Re: File #17-100200-PC, PREAPPLICATION CONFERENCE SUMMARY
Nautilus Elementary School, 1000 S. 280 St., Federal Way
Dear Mr. Comfort:
Thank you for participating in the preapplication conference with the City of Federal Way's Development
Review Committee (DRC) held February 2, 2017. We hope that the information discussed at that meeting
was helpful in understanding the general requirements for your project as submitted.
This letter summarizes comments given to you at the meeting by the members of the DRC. The members
who reviewed your project and provided comments include staff from the City's Planning and Building
Divisions and Public Works Department, and representatives from Lakehaven Water and Sewer District
and South King Fire and Rescue. Some sections of the Federal Way Revised Code (FWRC) and relevant
information handouts are enclosed with this letter. Please be advised, this letter does not represent all
applicable codes. In preparing your formal application, please refer to the complete FWRC and other
relevant codes for all additional requirements that may apply to your project.
The key contact for your project is Leila Willoughby -Oakes, 253-835-2644, lei la.willougChnv-
oakesycityoffederailway.cQm. For specific technical questions about your project, please contact the
appropriate DRC representative as listed below. Otherwise, any general questions about the
preapplication and permitting process can be referred to your key contact.
PROJECT DESCRIPTION
The applicant proposes to add two double classroom portables on an existing elementary school site.
N X;kJOP )(SUES
&-P-dined below is a summary of the major issues of your project based on the plans and information
SUbMitted-for preapplication review. These issues can change due to modifications and revisions in the
a Rlans. These major issues only represent comments that the DRC consider most signifcaant to your, project
} ,. t.s +and do not include the majority oFthe comments provided. The major issues section is only provided as a
pieans to highlight critical requirements or issues. Please be sure to read the entire departinent comments
4AAde in the next section of this letter.
Mr. Comfort
February IT 2017
Page 2
Public Works Traffic Division
+ Transportation Concurreney Management (FWRC 19.90) —Transportation concurrency
permit with application fee of $1,620.00 is required for the proposed project.
Traffic Impact Fees (FWRC 19.91) — Traffic impact fees are required for adding elementary
school gross floor area.
DEPARTMENT COMMENTS
Outlined below are the comments made by the representatives of each department present at the
preapplication conference. Each section should be read thoroughly. If you have questions, please contact
the representative listed for that section.
PLANNING DIVISION (Leila Willoughby -Oakes, 253-835-2644, lei] a.►villoughhv-oake (ir citvoffedcr ahi aiv.eom)
1. Zoning Designation and Use — The subject property is zoned Single -Family High Density
Residential (RS9.6). The RS9.6 zone permits school uses pursuant to standards set forth within
FWRC 19.200.090 (enclosed).
2. Land Use Application —The proposal will require a Use Process I Master Land Use application.
The proposed improvements do not exceed twenty-five percent of the gross floor area of the existing
school pursuant to FWRC 19.15.030.1.a.
3. State Environmental Policv Act (SEPA) —The proposed improvements are exempt from
environmental review, pursuant to FWRC 14.15.030(c), Categorical exemptions — flexible
thresholds for schools up to 12,000 square feet and 40 parking spaces.
4. Public Notification — Process I applications do not require public notice.
Nonconforming Development —The portables -will expand site gross floor area. Tile
nonconforming aspects of the development must be brought into conformance, unless the applicant
proposes to add less than 25 percent of the gross floor area of the building or a group of bttilding(s)
(FWRC 19.30.090.].a). The portables (3,584 sq. ft.) will not exceed 25 percent of the elementary
school gross floor area (39,571 sq. ft.). The Planning Division finds no nonconformance issues are
triggered by this proposal.
6. Key Development Regulations (FWRC 19.200.090) — Site improvements and portables must
comply with the applicable FWRC development regulations. The following general regulations
apply to the proposal. Sa . 4
a. Required Yords and Lot Coverage — Required yards for school uses in RS9.6 zones areZ9okpow S
side and rear, for schools with 50 or more attendees. The maximum lot ` 40k
coverage is 75 percent. So
b. Height— The permitted building height for the proposed classroom is 30 feet above average Gfiror
building elevation (AABE). On the elevations please show how the height requirement has '!�.
been met. �
Cu
17-100'_00-PC Doc ID 75244
3ri
Mr. Comfort
February 17.2017
Page 3
Per FWRC 19.110.060 'Exceptions,' rooftop appurtenances may exceed the applicable height
limitation by a maximum of four feet, if the area of all appurtenances and screening does not
exceed 10 percent of the total area of the building footprint. These appurtenances must be
located in such a way as to minimize view blockage.
C. Parking— 1 space per school employee; please provide a narrative with your Use Process I
application. Please advise if additional teachers are added as a result of the new portables, and
if so, additional parking is required.
7. Tree Retention Requirements — The proposed removal of three trees may require replacement. The
new portables cannot make the site more non -conforming by the further reduction of required tree
units below the site's minimum tree density. Under the current regulations, the minimum tree density
in SF residential zones is 25 tree units per acre. The school's required density is 255 tree units (25
tree units x 10.18 acres). Please refer to the tree unit credit requirements in FWRC 19.120.130.
You have two options:
If you find the development falls below the minimum tree density requirements please
replant three trees of a comparable species and mature canopy anywhere on the site, or;
Provide an existing tree unit count showing the property will not fall below required tree
density as a result of the tree removal.
8. Community Design Guidelines — Pursuant to FWRC 19.1 15.020, compliance with Community
Design Guidelines reasonably related and applicable to the area of expansion is required. Guidelines
specific to institutional uses such as schools are detailed in FWRC 19.1 15.100 and those reasonably
related to your proposal include:
a. Overall design continuity with the existing improvements by using similar elements such as
materials, colors, and textures.
b. Roof design shall utilize forms and materials that avoid the general appearance of a "flat" roof.
C. Provide delineated pedestrian connections to the main building(s).
d. Building facades longer than 60 feet that are visible either from a right-of-way or a residential
zone or use must provide two of four specific design treatments: (1) fagade modulation, (2)
landscape screening, (3) canopy or arcade, and (4) pedestrian plaza. Please note that if three
fagade treatment options are incorporated, dimensional flexibility can be provided.
Required Landscaping — Pursuant to FWRC 19.125.040(22), building walls which are
uninterrupted by window, door, or other architectural feature(s) that are 240 square feet or greater
in area, shall be screened by landscaping. Such planting shall include trees, shrubs and groundcover
appropriate for the area proposed. If the abovementioned screening of blank building walls is
required, please submit a landscape plan prepared by a Washington State licensed landscape
architect with the Process 1 application.
10. Application Fees —Please contact the Permit Center at permiteentecitvoffederaltivay.cgrn or 253-
835-2607 for updated fee schedules for Process I Master Land Use application, concurrency, and
building permit.
17-100200-PC Doe ID: 75244
Mr. Comfort
February 17, 2017
Pace 4
PUBLIC WORKS DEVELOPMENT SERVICES DIVISION (Kevin Peterson, 253-835-2734,
kevin.petersonncityoffederalway.com)
Land Use Issues — Stormwater
Surface water runoff control and water quality treatment will be required per the 2016 King County
Surface Water Design Manual (KCSWDM) and the City of Federal Way Addendum to the manual.
This project meets the definition for a Full Drainage Review. However, it appears that the project
will be exempt from having to provide formal detention and water quality facilities. At the time of
land use site plan submittal, a preliminary Technical Information Report (TIR), that addresses the
relevance of the project to the nine core and five special requirements of the KCSWDM will be
required. The City Addendum can be found at the following website:
w►vw.citvoffederalway.com/node/ 1467.
2. If infiltration is proposed, soil logs prepared by a licensed geotechnical engineer or septic designer
must be provided to verify infiltration suitability.
3. Show the proposed location and dimensions of the detention and water quality facilities on the
preliminary plans.
Building Permit Issues
Engineered plans are required for clearing, grading, road construction, and utility work. Plans must
be reviewed and approved by the City. Engineering review fees are $2,430.00 for the first 18 hours
of review for Commercial building permits and full subdivision EN permits. Additional review time
is charged at $135.00 per hour. A final TiR shall be prepared for the project and submitted with the
engineering plans. Both the TIR and the plans will require the signature/seal of a professional
engineer registered/licensed in the state of Washington.
2. The Federal Way Public Works Development Standards Manual (including standard detail drawings,
standard notes, and engineering checklists) is available on the City's website at:
www.cityoffederalway.coiii/iiode/ 1467 to assist the applicant's engineer in preparing the plans and
TIR.
3. When topographic survey information is shown on the plans, the vertical datum block shall include
the phrase "DATUM: N.G.V.D.-29" or "DATUM: K.C.A.S.," on all sheets where vertical elevations
are called out.
4. Drawings submitted for plan review shall be printed on 24" x 36" or 22" x 34" paper. Site plans shall
be drawn at a scale of 1 " = 20', or larger. Architectural scales are not perm itted on engineering plans.
5. Provide cut and fill quantities on the clearing and grading plan.
6. Temporary Erosion and Sediment -control (TESL) measures, per Appendix D of the KCSWDM, just
be shown on the engineering plans.
7. The site plan shall show the location of any existing and proposed utilities in the areas affected by
construction.
17-100200-PC Doc ID: 75244
,—)
Mr. Comfort.
February 17, 2017
Paee 5
COMMUNITY DEVELOPMENT —BUILDING DIVISION (Peter Lawrence, 253-835-2621,
Peter. Law rencena .cites offederalway.com i
International Building Code (IBC), 2015
Washington State Amendments WAC 51-50
International Mechanical Code (I MC), 2015
Washington State Amendments WAC 51-52
Uniform Plumbing Code (UPC), 2015
Washington State Amendments WAC 51-56 & WAC 51-57
International Fire Code (IFC), 2015
Washington State Amendments WAC 51 -54
National Electric Code (NEC), 2014
Accessibility Code, ICC/ANSI A 117.1 - 2009
Washington State Amendments WAC 51-51
Washington State Energy Code, 2015 WAC 5 1 -11
Building Criteria
Occupancy Classification: E
Type of Construction:
Floor Area: V-B
Number of Stories: I
Fire Protection: no
Wind/Seismic: Basic wind speed 85 Mph, Exposure, 25# Snow load, Seismic Zone D-1
A completed building permit application and commercial checklist required at submittal. (Additional
copies of application and checklists may be obtained on our web site at www.eit yoffederalway.com.)
Submit _5_ sets of drawings and specifications. Specifications shall include: 5 Soils report, _5_
Structural calculations, and 5 Energy calculations, _5_ Ventilation calculations. Note: A Washington
State Registered architects' stamp is required for additions/alterations (new or existing) of4,000 gross
floor areas or greater unless specifically listed as an "exempt" structure per the Revised Code of
Washington (RCW).
Energy code compliance worksheets are required to be completed and included with your permit
application.
17-100200-PC Doc ID 7;244
Mr. Comfort
February 17. 2017
Page 6
A wet stamp and signature is required on all sheets of plans and on the cover page of any calculations
submitted.
Federal Way reviews plans on a first in, first out basis; however, there are some small projects with
inconsequential review requirements that may be reviewed out of order.
Some project may require a third party review or inspection. The cost to cover these fees is the
responsibility of the applicant. Any third party fee is in addition to regular permit fees and costs.
Review Timing
The first comment letter can be expected within 6-8 weeks of submittal date. Re -check of plans will occur
in one to three weeks after re -submittal.
Revised or resubmitted plans shall be provided in the same format, size, and amount as the originally
submitted plans. Revised/resubmitted drawings shall indicate by means of clouding or written response,
what changes have been made from the original drawings. Plans for all involved departments will be
forwarded from the Community Development Department.
Other Permits & Inspections
Separate permits may be required for electrical, mechanical, plumbing, fire suppression systems, and
signs. Applicants may apply for separate permits at any time prior to commencement of construction.
When required, special inspections shall be performed by WABO approved agencies or by agencies
approved by the building official prior to permit issuance. Construction must be approved by all
reviewing departments prior to final building division inspection.
All concerned departments (Planning, Public Works, Electrical, & Fire) must sign off before the Building
Department can final the stricture for occupancy. Building final must be approved prior to the issuance of
a Certificate of Occupancy.
Construction projects may be required to have a pre -construction conference. If a pre -con meeting is
required, the general or representative, all subs, the architect or representative, the engineer or
representative, electrical contractor, and any other interested party, should attend this meeting. Meetings
will occur at the Building Department and will be scheduled by the inspector of record for the project.
Site -Specific Requirements:
• Copy of the NLEA to the Local jurisdiction required
• Inspections shall be:
• marriage line connections
• ramp and stair construction
• anchorage of buildings per the FOR
• separate electrical permit required
• possible restrooms based on the 2015 IBC chapter 29
crossover connections
The information provided is based on limited plans and information. The comments provided are
not intended to be a complete plan review and further comments are possible at time of building
permit plan review.
17-100200-PC Doc ID 7�244
Mr- Comfort
February 17. 2017
Pace 7
LAKEHAVEN WATER AND SEWER DISTRICT (Brian Asbury, 253-946-5407, BAsbury@lakehaven.org)
Water
A Certificate of Water Availability issued separately by Lakehaven may be required to be submitted
with any land use and/or building permit applications (check with land use agency for requirement).
Certificate is valid for one (1) year from date of issuance. If Certificate is needed, allow 1-2 work
days to issue for typical.
• Hydraulic model results (FF #328) indicate that Lakehaven's standard maximum allowable system
liquid velocity of 10 ft/s is exceeded at a fire flow rate above 1,800 GPM. This flow figure depicts
the calculated performance of the water distribution system under high demand conditions. Fire flow
rates greater than available in the existing distribution system may be accommodated through water
distribution system improvements. Please contact Lakehaven for further detail.
• The site has one (1) existing domestic water service connection (SvcNo 5089, 3" meter) & one (1)
existing irrigation water service connection (SvcNo 35719, 2").
Sewer
• A Certificate of Sewer Availability issued separately by Lakehaven may be required to be submitted
with any land use and/or building permit applications (check with land use agency for requirement).
Certificate is valid for one (1) year from date of issuance. If Certificate is needed, allow 1-2 work
days to issue for typical.
■ The site has one (1) existing sewer- service connection (SSCP 3649).
General
• All Lakehaven Development Engineering related application forms, and associated standards
information, can be accessed at Lakehaven's Development Engineering web pages
(http:1/www.lakehaven.nrg1204/Development-Engineerirl ).
• All comments herein are valid for one (1) year and are based on the proposal(s) submitted and
Lakehaven's current regulations and policies. Any change to either the development proposal(s) or
Lakehaven's regulations and policies may affect the above comments accordingly.
SOUTH KING FIRE AND RESCUE (Chris Cahan, 253-946-7243, Chris.Cahan(rtFsoutlikin!zlir-e.orp)
A fire alarm system will be required for this project.
CLOSING
This letter reflects the information provided at the preapplication meeting and is intended to assist you in
preparing plans and materials for formal application. We hope you found the comments useful to your
project. We have made every effort to identify major issues to eliminate surprises during the City's
review of the formal application. The completion of the preapplication process in the content of this letter
does not vest any future project application. Comments in this letter are only valid for one year as per
FWRC 19.40.070 (4).
As you know, this is a preliminary review only and does not take the place of the full review that will
follow submission of a formal application. Comments provided in this letter are based on preapplication
materials subm itted.
17-100200-PC Doc ID 7>'_44
Mr. Comfort
February 17. 2017
Page 8
Modifications and revisions to the project as presented for this preapplication may influence and modify
information regarding development requirements outlined above. In addition to this preapplication letter,
please exarnine.the complete FWRC and other relevant codes carefully. Requirements that are found in
the codes that are not addressed in this letter are still required for your project.
If you have questions about an individual comment, please contact the appropriate department
representative noted above. Any general questions can be directed towards the key project contact, Leila
Willoughby -Oakes, 253-835-2644. We look forward to working with you.
Sincerely,
Leila Willoughby -Oakes
Associate Planner
enc: Bulletin 003 Master Land Use Application
Bulletin 069 Tree and Vegetation Retention Requirements
Recommended Tree Species
Process I Submittal Checklist
Concurrency Application
Lakehaven Enclosures
c: Kevin Peterson, Engineering Plans Reviewer
Erik Preston, Senior Transportation Engineer
Peter Lawrence, Plans Examiner
Brian Asbury, Lakehaven Water and Sewer District
17-100200-PC Doc ID 75244
Lakehaven
WATER & SEWER DISTRICT
?21,,
52 0{38 515 9603 0
638 0
';0
152960 0 5 515 960330 51
29600
28641
1515292(
1 2891
151529Z
5153300230
�: 902
515
29101 r
1529 260
290 1 3 00190
7
FE: LakehavenWater and Sewer
trict neither warrants nor guarantees
accuracy of any facility information
vided. Facility locations and conditions
subject to field verification.
0 g 7 51529604 0
8725
5296 10 5152960 0
871 715
Otj
fr 20. $0001
805
800020
817
5700010 1
1 330016
908 15330015 51226
5153300
914 9
1
Nautilus Elementary School Portables 114
17-100200-00-PC
0 100 200
Feet 1/26/2017 BIA
Fence
/a.rocere
FeSE ff EX16
5'Wood
l
W.
New All ftgfher FIL rd !B ash
rile fs— Biel
7R? LF- 4"Fkr/o•Yr/od A[$ n+oltt T'Iv. '�,
sroPe D.53K
O
/////%Jj
�ilmornv Bor
q� 1
��
MaM•J per A S
� �
P H A L r
' �� 111
\� 1
NOTE-AprA,�AeAC Lean 7O
nrnermn
L/nR Fence
4"C/een Lbnrsa
RwnaasRsx-Arty Ro/i
ca,�
Y eL c�o�srsr�r+wns•ga�ec+>s r/ C.W,-Y -smo
Abce, spaw, 9Comocet abF:nn s .lxe
rA
mlll,lt_oml�
S UB GRADE.' CmnecalrSbWl RYpod�Li+.l1'.�fWCarm7'�Fa/a +YA
FiderW ,MWADS L*.Y— ve /r Rwl+�lWadf�vl-A RII DIMS
Cov ~ LWAW 5 7?'—f W/M AAno&71 CAA.-M h
AA—f—ft ers / a /—
SECTION A -A ALL WEATHER FIELD (Base BidJ
3/4" _ /'
�Swa e
R/maMf E.'s
Ex9 Cone
•'� �'' '.1 - .��+/ - 4"_ H/B'Min Cr Fxk Bose
F '8 - a• •. R zvff$o~ De0lh
•� s
�Ill�lllll
ASS 0, VERr/CAL DATUM -E/ev. _ /DO 00 Assumed
BL DG.
I
B L D G - - 'C O N C. -
ca.wm rms. •e
XICur d:a^wA, r_ .a&-Cr fb0
SECTION B-B NEW ASPHALT (Base SW
LEGEND
—92_ EXISTING CONTOUR
IE 99.9 INVERT ELEVATION
C.O. CLEANOUT
--•.—INSTALL NEW ADS DRAINTILE
k.L. .2.1... m. o.,
/"'F 20"
FILE
CITY OF
Ak444".' Federal Way
January 18, 2017
Sean M. Comfort
AHBL Inc.
2215 N. 30"' St., Suite 300
Tacoma, WA 98403
CITY HALL
33325 8th Avenue South
Federal Way, WA 98003-6325
(253) 835-7000
www. cityoffederalway.. com
Jim Ferrell, Mayor
Emailed: scoiiifort(@alibl.com
Re: Permit #17-100200-00-PC; PREAPPLICATION CONFERENCE
Nautilus Elementary School, 1000 S. 298'h St., :Federal Way (Parcel: 052104 9005)
Dear Mr. Comfort:
The Community Development Department is in receipt oryour preapplication conference request. The
application has been routed to members orthe Development Reviely Committee and the meeting has been
scheduled as follows:
11:00 a.m. — Thursday, February 2, 2017
Hylebos Conference Room
Federal Way City Hall, grid Floor
33325 8"' Avenue South
Federal Way, WA 98003
We look forward to meeting with you. Please coordinate directly with anyone else you would like to
attend the meeting as this will be the only notice sent by the department. If you have any questions
regarding the meeting, please contact me at leila.%,4illougltby-oakes. cityoffederalwav,coi-t or 253-835-
2644.
W
ughby-Oakes
Associate Planner
c: Sally Mclean, Federal Way Public Sehools,; Email:5mc ��arir!f�en.[ rg
17-100200-00-PC Doc 1 D. 73261
CITY OF FEDERAL WAY ,
COMMUNITY DEVELOPMENT DEPARTMENT `!
DEVELOPMENT REVIEW COMMITTEE TRANSMITTAL
DATE: January 18, 2017
TO: Cole Elliott, Development Services Manager
Peter Lawrence, Plans Examiner
Brian Asbury, Lakehaven Utility District
Chris Cahan, South King Fire & Rescue
Rob Van Orsow, Solid Waste/Recycling Coordinator
Rick Perez, City Traffic Engineer
FROM: Leila Willoughby -Oakes, Planning
FOR DRC MTG. ON: January 26, 2017- -10:00 AM Internal (3=d internal)
February 2, 2017 - 11:00 AM with applicant
FILE NUMBER(s) : 17-100200-00-PC
PROJECT NAME: NAUTILUS ELEMENTARY SCHOOL PORTABLES
PROJECT ADDRESS: 1000 S 289TH ST
ZONING DISTRICT: RS 9.6
PROJECT DESCRIPTION: Proposal to add (2) double portable classrooms to
existing site.
PROJECT CONTACT: SEAN M. OMFORT
2215 N. 30TH ST. 300
Tacoma, WA 98403
RELATED FILE NOS.: See Mirror Lake Portables: 15-102363-00-PC
MATERIALS SUBMITTED: Application
Site Plan
Large Plan Set
Narrative
Mirror Lake Pre-app Letter
CITY OF 4A Pre -application Conference Sign in Sheet
Federal Way
February 2, 2016
11:00 a.m.
COMMUNITY DEVELOPMENT REVIEW COMMITTEE
Project Name: Nautilus K-8 Elernent@a School Portables
Address: 1000 S 289th St. Federal Wa Parcel: 052104 9005
File Number: 17-100200-PC
City Hall
Hylebos Room
NAME
DEPARTMENT / DIVISION
TELEPHONE NUMBER
1
Leila Willoughby -Oakes,
Associate Planner
Planning/Community
Development
253-835-2644
Leila.Willou hb -
Oakes cit offederalwa .com
2.
1_�
3 ^
3.
— `
4.
��75
5.
f(2- ��� �CSQu'f6.
WC�!
/ ,�, 64,,J
72-1�3
7.
KULMI
14M GA
ZST SS a4pZI
27 -5 -3
54WAw
203 - 47-111- 5193-7
10.
2,.f ,fff —Z(33
12.
iVED
PROJECT MEMO JAN 12 2017
- CITY
OF
TO: City of Federal Way DATE: January 11, 2017
FROM: Sean M. Comfort, P.E.
Tacoma - (253) 383-2422
SUBJECT: Project Narrative for Concept Meeting
IBC00
PROJECT NO.: 2160955.10
PROJECT NAME: Nautilus K-8 School Portables
Statement of Existing and Proposed Use
The Federal Way Public Schools is proposing to add up to two double classroom portables to the Nautilus K-8
School located at 1000 South 289th Street for the 2017-2018 school year. Addition of these portables will not alter
the existing use of the site, which is a public school. The proposed portables will add additional instructional
space. The portables will have electricity, but no water or sewer service. The portable will not be used for
science labs, art studios, or other instructional types that would require running water. We would like to review
stormwater requirements for the project with you, including stormwater flow control and water quality thresholds.
The intention is to place the new double classroom portables west of the existing school, with opening in the start
of school. The double portables will be 1,792 square feet each in size, single story, and not fire sprinklered. The
portables will have metal stairs and ramps that will be connected to the existing school by a paved path.
The Type of Construction per the 2015 IBC will be VB. Occupancy Classification per the 2015 IBC will be
Classification Group E. The ITE Land Use Code is 520 — Elementary School.
The total site area is 443,556 square feet. Up to two double portables totaling 3,584 square feet of portable will
be added. No new parking stalls will be provided.
Statement of Architectural ❑esi n Intent
The proposed project will add up to two double classroom portable buildings at Nautilus K-8 School. The portable
will be of standard construction. The roofing material will be asphalt shingle, of a black -to -dark gray color. Siding
will be durable plywood surfaced with hardboard, with 8-inch grooves, and of a color designed to blend with and
complement the color of the Nautilus K-8 School's main building. The skirting surrounding the portable's
foundation will be plywood painted to match the siding. Trim, around windows and at the building corners, will be
clear cedar with a coloring to complement the siding.
Questions
The primary issues we would like to discuss are as follows:
1. Land use planning issues such as confirming that we meet bulk and dimensional regulations, parking
requirements, tree retention, landscaping requirements, and critical area requirements.
2. We would like to confirm our understanding of any required land use approvals.
3. anticipate that the Federal Way School 4rictOFLCity of Federal Way will be taking lead agency for
EPA review of the process.
4. Civil engineering issues such as grading, access, stormwater (flow control and water quality), and other
utilities as needed.
5�Building issues such as ramp locations, permitting requirements, and foundation plan review.
6. Fire department issues such as hydrant location and flow, and emergency vehicle access.
7. Confirm the submittal requirements for all departments, as well as expected review times. J,.i.(MQ�
If you have any questions in the meantime, please let me know at (253) 383-2422.
ULF
\\ahbl.com\data\Projects\2016\2160955\10_CIV\NON_CAD\SUBMITTALS\Pre-Application Meeting\20170109_Project Narrative_2160955.10.docx
Page 1 of 1
MivEDASTER LAND USE APPLICATION
DEPARTMENT OF COM. mi u-NITy DEVELOPIMENT
CITY OF Federal JAN 12 2017' f 33325 8'h Avenue South
Federal Way, WA 98003-6325
Fe �� I �� =V OF 11D�'N 253-835-2607;:Fax 253-835-2609
r V-, wwtiv.ciriaffederal way.com
APPLICATION NO(S) -7 - I () 07-00 - 0 0 - PC, Date January 11, 2017
Project Name
2017 Nautilus K-8 Elementary School Portables
Property Address/Location 1000 289th Street S., Federal Way, WA 98003
Parcel Number(s) 0520149005 ({? S ,� 6 CI —�( 00 S
Project Description The Federal Way School District is adding up to two
double classroom portable buildings tot the west of the
main building on the existing Nautilus K-8 Elementary
School Campus
PLI:.ASE MINT
Type of Permit Required
Annexation
Binding Site Plan
Boundary .Line Adjustment
Comp Plan/Rezone
Land Surface Modification
Lot Line Elimination
X Preapplication Conference
Process 1 (Director's Approval)
Process 11 (Site Plan Review)
Process III (Project Approval)
_ __ Process IV (Hearing Exanvner's Decision)
Process V (Quasi -Judicial Rezone)
Process VI
SEPA w/Project
SEPA Only
Shoreline: Variance/Conditional'Use
Short Subdivision
_ Subdivision
Variance: Conunercial/Residential
Required Information
Designation
Comprehensive Plan Designation
-- $12,000,000 Value of Existing Improvements
— $ 300,0000 Value of Proposed Improvements
International Building Code (IBC):
E Occupancy Type
513
Construction Type
Applicant
Name:
Sean M. Comfort, AHBL, Inc.
Address:
2215 North 30th Street, Suite 300
City/State:
Tacoma, WA
Zip:
98403
Phone:
253-383-2422
Fax:
25 3-38 3-2 5 72
Email:
scomfort@ahbl.com
Signature:
Agent (if different than Applicant)
Name:
Address:
City/State:
Zip:
Phone:
Fax:
Email:
Signature:
Owner
Federal Way Public Schools
Name:
Mr. Todd Kanyer
Address:
1211 S. 332nd Street
City/State:
Federal Way, WA
Zip:
98003
Phone:
253-945-5957
Fax:
253-945-5959
Email:
tkanyer@fwps.org
Signature:
Bulletin #003 January 1, 2011 Page 1 of 1 k:\Handouts\Master Land Use Application
)LUS K-8 SCHOOL PORTABLE PROJECT
" 6
I I -
I I �
E I
` I
! 22
k e-1Y�I_LD
PROPOSED
EXISTING ° DOUBLE CLASSROOM
SINGLE I PORTABLE
CLASSROOM I (3) TREES TO B
PORTABLE I REMOVED
I - !
�29 \I`
I k 28'
EXISTING
RESIDENTIAL I I o
DRIVEWAY
m 36'
I J ,
S 289TH ST. 30,
PROPOSED
DOUBLE CLASSROOM
sl PORTABLE —
l I — 28'
Ij[ �
k
�Y r ACCESSIBLE
PATHWAY
231' 1
I
I I I
irn
RS Oe S
RS9e S
�L.�YF�_Ln
1-
m
F.KZi r
/
—
FJ',0G77N0
1 0l
O
EXISTING SCHOOL I
RS:.6
� Fa
1 S 289TH ST.
F.H.
— -- — E60Er—
_ vp r '5o
RSOo S
v what's below.
:211 before you dia.
N
0
GRAPHIC SCALE
0 25 50 100
1" = 50 FEET
01IF17 o
ITE
• �..�a»�F.dv,wo,o
....yT., y.,o
Go g .w...e .-,. .... .
VICINITY MAP
OWNER:
FEDERAL WAY PUBLIC SCHOOLS
33330 6th AVENUE SOUTH
FEDERAL WAY, WASHINGTON 98003
CONTACT: TODD KANYER
PH: (253) 945-2000
UTILITIES/SERVICES:
WATER: LAKEHAVEN UTILITY DISTRICT
SEWER: LAKEHAVEN UTILITY DISTRICT
POWER: PUGET SOUND ENERGY (PSE)
TELEPHONE: CENTURYLINK
PARCEL NUMBER:
G521049005
CIVIL ENGINEER:
AHBL, INC
2215 NORTH 30th STREET, SUITE 300
TACOMA, WASHINGTON 95403
CONTACT: WILLIAM FIERST, P.E.
PH: (253) 393-2422
FAX: (253) 383-2572
SITE DATA:
SITE AREA:
443.656 SF
OCCUPANCY TYPE:
E
TYPE OF CONSTRUCTION:
5B
TOTAL PROP. FLOOR AREA:
3,584 SF
ZONING:
RS9 6
TOTAL EXISTING PARKING:
59
TOTAL PROPOSED PARKING:
59
SITE ADDRESS:
1000 S 289TH STREET
FEDERAL WAY, WASHINGTON 98003
D
TACOMA - SEATTLE • SPOKANE • TRICITIES
2215 North 30th Street, Suite 300 Tacoma, WA 98403
253 383 2422 TEL 253.3932672 FAX wwwahbl.com WEB
Protect Title:
NAUTILUS K-8
SCHOOL PORTABLE
PROJECT
Client:
FEDERAL WAY
PUBLIC SCHOOLS
33330 BTH AVENUE SOUTH
FEDERAL WAY, WA 98003
TODD KANYER
2160955 10
true Sei 6 0ai a.
PRE -APPLICATION
JANUARY 2017
NOTCE
�wu�:i �uc nv�o4ty
oar �K.�neanvi� eu" :m
�aui,�nsu w�s:sm
'i5C61v8D
I!dIIII it � 7�4Y
Revisions: —
Sheet Title:
CONCEPTUAL
SITE PLAN
Deslaned by: Drawn by: Checked by,
Sheet No.
C 1.00
of Sheets
DATE: January 11, 2017 FILENAME: O:t2016t216095SIO_CIV1CADt216095SSH-CONCEPT SITE dwg