Loading...
16-10345211�kCIT Federal Way September 9, 2016 Belmor Park Golf & Country Club 2101 S 324`' St. Federal Way, WA 98003 RE: File #16-103452-00-UP; USE PROCESS II SITE PLAN APPROVAL Belmor Park Clubhouse Addition, 2101 S 324`h St., Federal Way To Whom It May Concern: CITY HALL 33325 8th Avenue South Federal Way, WA 98003-6325 (253) 835-7000 www. cityofiederalway.. com Jim Ferrell, Mayor The City of Federal Way's Community Development Department has completed administrative review of Your proposal for an addition to the existing clubhouse building at Belmor Park Golf and Country Club located at 2101 South 324"' Street. The Process Il land use application submitted on July 18, 2016, and subsequent resubmittal on August 23, 2016, is hereby approved with conditions. The proposal meets site plan and community design guideline criteria set forth in Federal Way Revised Code (FWRC) 19.60.050 as found in the enclosed Exhibit - Findings for Process II Site Plan Approval and incorporated into this decision by reference. The remainder of this letter outlines the zoning and development review process required for this proposal and a summary of appeal procedures. REQUIRED REVIEW PROCESS The proposed improvements to the site are subject to Process II Site Plan Review pursuant to community clubhouse use requirements set forth in FWRC 19.205.150. The proposal does not exceed the city - adopted flexible thresholds set forth in FWRC 14.15.030(c) and therefore is exempt from review under the State Environmental Policy Act. APPEALS The effective date of this decision is September 12, 2016, or three days from the date of this letter. Pursuant to FWRC 19.60.080, any person who received notice of this administrative decision may appeal the decision to the Federal Way Hearing Examiner by September 26, 2016. Any appeal must be in the form of a letter delivered to the Department of Community Development with the established fee. The appeal letter must contain a clear reference to the matter being appealed and a statement of the alleged errors in the Director's decision, including the identification of specific findings and conclusions made by the Director disputed by the person filing. However, in that you are the only party of record, your appeal period is waived (assuming you do not wish to appeal this decision). Waiver of the right to appeal does not affect the effective date of this decision. APPROVAL DURATION Unless modified or appealed, the Process 11 decision is valid for five years from the date of issuance of the decision. Time extensions to the decision may be requested prior to the lapse of approval following the provisions listed in FWRC 19.15.110. The improvements must be substantially completed within the five-year time period or the land use decision becomes void. Belmor Park Clubhouse September 9, 2016 Page 2 CLOSING This land use decision does not waive compliance with future City of Federal Way codes, policies, and standards relating to this development. This Process II approval does not constitute approval of a building permit, authorization to clear and grade, or demolish the existing building. If you have any questions regarding this decision, please contact Dave Van De Weghe, Senior Planner, at 253-835-2638, or david.vandeweghe@cityoffederalway.com. S1 Acting Community Development Director enc: Approved Site Plan and Elevations Exhibit A `Findin,s for Process 11 Site Plan Review Approval' c: Jennifer Danison, AKS Architects, 1011 SW Klickitat Way. Suite 102, Seattle. WA 98134 Dave Van De Weghe, Senior Planner Cole Elliott, Development Services Manager Kevin Peterson. Engineering Plans Reviewer Sarady Long, Senior Transportation Planning Engineer Peter Lawrence. Plans Examiner Vince Faranda_ South King Fire & Rescue Brian Asbury, Lakehaven Utility District I6-103452 Doc I.D. 74634 CITY OF y Federal Way EXHIBIT A Findings for Process II Site Plan Approval Belmor Park Golf & Country Club Addition File #16-103452-00-UP FILE, The Director of Community Development hereby makes the following findings pursuant to content requirements of the Process II written decision as set forth in Federal Way Revised Code (FWRC) 19.60.070. These findings are based on review of existing city documents and submitted items by the applicant received July 18, 2016 and August 23, 2016. Proposal — The applicant proposes a 3,709 square -foot addition to the existing clubhouse building to include fitness, circulation, storage, activity office, restrooms, billiards room and card room spaces. Existing Conditions — The subject site is located off South 324"' Street, adjacent to Interstate 5. The site is bordered by the Commons Mall to the north, single-family residential to the south, Interstate 5 to the east and a water tower to the west. Comprehensive Plan & Zoning Designation — The subject property is located within the Multi - Family (RM) comprehensive plan and zoning designation. The property's use as a community clubhouse is a permitted use within the RM 3600 zoning designation pursuant to FWRC 19.205.150. 4. Review Process — Community clubhouse uses located in the RM 3600 zone are subject to development review procedures of Process II `Site Plan Review' set forth in FWRC Chapter 19.60, Process II review requires no public notice period and concludes with a written decision issued by the Director of Community Development. Appeals of the Director's decision are conducted by the city's Hearing Examiner. Environmental Review — The proposed improvements are exempt from environmental review. The addition is less than 12,000 square feet; the improvements are consistent with the State Environmental Policy Act (SEPA) definition of "minor new construction" as set forth in WAC 197- 11-800(2)(e). 6. Height — The height of the existing building will remain 22 feet, 1 inch. The height of the structure is below the 30-foot height maximum, per FWRC 19.205.150. 7. Setbacks — The required yard for the community clubhouse use is 20 feet front, side, and rear setbacks, per FWRC 19.205.150. The proposed improvements are shown to be set back more than 190 feet from the front yard, more than 100 feet from the side yards, and more than 1,000 feet from the rear yard. Lot Coverage —No maximum lot coverage applies. Instead, the buildable area will be determined by other site development regulations, i.e., required yards, landscaping, surface water facility, etc. 9. Parking — Pursuant to FWRC 19.205.150, community clubhouses shall provide 1 parking stall for each 300 square feet of gross floor area. The building will measure 12,694 square feet after the addition is complete, requiring 43 parking stalls. The 24 existing parking spaces provided along with other nearby parking areas on the site satisfy the requirement considering Belmor is a retirement community where residents primarily walk from their homes to the clubhouse and the golf course is not open to the public. 10. Landscaping — The RM 3600 zoning district landscaping standards set forth in FWRC 19.125.060(3) require Type III landscaping 20 feet in width along all public rights -of -way and ingress/egress easements. Type II landscaping 20 feet in width shall be provided along the common boundary abutting single-family zoning districts. Type III landscaping 10 feet in width shall be provided along all perimeter lot lines. Screening of site utilities applies in the front yard. No changes to the existing landscaping are required for the proposed addition. 11. Tree Retention — The RM 3600 zoning district requires 30 tree units per acre (FWRC 19.120.130). Planting locations for replacement trees (if needed) must be shown on the Use Process site plan or make a note. Planting locations must be shown on plans at the Building Permit stage. 12. Community Design Guidelines — The proposed addition complies with the provisions of FWRC Chapter 19.115. Subject applications for remodeling or expansion of existing developments shall meet only those provisions of this chapter that are determined by the director to be reasonably related and applicable to the area of expansion or remodeling, per 19.115.030. Building Design — The north building fagade will not change. The south and west facades are not visible from the right-of-way or single-family residential zoning districts. The eastern fagade is primarily a swimming pool, which will not change. The proposed addition matches the existing architecture. Screening of blank building walls — Building walls which are uninterrupted by window, door, or other architectural feature(s) listed in Chapter 19.115 FWRC, Community Design Guidelines, FWRC 19.1 15.060(3)(b), that are 240 square feet or greater in area, and not located on a property line, shall be screened by landscaping. Such planting shall include trees, shrubs and groundcover appropriate for the area proposed, per FWRC 19.125.040(22). 13. Rockeries— For commercial and multifamily lots, rockeries and retaining walls shall be a maximum of six feet in height as measured from finished grade at base of wall to top of wall. There shall be a minimum three-foot landscaped setback at the base of each rockery or retaining wall, per FWRC 19.120.120(3). 14. Transportation —Based on the submitted materials to add 3,709 square feet to the existing community clubhouse, the Institute of Transportation Engineers (ITE) Trip Generation - 8"' Edition, the proposed project is not expected to generate any net new trips. A concurrency permit is not required for this development project because no new trips are generated during the PM peak hour. Based on the submitted materials for no additional square footage, no traffic impact fee is required. Findings for Process Il Site Plan Approval Page 2 Belmor Park Golf & Country Club Addition File # I6-103452-00-UP/Doc. I.D. 74638 15. Stormwater - The project was reviewed by the Development Services Division of the Public Works Department for compliance with the stormwater requirements of the 2016 King County Surface Water Design Manual (KCSWDM), and City addendum to the manual. No additional stormwater facilities or water quality treatment are required. The project is subject to Full Drainage Review. Temporary erosion and sediment control (TESC) measures will be required during construction of the addition. 16. Fire Protection — The required fire flow for this project is 1,500 gallons per minute. A Certificate of Water Availability shall be provided indicating the fire flow available at the site. A hydraulic fire flow model shall be requested from the water district. a. Fire Hydrants: This project will require one fire hydrant. Existing fire hydrants on the property are available for this project. Fire hydrants shall be in service prior to and during the time of construction. b. Fire Lanes: Designated fire lanes may be required for emergency access. This may be done during the plans check or after the facility is in operation. Fire apparatus access roads shall be installed and made serviceable prior to and during the time of construction. C. Fire Sprinkler System: An automatic fire sprinkler system shall be installed per NFPA 13. The system demand pressure (to the source) required in a hydraulically designed automatic fire sprinkler system shall be at least 10 percent less than the correlative water supply curve pressure. d. Fire Alarm: A Fire Alarm System is required. An automatic fire detection system shall be installed in all buildings exceeding 3,000 square feet gross floor area. This fire detection system shall be monitored by a central and/or remote station conforming to the current requirements of the National Fire Protection Association standards and/or the fire chief or designee. e. Fire Department Lockbox: A Knox box is required for this project. Approved boxes can be ordered from www.knoxbox.com 17. Water — Lakehaven Utility District a. Lakehaven issued a Certificate of Water Availability for the proposed project/property on 12/10/15; Certificate is valid for one-year from date of issuance. b. Hydraulic model results (FF #148) indicate that Lakehaven's standard maximum allowable velocity of 10 ft/s is exceeded at a fire flow rate above 1,600 gpm. Fire flow rates greater than available in the existing distribution system may be accommodated through water distribution system improvements. Please contact Lakehaven for further detail. C. A new hydrant (as indicated on the preliminary Drainage, Grading & Utility Plan) is not required. d. A new Double Check Detector Assembly is not required (as indicated on the preliminary Drainage, Grading & Utility Plan), because the water main proposed for the new fire -protection service connection is an existing private water main with an existing DCDA at the point -of - connection to Lakehaven's water distribution system. 18. Sewer— Lakehaven Utility District a. Lakehaven issued a Certificate of Sewer Availability for the proposed project/property on 12/10/15; Certificate is valid for one-year from date of issuance. b. The preliminary plans do not indicate any sewer service line work, implying that new plumbing drains in the new building addition will connect to existing building plumbing (contact building official for requirements &/or additional information). C. If any sewer service line work (i.e., underground work outside of the building) is proposed, a separate Lakehaven sewer service connection permit would be required. Minimum pipe slope for gravity sewer service connections is 2%. Findings for Process II Site Plan Approval Page 3 Belmor Park Golf & Country Club Addition File #16-103452-00-UP/Doc. I.D. 74638 19. Building Permit— Prior to building construction, the applicant must obtain building permit approval. This Use Process II site plan approval decision does not grant building permit approval. 20. Decision Criteria — Staff finds the proposal is consistent with applicable site plan approval criteria required for Process II as set forth in FWRC 19.60.050. The proposal is consistent with the city's comprehensive plan; applicable provisions of FWRC Title 19 Zoning and Development Code; public health, safety, and welfare; and streets and utilities in the area are adequate to serve the anticipated demand from the proposal. The proposal is consistent with Community Design Guideline decisional criteria set forth in FWRC Chapter 19.115. Final construction drawings will be reviewed for compliance with specific regulations, conditions of approval, and other applicable city requirements. These findings shall not waive compliance with�future City of Federal Way codes, policies, and standards relating to this development. Prepared by: Dave Van De Weghe, Senior Planner Findings for Process II Site Plan Approval Belmor Park Golf& Country Club Addition Date: September 9, 2016 Page 4 File # 16-103452-00-U P/Doc. 1. D. 74638 RESUBMITTED AUG, 2 3 2016 CITY OF FEDERAL WAY CDS August 11, 2016 Robert Koch 1011 Klickitat Way, Suite 102 Seattle, WA 98134 RE: File #16-103452-00-UP; TECHNICAL REVIEW COMMENTS Belmor Park Clubhouse Addition, 2101 S 324tb St, Federal Way Dear Mr. Koch: South King Fire and Rescue and Lakehaven Utility District have reviewed the information submitted on July 18, 2016. The following comments must be addressed before the City can provide approval. SOUTH KING FME AND RESCUE (Vince Faranda, 253-946-7242, Vince.Faranda@southkingfire.org) The required fire flow for this project is 1,500 gallons per minute. A Certificate of Water Availability shall be provided indicating the fire flow available at the site. A hydraulic fire flow model shall be requested from the water district. Fire Hydrants: This project will require one fire hydrant. Existing fire hydrants on the property are available for this project. Fire hydrants shall be in service prior to and during the time of construction. Fire Lanes: Designated fire lanes may be required for emergency access. This may be done during the plans check or after the facility is in operation. Fire apparatus access roads shall be installed and made serviceable prior to and during the time of construction. Fire Sprinkler System: An automatic fire sprinkler system shall be installed per NFPA 13. The system demand pressure (to the source) required in a hydraulically designed automatic fire sprinkler system shall be at least 10 percent less than the correlative water supply curve pressure. Fire Alarm: A Fire Alarm System is required. An automatic fire detection system shall be installed in all buildings exceeding 3,000 square feet gross floor area. This fire detection system shall be monitored by a central and/or remote station conforming to the current requirements of the National Fire Protection Association standards and/or the fire chief or designee. Fire Department Lockbox: A Knox box is required for this project. Approved boxes can be ordered from.www.knoxbox.com Mr. Koch August 11, 2016 Page 2 LAKEHAVEN UTILITY DISTRICT (Brian Asbury, 253-946-5407, BAsbury@lakehaven.org) WATER • Lakehaven issued a Certificate of Water Availability for the proposed project/property on 12/10/15; Certificate is valid for one-year from date of issuance. • Hydraulic model results (FF #148) indicate that Lakehaven's standard maximum allowable velocity of 10 ft/s is exceeded at a fire flow rate above 1,600 gpm. Fire flow rates greater than available in the existing distribution system may be accommodated through water distribution system improvements. Please contact Lakehaven for further detail. ■ A new hydrant (as indicated on the preliminary Drainage, Grading & Utility Plan) is not required. ■ A new Double Check Detector Assembly is not required (as indicated on the preliminary Drainage, Grading & Utility Plan), because the water main proposed for the new fire -protection service connection is an existing private water main with an existing DCDA at the point -of -connection to Lakehaven's water distribution system. SEWER • Lakehaven issued a Certificate of Sewer Availability for the proposed project/property on 12/10/15; Certificate is valid for one-year from date of issuance. • The preliminary plans do not indicate any sewer service line work, implying that new plumbing drains in the new building addition will connect to existing building plumbing (contact building official for requirements &/or additional information). • If any sewer service line work (i.e., underground work outside of the building) is proposed, a separate Lakehaven sewer service connection permit would be required. Minimum pipe slope for gravity sewer service connections is 2%. GENERAL All comments herein are valid for one (1) year and are based on the proposal(s) submitted and Lakehaven's current regulations and policies. Any change to either the development proposal(s) or Lakehaven's regulations and policies may affect the above comments accordingly. Sincerely, Dave Van De Weghe Senior Planner enc: Lakehaven Utility Map 16-103452 Doc. I D. 74369 RESUBMITTED AUG 2 3 2016 CITY OF FEDERAL WAY CDS July 27, 2016 Robert Koch 1011 Klickitat, Suite 102 Seattle, WA 98134 RE; Selmor Park Clubhouse Addition; Permit # 16-103452-00-UP; 2101 S 3241h St Dear Mr. Koch: Development Services has reviewed the information submitted on July 18, 2016. The following comments must be addressed before the City can provide approval: Plans Prior to land use approval, the following comments must be addressed: Sheet Al 1. Cover sheet indicates a Geotechnical Engineer but no report has been provided with plan set. Sheet C1 1. Provide some indication of clearing limits on plan sheet. 2. Because portions of the retaining wall (southwest side of the building) exceed 4-feet in height, a separate building permit will be required. 3. Additional structural details must be provided for the retaining wall. 4. Existing CB #2 indicates a 6-inch storm main which may be affected by retaining wall and new addition. If necessary, provide additional information about relocation of the main or cutting and capping. 5. No erosion protection or concrete cleanout is shown on the plan sheets. Provide additional information on both of these items. 6. Provide additional information on Stormwater L.I.D. being proposed on southern storm main. 7. On the southern storm main, a catch basin is proposed but no information has been provided for the rim and pipe inverts. 8. The slope and pipe size has not been provided on the southern storm main. Technical Inforination Report Prior to land use approval, the following comments must be addressed: 1. Provide a small site Surface Water Pollution Protection (SWPP) plan in accordance with King County Surface Water Design Manual Appendix D 3.2. 2. Provide additional information on Stormwater L.I.D. being proposed on southern storm main. Sincerely, Cole Elliott, PE Development Services Manager CE: su cc: David VanDeWeghe, Senior Planner Project File Day File 4\AKS ARCHITECTURE 22 August 2016 RESUBMITTED From: Robert Koch, AKS Imo'"' AUG, 2 3 2016 To: Dave Van De Weghe, Senior Planner CITY OF FEDERAL WAY CDS Subj: RESPONSE TO COMMENTS 02 Permit # 16-103452-00-UP BELMOR PARK CLUBHOUSE ADDITION Ref: (a) Dave Van De Weghe Letter dtd 11 August 2016 Encls: (1) Email — General Fire Flow Information (3 pages) (2) Water and Sewer Availability (4 pages) (3) Fire Flow Information (2 pages) The following are the responses to the comments dated August 11 th, 2016 from the Federal Way Development Services on the Belmor Park Clubhouse Use Process II Submittal: SOUTH KING FIRE AND RESCUE (Vince Faranda 1. The required fire flow for this project is 1,500 gallons per minute. A Certificate of Water Availability shall be provided indicating the fire flow available at the site. A hydraulic fire flow model shall be requested from the water district. Response: 1.1 The Certificate of Water Availability as well as the Hydraulic Fire Flow Model has been provided by Lakehaven Utility District. Please see Enclosures (1), (2), and (3). Fire Hydrants: 2. This project will require one fire hydrant. Existing fire hydrants on the property are available for this project. Fire hydrants shall be in service prior to and during the time of construction. Response: 2.1 This project will be utilizing the existing private hydrant on the northern end of the property. The hydrant is currently and will remain in service. Fire Lanes: 3. Designated fire lanes may be required for emergency access. This may be done during the plans check or after the facility is in operation. Response: 3.1 Designated fire lane locations/proposals will be included during the building permit phase of the project. AKS, P. S.. Inc 1011 SW Klickitat Way, Suite 102 1 Seattle, WA 98134 1 206.623.6832 1 f 206.682.3484 4. Fire apparatus dCcess roads shall be installed and n.cide serviceable prior to and during the time of construction. Response: 4.1 The Existing Fire apparatus access road (Pebble Beach Cir.) will remain serviceable. Fire Sprinkler System: 5. A new automatic fire sprinkler system shall be installed per NFPA 13. Response: 5.1 An NFPA 13 compliant automatic fire sprinkler system is to be installed. All necessary documents will be submitted at the time of the building application. 6. The system demand pressure (to the source) required in a hydraulically designed automatic fire sprinkler system shall be at least 10 percent less than the correlative water supply curve pressure. Response: 6.1 Acknowledged. Fire Alarm: 7. A Fire Alarm System is required. An automatic fire detection system shall be installed in all buildings exceeding 3,000 square feet gross floor area. This fire detection system shall be monitored by a central and/or remote station conforming to the current requirements of the National Fire Protection Association standards and/or the fire chief or designee. Response: 7.1 A Fire Alarm System and its associated monitoring station will be installed per NFPA requirements and requirements of the Federal Way Fire Marshal. All necessary drawings & documents are to be submitted at the time of the building permit application. Fire Department Lockbox: 8. A Knox box is required for this project. Approved boxes can be ordered from www.knc)xl)ox.com. Response: 8.1 Acknowledged. The Knox box location will be provided during the building permit phase. AKS, P.S., Inc 2 1011 SW Klickitat Way, Suite 102 1 Seattle, WA 98134 1 206.623.6832 1 f 206.682.3484 LAKEHAVEN UTI LITY L,,STRICT Brian Asbu Water: Lakehaven issued a Certificate of Water Availability for the proposed project/property on 12/10/15; Certificate is valid for one-year from date of issuance. Response: 1.1 Acknowledged. Enclosure (2) - The Lakehaven issued Certificate of Water Availability is attached. 2. Hydraulic model results (FF #148) indicate that Lakehaven's standard maximum allowable velocity of 10 ft/s is exceeded at a fire flow rate above 1,600 gpm. Fire flow rates greater than available in the existing distribution system may be accommodated through water distribution system improvements. Please contact Lakehaven for further detail. Response: 2.1 AKS contacted Lakehaven on 8116116 for clarification. Lakehaven confirmed that the existing hydrant meets the required standards pertaining to the scope of this project and no further action is required. Please see Enclosure (1) - attached email from Brian Asbury, Lakehaven Development Engineering Supervisor. 3. A new hydrant (as indicated on the preliminary Drainage, Grading & Utility Plan) is not required. Response: 3.1 The proposed new hydrant located on drawing C1 has been removed. See Response to Comments 02, letter to Cole Elliott dated 819116. 4. A new Double Check Detector Assembly is not required (as indicated on the preliminary Drainage, Grading & Utility Plan), because the water main proposed for the new fire -protection service connection is an existing private water main with an existing DCDA at the point -of -connection to Lakehaven's water distribution system. Response: 4.1 UPDATE. Per subsequent phone conversation with Brian Asbury, Lakehaven Development Engineering Supervisor, on 8116116 a new Double Check Detector Assembly WILL BE REQUIRED. The Double Check Detector Assembly indicated on the Drainage, Grading, & Utility Plan is to remain. Please see attached email from Brian - Enclosure (1). AKS. P.S., Inc 1011 SW Klickitat Way, Suite 102 1 Seattle, WA 98134 1 206.623.6832 1 f 206.682.3484 Sewer: 5. Lakehaven issued a Certificate of Sewer Availability for the proposed project/property on 12/10/15; Certificate is valid for one-year from date of issuance. Response: 5.1 Acknowledged. The Lakehaven issued Certificate of Sewer Availability is attached. Please refer to Enclosure (2). 6. The preliminary plans do not indicate any sewer service line work, implying that new plumbing drains in the new building addition will connect to existing building plumbing (contact building official for requirements &/or additional information). If any sewer service line work (i.e., underground work outside of the building) is proposed, a separate Lakehaven sewer service connection permit would be required. Minimum pipe slope for gravity sewer service connections is 2%. Response: 6.1 Acknowledged. If any new sewer service line work is deemed necessary in the future, a Lakehaven Sewer Service Connection Permit will be obtained. AKS, PS., Inc 4 1011 SW Klickitat Way, Suite 102 1 Seattle, WA 98134 1 206.623.6832 1 f 206.682.3484 ENCL (1): EMAIL - r--NERAL FIRE FLOW & SEWER IN")RMATION. (3 Pages) Jennifer Danison From: Brian Asbury <BAsbury@lakehaven.org> Sent: Tuesday, August 16, 201610:42 AM To: Jennifer Danison Subject: FW: Belmor Park Clubhouse Addition (16-103452-00-UP) Attachments: 16-103452-00-UP.pdf, Belmore Park joint 3839446099.pdf, K9 S 324 St & 22 Ave S.pdf Jennifer, Some clarification on Lakehaven's comments & additional info, for the subject proposed project. Let me know if you've any questions or need additional information. • The Certificates of Availability indicated below (copies attached) are actually for Lot/Site 11 of the mobile home park. However, except for distance reference to nearest hydrant, all other comments would be the same for Certificates issued specifically for this clubhouse project. Apologies for any confusion here. • The nearest existing hydrant is the hydrant located approximately 70+/- feet north of the clubhouse building. This hydrant was installed in 2003 under a Lakehaven Developer Extension Agreement. The hydrant is supplied directly from the adjacent Lakehaven tank site, with 12" diameter water main that reduces to 8" diameter water main into the mobile home park property. This would be standard construction for a hydrant 'run' of this length (>500') & that required/needed >1,000 GPM of available fire flow. • The attached Hydraulic Model report, performed specifically to determine what size mains would be needed for the previously indicated 2003 water main work, indicates that the available fire flow from the hydrant indicated in the above bullet -point would be approximately 1,600 GPM at 20 psi for 2 hours or more duration. • To my knowledge, no new onsite hydrant is required. • While the new Double Check Detector Assembly (DCDA) for the new fire -protection system for the clubhouse building will be connected to private water main (which is 'master' metered for the entire mobile home park site), installation of the DCDA & initial device testing needs to be coordinated with Lakehaven's Cross -Connection Control Program Manager (Chris Zoepfl, CZoepfl@Lakehaven.orq). Premise isolation devices should be located as close to the supplying water main/source as possible, but no further than 50-feet from such main/source. This is Lakehaven's typical requirement, where the device is directly connected to Lakehaven's water system; coordinate actual DCDA location with Lakehaven's CCCP Manager. • While this won't technically be a new Lakehaven water service connection, it is a water service connection. But because the supplying private water main is already monitored for water use (not metered, just whether water was used or not), no new Lakehaven service connection application is required. Just coordinate with Lakehaven's CCCP Manager as noted directly above. • Any sewer service work performed outside of the building/foundation walls will require a Lakehaven Sewer Service Connection Permit (application form attached). However, if the intent is to simply extend plumbing into any new building addition, then a Lakehaven SSCP is not required (all such work would be managed under a City plumbing permit). Brian Asbury Development Engineering Supervisor Lakehaven Utility District Lakehaven DE Website From: Brian Asbury Sent: Thursday, August 11, 2016 1:32 PM RESUBMITTED AUG. 2 3 2016 CITY OF FEDERAL WAY CDS ENCL (1)- EMAIL - -NERAL FIRE FLOW & SEWER IN'-)RMATION. (3 Pages) To: 'David VanDeWeghe' Subject: RE: Belmor Park Clubhouse Addition (16-103452-00-UP) Dave, Confirming that the comments below are correct for the subject project, I'd just attached an incorrect GIS map initially. Let me know if you've any questions or need additional information. Brian Asbury Development Engineering Supervisor Lakehaven Utility District Lakehaven DE Website From: Brian Asbury Sent: Thursday, August 04, 2016 11:10 AM To: 'David VanDeWeghe' Subject: Belmor Park Clubhouse Addition (16-103452-00-UP) Dave, Lakehaven's comments below, regarding the proposed private golf course clubhouse addition on tax parcel 1621049037. Let me know if you've any questions or need additional information. WATER • Lakehaven issued a Certificate of Water Availability for the proposed project/property on 12/10/15; Certificate is valid for one-year from date of issuance. • Hydraulic model results (FF #148) indicate that Lakehaven's standard maximum allowable velocity of 10 ft/s is exceeded at a fire flow rate above 1,600 gpm. Fire flow rates greater than available in the existing distribution system may be accommodated through water distribution system improvements. Please contact Lakehaven for further detail. • A new hydrant (as indicated on the preliminary Drainage, Grading & Utility Plan) is not required. • A new Double Check Detector Assembly is not required (as indicated on the preliminary Drainage, Grading & Utility Plan), because the water main proposed for the new fire -protection service connection is an existing private water main with an existing DCDA at the point -of -connection to Lakehaven's water distribution system. SEWER Lakehaven issued a Certificate of Sewer Availability for the proposed project/property on 12/10/15; Certificate is valid for one-year from date of issuance. The preliminary plans do not indicate any sewer service line work, implying that new plumbing drains in the new building addition will connect to existing building plumbing (contact building official for requirements &/or additional information). If any sewer service line work (i.e., underground work outside of the building) is proposed, a separate Lakehaven sewer service connection permit would be required. Minimum pipe slope for gravity sewer service connections is 2%. GENERAL All comments herein are valid for one (1) year and are based on the proposal(s) submitted and Lakehaven's current regulations and policies. Any change to either the development proposal(s) or Lakehaven's regulations and policies may affect the above comments accordingly. ENCL (1): EMAIL - r 7NERAL FIRE FLOW & SEWER 1Nr")RMATION. (3 Pages) << File: 16-103542-00-AD.pdf >> Brian Asbury Development Engineering Supervisor Lakehaven Utility District Cakehaven ❑E Website The contents of this email may be determined to be a public record and subject to disclosure pursuant to RCW 42.56 regardless of any expectations or claims of confidentiality or privilege asserted. ENCL (, INATER & SEWER AVAILABILITY PAGES RESUBMITTED nAUG, 2 3 2016 bli1TT Dlsri'",,,�+j CITY OF FEDERAL WAY _ F AV ABILITY CDS Lakehaven Utility District - Development Engineering Section 31623 - 1st Ave S * PO Box 4249 * Federal Way, WA 98063-4249 Telephone: 253-945-1581 * Email: cjenkinshouse@Lakehaven.org This certificate is intended to provide the applicant, land use agencies &/or public health departments with information necessary to evaluate development proposals. Lakehaven Utility District, at its sole discretion, reserves the right to delay, or deny, water service based upon capacity &/or supply limitations in Lakehaven's or Other Purveyor's system facilities. Proposed Land Use: ® Building Permit-SFR ❑ Building Permit-MFR ❑ Building Permit -Other ❑ Subdivision ❑ Short Subdivision ❑ Binding Site Plan ❑ Rezone ❑ Boundary Line Adjustment ❑ Other (specify/describe) Tax Parcel Number(s): 3839446099 Site Address: 2101 S 32411 St. Lot 11 Lakehaven Grid: K-09 Ex. Bldg. Area to Remain: UNKNOWN New Bldg. Area Proposed: 1.836 +/- sf Applicant's Name: Belmor Park Golf & Country Club WSYSTEM INFORMATION 1. ® Water service can be provided by service connection to an existing private 2 diameter water main that is on the site. 2. ❑ Water service for the site will require an improvement to Lakehaven's water distribution system of: ❑ a. feet of " diameter water main to reach the site; and/or ❑ b. The construction of a water distribution system on the site; and/or ❑ c. A major portion of Lakehaven's comprehensive water system plan would need to be implemented and/or constructed; and/or ❑ d. Other (describe): 3. ® a. The existing water system is in conformance with Lakehaven's Comprehensive Water System Plan. ❑ b. The existing water system is not in conformance with Lakehaven's Comprehensive Water System Plan and an Amendment to this Plan will be required. This may cause a delay in issuance of land use approvals or permits. 4. ® a. The subject property is within the corporate limits of Lakehaven Utility District, or has been granted Boundary Review Board approval for extension of water service outside of Lakehaven's water service area. ❑ b. Annexation or Boundary Review Board approval will be necessary to provide service. S. Water service is subject to: ❑ a. Payment of connection charges (to be determined by Lakehaven); ❑ b. Proof or reservation of easement(s) as required by Lakehaven; ❑ c. Other Comments/special conditions: The Belmor Mobile Home Park is sunplied wit water via a nrivate water system o[3.eratgd by the Mobile Horne Park Water feeding the private water system is suppli-ed by Lakehayen. The nearest fire hydrant is approximately 405+ - feet from the site's Lot 11 (as marked on map on the back of this page). Fire Flow at no less than 20 psi available within the water distribution system is 1.000+ gpm (approximate) for two (2) hours or more. This flow figure depicts the theoretical performance of the water distribution system under high demand conditions. Fire flow rates greater than this may be accommodated through water distribution system improvements, contact Lakehaven for additional information. 538 Pressure Zone Property Elevations (GIS): High 405+/-, Low 400+/- Est. Pressures (psi): Min. 48, Max. 59 I hereby certify that the above water system information is true. This certification shall be valid for one (1) year from the date of signature. Name: BRIAN ASBURY , Title: DEVELOPMENT ENGINEERING SUPERVISOR Signature: Date: !� Belmor Park wtr 3839446099.docx (9/21/15) Page 1 of 2 4 ;;". ENCL (r WATER & SEWER AVAILABILITY 'A) PAGES i r Lot 11 v 0�2 1621049037 2101 COLONIAL BLVD �V a rx. 144170000D S :AHy nt 32820 tare: takthaven utility District Certificate of Water Aval lab] I Ity i r , neither warrads nor guarantees the Ifni.4 k BCCItrdRrr or aawry facl8ty Information a Parcel Ho. 762 lafi49037, Lot 77 2aa provided. Facility locations an UT1L1rY lk[ j '" conditlons are sutdeet to fietd Feed 12110/15 8IA veriffcatian. Belmor Park wtr 3839446099.docx (9/21/15) Page 2 of 2 ?✓ ENCL (r WATER & SEWER AVAILABILITY 'A) PAGES "1.1ITY DIS'V'y Lakehaven Utility District - Development Engineering Section 31623 - 1st Ave S * PO Box 4249 * Federal Way, WA 98063-4249 Telephone: 253-945-1581 * Email: cjenkinshouse@Lakehaven.org This certificate is intended to provide the applicant, land use agencies &/or public health departments with information necessary to evaluate development proposals. Lakehaven Utility District, at its sole discretion, reserves the right to delay, or deny, sewer service based upon capacity &/or supply limitations in Lakehaven's or Other Purveyor's system facilities. Proposed Land Use: ® Building Permit-SFR ❑ Building Permit-MFR ❑ Building Permit -Other ❑ Subdivision ❑ Short Subdivision ❑ Binding Site Plan ❑ Rezone ❑ Boundary Line Adjustment ❑ Other (specify/describe) Tax Parcel Number(s): 3839446099 Site Address: 2101 S 3 e St. Lot Lakehaven Grid: K-09 Ex. Bldg. Area to Remain: UNKNOWN New Bldg. Area Proposed: 1.836 +/- sf Applicant's Name: B Im r P If & Country lute SEWER SYSTEM INFORMATIOL�I 1. ® Sewer service can be provided by service connection to an existing private 8" diameter sewer main that is on the site and the sewer system has the capacity to serve the proposed land use. 2. ❑ Sewer service for the site will require an improvement to Lakehaven's sanitary sewer system of: ❑ a. feet of " diameter sewer main or trunk to reach the site; and/or ❑ b. The construction of a sanitary sewer collection system on the site; and/or ❑ c. A major portion of Lakehaven's comprehensive wastewater system plan would need to be implemented and/or constructed; and/or ❑ d. Other (describe): 3. ® a. The existing sewer system is in conformance with Lakehaven's Comprehensive Wastewater System Plan. ❑ b. The existing sewer system is not in conformance with Lakehaven's Comprehensive Wastewater System Plan and an Amendment to this Plan will be required. This may cause a delay in issuance of land use approvals or permits. 4. ® a. The proposed site land use is within the corporate limits of Lakehaven Utility District, or has been granted Boundary Review Board approval for extension of sewer service outside of Lakehaven's sewer service area. ❑ b. Annexation or Boundary Review Board approval will be necessary to provide service. S. Sewer service is subject to: ® a. Payment of connection charges (to be determined by Lakehaven); ❑ b. Proof or reservation of easement(s) as required by Lakehaven; ® c. Other: Sewer Service Connection Per it r aired on ❑ isconnect I i & t onn new. Comments/special conditions: I hereby certify that the above sewer system information is true. This certification shall be valid for one (1) year from the date of signature. Name: BRIAN ASBURY Title: DEVELOPMENT N INEER G SUPEBV FOR 011 Signature: - Date: _ Belmor Park swr 3839446099.docx (4/6/15) Page 1 of 2 ENCL (r WATER & SEWER AVAILABILITY '?) PAGES Belmor Park swr 3839446099.docx (4/6/15) Page 2 of 2 r� ENC' 3): FIRE FLOW INFORMATION. (2' ''AGES LAKEHAVEN UTILITY DISTRICT Hydraulic Model Fire Flow Estimate Request/Reporting Form Requested By: Mary Young Date: 102/13/01 Hydrant Location: Section K- 9 Intersection: S 324 St & 22nd Ave S Additional Description: see attached map Results By: Date: 102/15/01 Model Run No.: Bert Rois Z 195LUDSFF.INP FF#148 Condition Pressure (psi) Flow (gpm) Static 52 0 Fire Flow (terminus of prop. 12" pipe) 20 8,600 (terminus of prop. 8" pipe) 20 3,000 NOTE: The fire flow analysis was performed at the terminus of a proposed 450-foot water main extension (utilizing a 12-inch size pipe and an 8-inch size pipe) that would start at the inlet/outlet of the SeaTac Tank at S 324th St and 22nd Ave. S. On -site fire flow estimates would have to be determined during design of the water system improvements. This fire flow rate will cause velocities in excess of 10 f/s within the water distribution system. For a proposed 12-inch pipe, a fire flow rate less than 3,500 gpm will maintain flow velocities below 10 f/s. For a proposed 8-inch pipe, a fire flow rate less than 1,600 gpm will maintain flow velocities below 10 f/s. A maximum fire flow rate of 1000 gpm is available at the terminus of a proposed 450-foot water main extension utilizing 8-inch pipe. A maximum fire flow rate of 2500 gpm is available at the terminus of a proposed 450-foot water main extension utilizing 12-inch pipe. There is no guarantee that the Hydraulic Model results will represent actual system performance. Model results depict the theoretical performance of the system under high demand conditions. Field measurements should always be obtained for design purposes. K _q _ �. •- •ti ,.. ... �L / 11 r � � Page 1 of 1 J 1 http://gismaps.kingcounty. gov/arcgis/rest/directories/arcgisoutput/Printing/PrintingService_... 9/8/2016 r. 9 J FI A N ON w 7 FILE 1�k Federal Way August 11, 2016 Robert Koch 1011 Klickitat Way, Suite 102 Seattle: WA 98134 RE: File #16-103452-00-UP; TECHNICAL REVIEW COMMENTS Belmor Park Clubhouse Addition, 2101 S 324`h St, Federal Way Dear Mr. Koch: CITY HALL 33325 8th Avenue South Federal Way, WA 98003-6325 (253) 835-7000 www. cityoffederalway.. com Jim Ferrell, Mayor South King Fire and Rescue and Lakehaven Utility District have reviewed the information submitted on July 18, 2016. The following comments must be addressed before the City can provide approval. SOUTH KiNG FiRE AND RESCUE (Vince Faranda, 253-946-7242, Vince.Faranda@southkingfire.org) The required fire flow for this project is 1,500 gallons per minute. A Certificate of Water Availability shall be provided indicating the fire flow available at the site. A hydraulic fire flow model shall be requested from the water district. Fire Hydrants: This project will require one fire hydrant. Existing fire hydrants on the property are available for this project. Fire hydrants shall be in service prior to and during the time of construction. Fire Lanes: Designated fire lanes may be required for emergency access. This may be done during the plans check or after the facility is in operation. Fire apparatus access roads shall be installed and made serviceable prior to and during the time of construction. Fire Sprinkler System: An automatic fire sprinkler system shall be installed per NFPA 13. The system demand pressure (to the source) required in a hydraulically designed automatic fire sprinkler system shall be at least 10 percent less than the correlative water supply curve pressure. Fire Alarm: A Fire Alarm System is required. An automatic fire detection system shall be installed in all buildings exceeding 3,000 square feet gross floor area. This fire detection system shall be monitored by a central and/or remote station conforming to the current requirements of the National Fire Protection Association standards and/or the fire chief or designee. Fire Department Lockbox: A Knox box is required for this project. Approved boxes can be ordered from www.knoxbox.com Mr. Koch August 11, 2016 Page 2 LAKEHAVEN UTILITY DISTRICT (Brian Asbury, 253-946-5407, BAsbury@lakehaven.org) WATER • Lakehaven issued a Certificate of Water Availability for the proposed project/property on 12/10/15, Certificate is valid for one-year from date of issuance. • Hydraulic model results (FF #148) indicate that Lakehaven's standard maximum allowable velocity of 10 ft/s is exceeded at a fire flow rate above 1,600 gpm. Fire flow rates greater than available in the existing distribution system may be accommodated through water distribution system improvements. Please contact Lakehaven for further detail. • A new hydrant (as indicated on the preliminary Drainage, Grading & Utility Plan) is not required. • A new Double Check Detector Assembly is not required (as indicated on the preliminary Drainage, Grading & Utility Plan), because the water main proposed for the new fire -protection service connection is an existing private water main with an existing DCDA at the point -of -connection to Lakehaven's water distribution system. SEWER • Lakehaven issued a Certificate of Sewer Availability for the proposed project/property on 12/10/15; Certificate is valid for one-year from date of issuance. • The preliminary plans do not indicate any sewer service line work, implying that new plumbing drains in the new building addition will connect to existing building plumbing (contact building official for requirements &/or additional information). • If any sewer service line work (i.e., underground work outside of the building) is proposed, a separate Lakehaven sewer service connection permit would be required. Minimum pipe slope for gravity sewer service connections is 2%. GENERAL All comments herein are valid for one (1) year and are based on the proposal(s) submitted and Lakehaven's current regulations and policies. Any change to either the development proposal(s) or Lakehaven's regulations and policies may affect the above comments accordingly. Sincerely, Dave Van De eghe Senior Planner enc: Lakehaven Utility Map 16-1034S2 Doc I D 74369 CITY OF FEDERAL WAY COMMUNITY DEVELOPMENT DEPARTMENT DEVELOPMENT REVIEW COMMITTEE TRANSMITTAL DATE: July 19, 2016 TO: E.J. Walsh, Development Services Manager Cole Elliott, Development Services Manager for PW Peter Lawrence, Plans Examiner Brian Asbury, Lakehaven Utility District Vince Faranda, South King Fire & Rescue Rick Perez, City Traffic Engineer FROM: Dave Van De Weghe FOR DRC MTG. ON: Internal Review on August 4, 2016 FILE NUMBER(s): 16-103452-00-UP RELATED FILE NOS.: none PROJECT NAME: Belmor Park Clubhouse Addition PROJECT ADDRESS: ZONING DISTRICT: PROJECT DESCRIPTION: 2101 S 324th St RM 3.6 Proposed addition to existing golf course clubhouse building to include fitness, circulation, storage, activity office, restrooms, billiards room and card room spaces. A new fire sprinkler system will be provided throughout the new addition and existing building. LAND USE PERMITS: Use Process II PROJECT CONTACT: AKS Architecture, Robert Koch - Architect 1011 SW Klickitat Way, Suite 102 Seattle, WA 98134 (206)954-9505 Robertkochl@me.com MATERIALS SUBMITTED: Cover Sheet Expansive Site Plan Site Plan Topographic Survey Drainage, Grading and Right of Way Plan Exterior Elevations Material Board 3D Images 4ik CITY 40';:tSp OF Federal Way MASTER LAND USE APPLICATION DEPARTMENT OF COMMUNITY DEVELOPMENT SERVICES RECEWED33325 8"' Avenue South Federal Way, WA 98003-6325 JUL 18 2016 253-835-2607; Fax 253-835-2609 www.cityoffederalway.com CITY OF FEDERAL WAY CDS APPLICATION NO(s) _ I r ( O V l /,o Date 7.15.16 Project Name Belmor Park Golf & Country Club Addition Property Address/Location 2101 S 324TH Street Parcel Number(s) 1621049037 Project Description Addition to existing golf course clubhouse building to include fitness, circulation, storage, activity office, restrooms, billiards room and card room spaces. A new fire sprinkler system will be provided throughout the new adiditon and existing building. PLEASE PRINT Type of Permit Required _ Annexation Binding Site Plan Boundary Line Adjustment Comp Plan/Rezone _ Land Surface Modification _ Lot Line Elimination Preapplication Conference _ Process I (Director's Approval) X Process II (Site Plan Review) Process III (Project Approval) Process IV (Hearing Examiner's Decision) Process V (Quasi -Judicial Rezone) Process VI SEPA w/Project SEPA Only _ Shoreline: Variance/Conditional Use _ Short Subdivision _ Subdivision Variance: Commercial/Residential Required Information RM 3600 Zoning Designation RM 3600 Comprehensive Plan Designation $1,250,000 Value of Existing Improvements $800,000 Value of Proposed Improvements International Building Code (IBC): A-3 Occupancy Type V-B Construction Type Applicant Name: Belmor Park Golf & Country Club - Tyler Flint, Manager Address: 2101 S 324th Street City/State: Federal Way, WA Zip: 98003 Phone: (253) 838-0517 Fax: (253)838-6865 Email: tfiint§hynesnet. m Signature: � Agent (if different than Applicant) Name: AKS Architecture, Robert Koch - Architect Address: 1011 SW Klickitat Way, Suite 102 City/State: Seattle, WA Zip: 98134 Phone: (206) 954-9505 Fax: (206)682-3484 Email: robertkochl @me.com Signature: 12. Owner - Qe fcesz-\6i vc Name: Belmor Park Golf & Country Club - Tyler Flint, Manager Address: 2101 S 324th Street City/State: Federal Way, WA Zip: 98003 Phone: (253) 838-0517 Fax: (253)838-6865 Email: tflint@hynesnet.com Signature: �f Bulletin #003 — January 1, 2011 Page 1 of 1 k:\Handoutsuvlaster Land Use Application