD
WITHOUT INSULATORS. TYPE VV TYPE VS TYPE VB TYPE PT #6 AWG STRANDED COPPER
BONDED DIRECTLY TO TOP GROUND WIRE (GROUNDED TO
OF MONOPOLE OR TOWER. GROUND BAR). SEE NOTE 1 & 2
COAX TO SHELTER
ANTENNA CABLE ® CABLE CONNECTOR VIA TRAY OR ICE BRIDGE MONOPOLE FOUNDATION
TO BTS EQUIPMENT (TYP)wi
FNOTES: GROUND RING
1. DO NOT INSTALL CABLE GROUND KIT AT A BEND AND ALWAYS DIRECT GROUND WIRE #2 AWG BCW SOLID
TO GROUND RING TYPE GT TYPE GY TYPE GR TYPE GL DOWN TO GROUND BAR. 4-- - - - - - - - - --� TINNED (TYPICAL OF 3)
NOTES: 2. GROUNDING KIT SHALL BE TYPE AND PART NUMBER AS SUPPLIED OR RECOMMENDED
DO NOT INSTALL CABLE GROUND KIT AT A BEND AND ALWAYS DIRECT GROUND WIRE BY CABLE MANUFACTURER.
NOTE:
DOWN TO ANTENNA GROUND BAR. NUMBER OF GROUND BARS MAY VARY DEPENDING ON THE TYPE OF MONOPOLE,
3. WEATHER PROOFING SHALL BE TWO-PART TAPE KIT, COLD SHRINK SHALL NOT BE USED.
WEATHER PROOFING SHALL BE TWO-PART TAPE KIT. COLD SHRINK SHALL NOT BE USED.
ANTENNA LOCATION AND CONNECTION ORIENTATION. PROVIDE AS REQUIRED.
GROUND CABLE CONNECTIONS4 CADWELD GROUNDING CONNECTIONS CABLE GROUND KIT CONNECTION2 ANTENNA CABLE GROUND - MONOPOLE
24"x36" SCALE: NOT TO SCALE 24"x36" SCALE: NOT TO SCALE 3 24"x36" SCALE: NOT TO SCALE 24"x36" SCALE: NOT TO SCALE 1
1 1 %17" SCALE: NOT TO SCALE 1 1 "x17" SCALE: NOT TO SCALE 1 1 %17" SCALE: NOT TO SCALE 1 1 "x17 SCALE: NOT TO SCALE
THE INFORMATION CONTAINED IN THIS SET OF CONSTRUCTION DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO CARRIER SERVICES IS STRICTLY PROHIBITED.
cleary ,
1475 120TH AVE NE
BELLEVUE, WA 98005
PACIFIC TELECOM SERVICES,
LLC
111 South Jackson, Suite 200
Seattle, WA. 98104
Phone: (206) 342-9000 Fax: (206) 903-8513
8828 REGISTERED
ARCHITECT
�RICHARD B. HALL
STATE OF WASHINGTON
EXPIRATION DATE OF THE
LICENSE: 08/20113
h�
f-
0 r0
Q DO
Q OF)
Q
W
T (J U
h�
U J
Q Q
i LLJ
o
0 Li
O
I�
REVISIONS
NO.
DATE
DESCRIPTION
INITIAL
A
02/24/12
ISSUED FOR SITE PCD
BW
B
03/09/12
FINAL CONSTRUCTION DOCUMENTS
PHD
C
05/03/12
SUBMITTAL SET
PHD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
SHEET TITLE
GROUNDING DETAILS
SHEET NUMBER
E-2
1"
1"
FINISHED GRADE OR PAVING.
BACKFILL (SAND OR NATIVE MATCH SLOPE AND THICKNESS _
SOIL) PER ASTM STANDARDS OF EXISTING CONDITIONS
UNDISTURBED SOIL
CONNECTORS ELECTRICAL TAPE (1 LAYER)
_ STEP 1 STEP 2
— —_� COMPACTED
_ _ _ _ BACKFILL WITH
SATISFACTORY NATIVE
OR IMPORTED SOIL
— I -
- — VERTICAL CONNECTIONS SHALL BE
TAPED BUTYL TAPE (ALSO KNOWN OVERLAP RMOVES OM EWATER OAWAY
M UP SO
UTILITY WARNING TAPE AS MASTIC, TAFFY TAPE) FROM CONNECTION, TYP.
L4"O
STEP 3
Ed I — I 2„2"
4"0 POWER CONDUIT WHERE
APPLICABLE COORDINATE SIZE TELCO CONDUIT WHERE
AND TYPE WITH LOCAL UTILITY APPLICABLE COORDINATE
SIZE AND TYPE WITH LOCAL
UTILITY
6" MIN. (TYP) 4" MIN TO SECONDARY ELECTRIC ELECTRICAL TAPE: 3 LAYERS WITH 2" TAPE
12" MIN TO PRIMARY ELECTRIC AND 3 LAYERS IN 3/4" TAPE (ALL TAPE
NOTE: WITH MINIMUM 50% OVERLAP). ALL TAPE
SEPARATION DIMENSION TO BE VERIFIED WITH LOCAL UTILITY COMPANY REQUIREMENTS. ENDS SHALL BE CUT (DO NOT STRETCH).
COAT WITH 3M SCOTCH COTE SPRAY SEALER.
STEP 4
POWER Z TELCO TRENCH WEATHERPROOFING DETAIL
24"x36" SCALE: NOT TO SCALE 6 24"x36" SCALE: NOT TO SCALE 5
11 "x17" SCALE: NOT TO SCALE 11 "x17" SCALE: NOT TO SCALE
EXISTING EXISTING EXISTING EXISTING EXISTING
SECTOR A SECTOR A SECTOR B SECTOR C MICROWAVE DISH
PANEL ANTENNA
RRU MICROWAVE DISH
COAX GROUND
WIRE (TYP)
GROUND BUSS BAR AT
ANTENNA LEVEL
NOT USED WITHOUT ISOLATORS
24"x36" SCALE: NOT TO SCALE 4'
11"x17" SCALE: NOT TO SCALE
COAXIAL CABLES (TYP O
OF (2) PER ANTENNA)
GROUND BAR
WITH ISOLATORS
#2 SOLID BARE TINNED
(clear
1475 120TH AVE NE
BELLEVUE, WA 98005
�r�
PACIFIC TELECOM SERVICES,
LLC
111 South Jackson, Suite 200
Seattle, WA. 98104
Phone: (206) 342-9000 Fax: (206) 903-8513
8828 REGISTERED
ARCHITECT
CHARD LL
STATE OF WASHINGTON
EXPIRATION DATE OF THE
LICENSE: 08/20/13
V• O O
w o CO
� Q0-)
�Q
CD
� 1 � U a
Q Q
i � W
_ W
O
REVISIONS
N0.
DATE
DESCRIPTION
INITIAL
A
02/24/12
ISSUED FOR SITE PCD
BW
B
03/09/12
FINAL CONSTRUCTION DOCUMENTS
PHD
C
05/03/12
SUBMITTAL SET
PHD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
COPPER GROUND WIRE
SHEET TITLE
TO GROUND RING (SEE TOWER ELECTRICAL DETAILS
GROUNDING SCHEMATIC)
NOT
24"x36" SCALE: NOT
USEDE
TO SCALE
NOT
USED
21
ANTENNA GROUNDING DIAGRAM
24"x36" SCALE: NOT
TO SCALE
1 %17" SCALE: NOT
TO SCALE
1 1 %17" SCALE: NOT
TO SCALE
24"x36" SCALE: 1/2"
THE INFFnRMATION CONTAINED IN THIS SET OF CONSTRUCTION DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE
OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO CARRIER SERVICES IS STRICTLY PROHIBITED.
1 1 "xi 7" SCALE: 1 4" = 1'-0"
SHEET NUMBER
E-3