PROJECT INFORMATION
PROJECT DESCRIPTION:
AT&T PROPOSES TO MODIFY EXISTING UNSTAFFED TELECOMMUNICATIONS FACILITY BY REMOVING AN EXISTING ANTENNA MOUNT
AND RELOCATING (3) EXISTING ANTENNAS TO A NEW ANTENNA MOUNT EXTENSION WITH THE ADDITION OF (3) LTE PANEL
ANTENNAS, (3) TMA'S. PLUS THE ADDITION OF (6) RRH UNITS, (6) DIPLEXERS MOUNTED TO A NEW H-FRAME ALONG WITH
(1) LTE EQUIPMENT RACK MOUNTED WITHIN EXISTING AT&T EQUIPMENT ROOM LOCATED BETWEEN STORAGE DOORS #152 AND
#149.
APPLICANT:
AT&T MOBILITY
RTC BUILDING 3
16221 NE 72ND WAY
REDMOND, WA 98052
CODE INFORMATION:
ZONING CLASSIFICATION: BN
BUILDING CODE: 2009 IBC
CONSTRUCTION TYPE: IIB
OCCUPANCY: U, S-2
JURISDICTION: CITY OF FEDERAL WAY
CURRENT USE: UNMANNED TELECOM FACILITY
PROPOSED USE: UNMANNED TELECOM FACILITY
SITE LOCATION: (BASED ON NAD 83
LATITUDE: 47° 19' 25.5" N
LONGITUDE: -122° 21' 37.2" W
TOP OF STRUCTURE AGL: 53'-6"
BASE OF STRUCTURE AMSL: 276'-0"
PARCEL NUMBER (Si:
1221039088, 1221039087
GENERAL INFORMATION:
1. PARKING REQUIREMENTS ARE UNCHANGED.
2. TRAFFIC IS UNAFFECTED.
PROPERTY OWNER:
FEDERAL WAY SELF STORAGE INVESTORS, LLC
14100 SE 36TH ST, STE 200
BELLEVUE, WA 98006
TOWER OWNER:
PUGET SOUND ENERGY
355 110TH AVE NE EST-06E
BELLEVUE, WA 98004
CONTACT: TIM GASSER
PH: (425) 456-2776
TEAM LEAD:
WESTOWER COMMUNICATIONS
7525 SE 24TH STREET,, -SUITE 500
MERCER ISLAND, WA-98040
CONTACT: KEITH ELWELL
PH: (425) 753-3458
SITE ACQUISITION:
PACIFIC TELECOM SERVICES, LLC
111 SOUTH JACKSON STREET 2ND FLOOR
SEATTLE, WA 98104
CONTACT: BECKY TODD
PH: (206) 342-6388
PERMITTING:
PACIFIC TELECOM SERVICES, LLC
111 SOUTH JACKSON STREET, 2ND FLOOR
SEATTLE, WA 98104
CONTACT: SUNNY AUSINK
PH: (206) 342-6390
CONSTRUCTION MANAGER:
WESTOWER COMMUNICATIONS
7525 SE 24TH STREET, SUITE 500
MERCER ISLAND, WA 98040
CONTACT- KEITH ELWELL
PH: (425) 753-3458
RF ENGINEER:
WESTOWER COMMUNICATIONS
7525 SE 24TH STREET, SUITE 500
MERCER ISLAND, WA 98040
CONTACT: MICHELLE BRAASCH
PROJECT TEAM
PROJECT ARCHITECT PROJECT CONSULTANT PROJECT CONSULTANT
RICHARD B. HALL, AIA PACIFIC TELECOM SERVICES, LLC WESTOWER COMMUNICATIONS
PACIFIC TELECOM SERVICES, LLC 111 SOUTH JACKSON STREET, 2ND FLOOR 7525 SE 24TH STREET, SUITE 500
111 SOUTH JACKSON STREET, 2ND FLOOR SEATTLE, WA 98104 MERCER ISLAND, WA 98040
SEATTLE, WA 98104 CONTACT: KATIE KENNEY PH: (206) 819-4727
CONTACT: CHRIS WICKLANDER PH: (206) 909-9454
PH: (425) 478-7988
EMAIL: CWICKLANDERQPTSWA.COM
SS66
31031 21ST PLACE SW
FEDERAL WAY, WA 98023
VICINITY MAP
DRIVING DIRECTIONS
START FROM REGIONAL OFFICE:
DEPART NE 72ND WAY TOWARD 164TH AVE NE
475
FT
TURN RIGHT ONTO 164TH AVE NE, AND THEN IMMEDIATELY
TURN RIGHT ONTO BEAR CREEK PKWY
0.4
MI
TURN LEFT ONTO LEARY WAY NE
0.1
MI
ROAD NAME CHANGES TO NE LEARY WAY
0.2
MI
TAKE RAMP RIGHT FOR WA-520 WEST TOWARD SEATTLE
5.0
MI
TAKE RAMP RIGHT FOR 1-405 SOUTH TOWARD RENTON
15.0
MI
ROAD NAME CHANGES TO WA-518 WEST
0.1
MI
TAKE RAMP RIGHT FOR 1-5 SOUTH TOWARDPORTLAND
7.6
MI
AT EXIT 147, TAKE RAMP RIGHT AND FOLLOW SIGNS FOR S. 272ND ST.
0.3
MI
TURN RIGHT ONTO S 272ND ST
0.6
MI
TURN LEFT ONTO WA-99 / PACIFIC HWY S
0.5
MI
KEEP STRAIGHT ONTO WA-99 / WA-509 / PACIFIC HWY S
1.1
MI
TURN RIGHT ONTO WA-509 / S DASH POINT RD
2.8
MI
TURN RIGHT ONTO 21 ST WAY SW
0.2
MI
ARRIVE AT 31031 21ST WAY SW, FEDERAL WAY, WA 98023
APPROVAL
DATE
SIGNATURE
APPROVAL
DATE
SIGNATURE
RF ENGINEER:
LANDLORD:
RF MANAGER:
SITE ACQUISITION:
OPPS MANAGER:
ZONING AGENT:
CONSTR MANAGER:
PROJECT MANAGER:
NSB MANAGER:
CONSTR MANAGER:
TRANSPORT:
EQUIP ENGINEER:
COMPLIANCE:
REVIEWERS SHALL CLEARLY PLACE INITIALS ADJACENT TO
EACH REDLINE NOTE AS DRAWINGS ARE
BEING REVIEWED
THE INFORMATION CONTAINED IN THIS SET OF CONSTRUCTION DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE O I HER I HAN I HAI WHICH RLLAI L5 I U CARRILR `SERVICES 15 `S I NIC I LY PROHIt3I 1 LU.
DRAWING INDEX
SHEET IDESCRIPTION
T-1 TITLE SHEET
G-1 GENERAL NOTES & SYMBOLS
A-1 SITE PLAN
A-2 EXISTING EQUIPMENT & ANTENNA PLAN
A-3 PROPOSED EQUIPMENT & ANTENNA PLAN
A-4 EXISTING & PROPOSED SOUTHEAST ELEVATION
A-5 CONSTRUCTION DETAILS
A-6 CONSTRUCTION DETAILS
RF-1 ANTENNA CONFIGURATIONS
RF-2 RF & EQUIPMENT DETAILS
E-1 SCHEMATIC GROUNDING PLAN
E-2 GROUNDING DETAILS
ABBREVIATIONS
PROPRIETARY INFORMATION
THE INFORMATION CONTAINED IN THIS SET OF
CONSTRUCTION DOCUMENTS IS PROPRIETARY BY NATURE.
ANY USE OR DISCLOSURE OTHER THAN THAT WHICH
RELATES TO CARRIER SERVICES IS STRICTLY PROHIBITED.
FINAL
CONSTR.LICTION DRAWINGS
0+04-12
LEGAL DESCRIPTION
PARCEL A:
THAT PORTION OF THE WEST 135 FEET OF THE SOUTHEAST QUARTER OF
THE NORTHEAST QUARTER OF SECTION 12, TOWNSHIP 21 NORTH, RANGE 3
EAST, W.M., LYING SOUTHWESTERLY OF COUNTY ROAD NO 980 (J.M.
ERCHINGER ROAD, AS CONVEYED BY DEED RECORDED UNDER RECORDING
NO. 980310) AND NORTH OF THE FOLLOWING DESCRIBED LINE;
BEGINNING AT A POINT ON THE EAST LINE OF SAID WEST 135 FEET WHICH
IS 80 FEET SOUTH OF THE SOUTHWESTERLY MARGIN OF SAID COUNTY
ROAD; THENCE WEST AT RIGHT ANGLES TO SAID EAST LINE 135 FEET TO
THE EST LINE OF SAID SOUTHEAST QUARTER OF THE NORTHEAST QUARTER
AND THE TERMINUS OF THE LINE HEREIN DESCRIBED.
SITUATE IN THE COUNTY OF KING, STATE OF WASHINGTON.
PARCEL B:
AN UNDIVIDED HALF INTEREST IN THE FOLLOWING DESCRIBED PROPERTY:
THE WEST 165 FEET OF THAT PORTION OF THE SOUTHEAST QUARTER OF
THE NORTHEAST QUARTER OF SECTION 12, TOWNSHIP 21 NORTH, RANGE 3
EAST, W.M., LYING SOUTHWESTERLY OF COUNTY ROAD NO. 980 AS
CONVEYED BY DEED RECORDED UNDER RECORDING NO. 980310;
EXCEPT THAT PORTION LYING NORTH OF A LINE RUNNING WEST AT RIGHT
ANGLES FROM A POINT ON THE EAST LINE OF THE WEST 135 FEET OF
SAID SUBDIVISION WHICH IS 80 FEET SOUTH OF THE SOUTHWESTERLY
MARGIN OF SAID COUNTY ROAD NO. 980, TO THE WEST LINE OF SAID
SOUTHEAST QUARTER OF THE NORTHEAST QUARTER.
SITUATE IN THE COUNTY OF KING, STATE OF WASHINGTON.
PARCEL C:
AN UNDIVIDED HALF INTEREST IN THE FOLLOWING DESCRIBED PROPERTY:
THE EAST 135 FEET OF THE WEST 300 FEET OF THAT PORTION OF THE
SOUTHEAST QUARTER OF THE NORTHEAST QUARTER OF SECTION 12,
TOWNSHIP 21 NORTH, RANGE 3 EAST, W.M., LYING SOUTHEASTERLY OF
COUNTY ROAD NO. 980 (ERCHINGER ROAD, 21ST PLACE SOUTHWEST AS
CONVEYED BY DEED RECORDED UNDER RECORDING NO. 980310).
SITUATE IN THE COUNTY OF KING, STATE OF WASHINGTON.]
PARCEL D:
AN UNDIVIDED HALF INTEREST IN THE FOLLOWING DESCRIED PROPERTY:
THAT PORTION OF THE SOUTHEAST QUARTER OF THE NORTHEAST QUARTER
OF SECTION 12, TOWNSHIP 21 NORTH, RANGE 3 EAST W.M., LYING
SOUTHWESTERLY OF COUNTY ROAD NO. 980 (21ST AVENUE SOUTHWEST AS
CONVEYED BY DEED RECORDED UNDER RECORDING NO. 980310;)
EXCEPT THE WESTERLY 300 FEET THEREOF;
SITUATED IN THE COUNTY OF KING, SATED OF WASHINGTON
A/C
AIR CONDITIONING
HORZ
HORIZONTAL
PLYWD
PLYWOOD
AGL
ABOVE GROUND LEVEL
HR
HOUR
PROJ
PROJECT
APPROX
APPROXIMATELY
HT
HEIGHT
PROP
PROPERTY
HVAC
HEATING
PT
PRESSURE TREATED
BLDG
BUILDING
VENTILATION
REQ
REQUIRED
BLK
BLOCKING
AIR CONDITIONING
RM
ROOM
SHT
SHEET
CLG
CEILING
ID
INSIDE DIAMETER
SIM
SIMILAR
-,
CLR
CLEAR
IN
INCH
SPEC
SPECIFICATION
CONC
CONCRETE
INFO
INFORMATION
SF
SQUARE FOOT
CONST
CONSTRUCTION
INSUL
INSULATION
SS
STAINLESS STEEL
CONT
CONTINUOUS
INT
INTERIOR
STL
STEEL
IBC
INTERNATIONAL
STRUCT
STRUCTURAL
�
DBL
DOUBLE
BUILDING CODE
STD
STUD
-
DIA
DIAG
DIAMETER
DIAGONAL
LBS
POUNDS
SUSP
SUSPENDED
DN
DOWN
MAX
MAXIMUM
THRU
THROUGH
DET
DWG
DETAIL
DRAWING
MECH
MTL
MECHANICAL
METAL
TNNG
TYP
TINNED
TYPICAL
- -
MFR
MANUFACTURE
EA
EACH
MGR
MANAGER
UNO
UNLESS NOTED OTHERWISE
ELEV
ELEVATION
MIN
MINIMUM
ELEC
ELECTRICAL
MISC
MISCELLANEOUS
VERT
VERTICAL
EQ
EQUAL
RO
ROUGH OPENING
VIF
VERIFY IN FIELD
EQUIP
EQUIPMENT
EXT
EXTERIOR
NA
NOT APPLICABLE
W/
WITH
NIC
NOT IN CONTRACT
W�O
WITHOUT
FIN
FINISH
NTS
NOT TO SCALE
WP
WATER PROOF
FLUOR
FLOURESCENT
FLR
FLOOR
OC
ON CENTER
FT
FOOT
OD
OUTSIDE DIAMETER
RECEIVED
GA
GAUGE
APR U 6 201z
GALV
GALVANIZED
GC
GENERAL CONTRACTOR
GRND
GROUND
CITY OF FEDERAL WAY
GYP BD
GYPSUM WALL BOARD
CDS
Dat&t
Your world. Delivered.
PACIFIC TELECOM SERVICES,
LLC
8828
REGISTERED
ARCHITT�C-
�
C
CH
TATE
D B. HA
F WASHIN N
EXPIRATION DATE OF THE
LICENSE: 08/20113
F�
�
N
U)
O
00
w
n-
o�
U)
N
<
O
w
Q
w
O
w
w
w
REVISIONS
NO.
DATE
I DESCRIPTION
INITIAL
A
12/07/11
ISSUED FOR PCD REVIEW
RC
0
04/04/12
ISSUED FOR FINAL CONSTRUCTION
RLD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
SHEET TITLE
TITLE SHEET
SHEET NUMBER
T-1
GENERAL NOTES:
1. THE CONTRACTOR SHALL NOTIFY TOWER NETWORK CARRIER OF ANY
ERRORS, OMISSIONS, OR INCONSISTENCIES AS THEY MAY BE DISCOVERED
IN PLANS, DOCUMENTS, NOTES, OR SPECIFICATIONS PRIOR TO STARTING
CONSTRUCTION INCLUDING, BUT NOT LIMITED BY, DEMOLITION. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR CORRECTING ANY ERROR,
OMISSION, OR INCONSISTENCY AFTER THE START OF CONSTRUCTION WHICH
HAS NOT BEEN BROUGHT TO THE ATTENTION OF TOWER NETWORK CARRIER
CONSTRUCTION PROJECT MANAGER AND SHALL INCUR ANY EXPENSES TO
RECTIFY THE SITUATION. THE MEANS OF CORRECTING ANY ERROR SHALL
FIRST BE APPROVED BY TOWER NETWORK CARRIER CONSTRUCTION
PROJECT MANAGER.
2. PRIOR TO THE SUBMISSION OF BIDS, CONTRACTORS INVOLVED SHALL VISIT
THE JOB SITE TO FAMILIARIZE THEMSELVES WITH ALL CONDITIONS
AFFECTING THE PROPOSED PROJECT. CONTRACTORS PRIOR TO THE
COMMENCEMENT OF CONSTRUCTION, THE CONTRACTOR HAVING BEEN
AWARDED THIS PROJECT SHALL VISIT THE CONSTRUCTION SITE WITH THE
CONSTRUCTION/CONTRACT DOCUMENTS TO VERIFY FIELD CONDITIONS AND
CONFIRM THAT THE PROJECT WILL BE ACCOMPLISHED AS SHOWN. PRIOR
TO PROCEEDING WITH CONSTRUCTION, ANY ERRORS, OMISSIONS, OR
DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT/ENGINEER VERBALLY AND IN WRITING.
3. FOR COLLOCATION SITES: CONTACT TOWER OWNER REPRESENTATIVE FOR
PARTICIPATION IN BID WALK.
4. NOT USED
5. THE ARCHITECTS/ENGINEERS HAVE MADE EVERY EFFORT TO SET FORTH IN
THE CONSTRUCTION AND CONTRACT DOCUMENTS THE COMPLETE SCOPE OF
WORK. CONTRACTORS BIDDING THE JOB ARE NEVERTHELESS CAUTIONED THAT
MINOR OMISSIONS OR ERRORS IN THE DRAWINGS AND OR SPECIFICATIONS
SHALL NOT EXCUSE SAID CONTRACTOR FROM COMPLETING THE PROJECT AND
IMPROVEMENTS IN ACCORDANCE WITH THE INTENT OF THESE DOCUMENTS.
THE BIDDER SHALL BEAR THE RESPONSIBILITY OF NOTIFYING (IN WRITING)
THE ARCHITECT/ENGINEER OF ANY CONFLICTS, ERRORS, OR OMISSIONS PRIOR
TO SUBMISSION OF CONTRACTOR'S PROPOSAL. IN THE EVENT OF
DISCREPANCIES THE CONTRACTOR SHALL PRICE THE MORE COSTLY OR
EXTENSIVE WORK, UNLESS DIRECTED OTHERWISE.
6. DRAWINGS ARE NOT TO BE SCALED UNDER ANY CIRCUMSTANCE. TOWER NETWORK
CARRIER IS NOT RESPONSIBLE FOR ANY ERRORS RESULTING FROM THIS PRACTICE
WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALE SHOWN ON PLANS.
7. OWNER, CONTRACTOR, AND TOWER NETWORK CARRIER CONSTRUCTION
PROJECT MANAGER SHALL MEET JOINTLY TO VERIFY ALL DRAWINGS AND
SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION.
8. THE GENERAL CONTRACTOR SHALL RECEIVE WRITTEN AUTHORIZATION TO
PROCEED WITH CONSTRUCTION PRIOR TO STARTING WORK ON ANY ITEM NOT
CLEARLY DEFINED BY THE CONSTRUCTION DRAWINGS/CONTRACT DOCUMENTS.
9. THE CONTRACTOR SHALL PERFORM WORK DURING OWNER'S PREFERRED
HOURS TO AVOID DISTURBING NORMAL BUSINESS.
10. THE CONTRACTOR SHALL PROVIDE TOWER NETWORK CARRIER PROPER INSURANCE
CERTIFICATES NAMING TOWER NETWORK CARRIER AS ADDITIONAL INSURED, AND
TOWER NETWORK CARRIER PROOF OF LICENSE(S) AND PE & PD INSURANCE.
11. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE PROJECT DESCRIBED IN
THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE SOLELY
RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, TECHNIQUES,
SEQUENCES, AND PROCEDURES FOR COORDINATING ALL PORTIONS OF THE
WORK UNDER THE CONTRACT.
12. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS
ACCORDING TO MANUFACTURER'S/VENDOR'S SPECIFICATIONS UNLESS NOTED
OTHERWISE OR WHERE LOCAL CODES OR ORDINANCES TAKE PRECEDENCE.
13. ALL WORK PERFORMED ON THE PROJECT AND MATERIALS INSTALLED SHALL
BE IN STRICT ACCORDANCE WITH ALL APPLICABLE CODES, REGULATIONS, AND
ORDINANCES. CONTRACTOR SHALL GIVE ALL NOTICES AND COMPLY WITH
ALL LAWS, ORDINANCES, RULES, REGULATIONS AND LAWFUL ORDERS OF ANY
PUBLIC AUTHORITY, MUNICIPAL AND UTILITY COMPANY SPECIFICATIONS, AND
LOCAL AND STATE JURISDICTIONAL CODES BEARING ON THE PERFORMANCE
OF THE WORK.
14. NOT USED
15. A COPY OF GOVERNING AGENCY IS APPROVED PLANS SHALL BE KEPT IN A
PLACE SPECIFIED BY THE GOVERNING AGENCY, AND BY LAW, SHALL BE
AVAILABLE FOR INSPECTION AT ALL TIMES. THE ORIGINAL PERMIT SET PLANS
ARE NOT TO BE USED BY THE WORKMEN. ALL CONSTRUCTION SETS SHALL
REFLECT THE SAME INFORMATION AS GOVERNING AGENCY APPROVED PLANS.
THE CONTRACTOR SHALL ALSO MAINTAIN ONE SET OF PLANS, IN GOOD
CONDITION, COMPLETE WITH ALL REVISIONS, ADDENDA, AND CHANGE ORDERS
ON THE PREMISES AT ALL TIMES UNDER THE DIRECT CARE OF THE
SUPERINTENDENT. THE CONTRACTOR SHALL SUPPLY TOWER NETWORK
CARRIER CONSTRUCTION PROJECT MANAGER. WITH A COPY OF ALL REVISIONS,
ADDENDA, AND/OR CHANGE ORDERS AT THE CONCLUSION OF THE WORK AS
A PART OF THE AS -BUILT DRAWING RECORDS.
16. THE STRUCTURAL COMPONENTS OF ADJACENT CONSTRUCTION OR FACILITIES
ARE NOT TO BE ALTERED BY THIS CONSTRUCTION PROJECT UNLESS NOTED
OTHERWISE.
17. THE CONTRACTOR SHALL STUDY THE STRUCTURAL, ELECTRICAL, MECHANICAL,
AND PLUMBING PLANS AND CROSS CHECK THEIR DETAILS, NOTES,
DIMENSIONS, AND ALL REQUIREMENTS PRIOR TO THE START OF ANY WORK.
18. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COMPLETE SECURITY OF
THE PROJECT AND SITE WHILE THE WORK IS IN PROGRESS UNTIL THE JOB
IS COMPLETE.
19. THE CONTRACTOR HAS THE RESPONSIBILITY OF LOCATING ALL EXISTING
UTILITIES WHETHER OR NOT SHOWN ON THE PLANS, AND TO PROTECT THEM
FROM DAMAGE. THE CONTRACTOR, OR SUBCONTRACTOR AS SPECIFIED IN THE
AGREEMENT BETWEEN SUBCONTRACTOR AND CONTRACTOR, SHALL BEAR THE
EXPENSES OF REPAIR AND/OR REPLACEMENT OF UTILITIES OR OTHER
PROPERTY DAMAGE BY OPERATIONS IN CONJUNCTION WITH THE EXECUTION
OF THE WORK.
20. THE REFERENCES ON THE DRAWINGS ARE FOR CONVENIENCE ONLY AND
SHALL NOT LIMIT THE APPLICATION OF ANY DRAWING OR DETAIL.
21. ALL DIMENSIONS ON THE PLANS ARE TO FACE OF STUD (F.O.S.) UNLESS
NOTED OTHERWISE (U.N.O.).
22. ALL EXISTING CONSTRUCTION, EQUIPMENT, AND FINISHES NOTED TO BE
REMOVED SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND WILL
BE REMOVED FROM THE SITE WITH THE FOLLOWING EXCEPTIONS:
A. PROPERTY NOTED TO BE RETURNED TO THE OWNER.
B. PROPERTY NOTED TO BE REMOVED BY THE OWNER.
23. THE GOVERNING AGENCIES, CODE AUTHORITIES, AND BUILDING INSPECTORS
SHALL PROVIDE THE MINIMUM STANDARDS FOR CONSTRUCTION TECHNIQUES,
MATERIALS, AND FINISHES USED THROUGHOUT THE PROJECT. TRADE
STANDARDS AND/OR PUBLISHED MANUFACTURERS SPECIFICATIONS MEETING
OR EXCEEDING DESIGN REQUIREMENTS SHALL BE USED FOR INSTALLATION.
24. WHEN REQUIRED STORAGE OF MATERIALS OCCURS, THEY SHALL BE EVENLY
DISTRIBUTED OVER ROUGH FRAMED FLOORS OR ROOFS SO AS NOT TO
EXCEED THE DESIGNED LIVE LOADS FOR THE STRUCTURE. TEMPORARY
SHORING AND/OR BRACING IS TO BE PROVIDED WHERE THE STRUCTURE HAS
NOT ATTAINED THE DESIGN STRENGTH FOR THE CONDITIONS PRESENT.
25. PRIOR TO THE POURING OF ANY NEW SLAB OVER AN EXISTING SLAB THE
CONTRACTOR SHALL VERIFY LOCATIONS OF ALL OPENINGS, CHASES, AND
EQUIPMENT WHICH ARE TO BE IMPLEMENTED INTO THE NEW WORK. ALL
ITEMS DESIGNATED TO BE ABANDONED SHALL BE NOTED AND DISCUSSED
WITH THE OWNER AND TOWER NETWORK CARRIER CONSTRUCTION PROJECT
MANAGER AS PART OF THE AS -BUILT DRAWING PACKAGE.
26. SEAL ALL PENETRATIONS THROUGH FIRE -RATED AREAS WITH U.L. LISTED OR
FIRE MARSHALL APPROVED MATERIALS IF APPLICABLE TO THIS FACILITY AND
OR PROJECT SITE.
27. BUILDING INSPECTORS AND/OR OTHER BUILDING OFFICIALS ARE TO BE
NOTIFIED PRIOR TO ANY GRADING, CONSTRUCTION, AND ANY OTHER PROJECT
EFFORT AS MANDATED BY THE GOVERNING AGENCY.
28. CONTRACTOR TO PROVIDE A PORTABLE FIRE EXTINGUISHER WITH A RATING OF
NOT LESS THAN 2-A OR 2-A10BC WITHIN 75 FEET TRAVEL DISTANCE TO
ALL PORTIONS OF PROJECT AREA DURING CONSTRUCTION.
29. THE PROJECT, WHEN COMPLETED, SHALL COMPLY WITH LOCAL SECURITY
CODES AND TITLE-24 ENERGY CONSERVATION REQUIREMENTS. (TITLE-24
WHEN APPLICABLE)
30. ALL GLASS AND GLAZING IS TO COMPLY WITH CHAPTER 54 OF THE U.S.
CONSUMER SAFETY COMMISSION - SAFETY STANDARDS FOR ARCHITECTURAL
GLAZING MATERIALS (42 FR 1428, CFR PART 1201) AND LOCAL SECURITY
REQUIREMENTS.
31. CONTRACTOR SHALL MAKE NECESSARY PROVISIONS TO PROTECT EXISTING
IMPROVEMENTS EASEMENTS PAVING CURB
ING, ETC. DURING CONSTRUCTION.
UPON COMPLETION OF WORK, CONTRACTOR SHALL REPAIR ANY DAMAGE
THAT MAY HAVE OCCURRED DUE TO CONSTRUCTION ON OR ABOUT THE
PROPERTY,
32. CONTRACTOR SHALL KEEP GENERAL WORK AREA CLEAN AND HAZARD FREE
DURING CONSTRUCTION AND DISPOSE OF ALL DIRT, DEBRIS, AND RUBBISH.
CONTRACTOR SHALL REMOVE EQUIPMENT NOT SPECIFIED AS REMAINING ON
THE PROPERTY OR PREMISES. SITE SHALL BE LEFT IN CLEAN CONDITION
AND FREE FROM PAINT SPOTS, DUST, OR SMUDGES OF ANY NATURE.
33. NEW CONSTRUCTION ADDED TO EXISTING CONSTRUCTION SHALL MATCH IN
FORM, TEXTURE, FINISH, AND IN MATERIALS EXCEPT AS NOTED IN THE PLANS
AND SPECIFICATIONS.
34. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY BACKING, BLOCKING,
AND/OR SLEEVES REQUIRED FOR THE INSTALLATION OF FIXTURES,
MECHANICAL EQUIPMENT, PLUMBING, HARDWARE, AND FINISH ITEMS TO
INSURE A PROPER AND COMPLETE JOB.
35. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING A PROJECT LEVEL,
STRAIGHT, AND TRUE ACCORDING TO THE PLANS. THE CONTRACTOR SHALL
COMPARE THE LINES AND LEVELS OF THE EXISTING CONDITIONS WITH THOSE
SHOWN ON THE PLANS PRIOR TO THE START OF ANY CONSTRUCTION. TOWER
NETWORK CARRIER SHALL BE NOTIFIED OF ANY ERRORS, OMISSIONS, OR
INCONSISTENCIES PRIOR TO ANY CONSTRUCTION.
36. THE CONTRACTOR IS TO PROVIDE PROTECTION FOR ADJOINING PROPERTIES
FROM PHYSICAL HARM, NOISE, DUST, DIRT, AND FIRE AS REQUIRED BY THE
GOVERNING AGENCIES.
37. WHERE SPECIFIED, MATERIALS TESTING SHALL BE TO THE LATEST STANDARDS
AND/OR REVISIONS AVAILABLE AS REQUIRED BY THE GOVERNING AGENCY
RESPONSIBLE FOR RECORDING THE RESULTS.
38. THE CONTRACTOR IS RESPONSIBLE FOR THE STORAGE OF ALL MATERIALS
AND SHALL NOT DO SO ON PUBLIC PROPERTY WITHOUT A PERMIT TO DO
SO FROM THE GOVERNING AGENCIES FOR THIS PURPOSE.
39. GENERAL NOTES AND STANDARD DETAILS ARE THE MINIMUM REQUIREMENTS
TO BE USED IN CONDITIONS WHICH ARE NOT SPECIFICALLY SHOWN
OTHERWISE.
40. TRADES INVOLVED IN THE PROJECT SHALL BE RESPONSIBLE FOR THEIR
OWN CUTTING, FITTING, PATCHING, ETC., SO AS TO BE RECEIVED
PROPERLY BY THE WORK OF OTHER TRADES.
41. ALL DEBRIS AND REFUSE IS TO BE REMOVED FROM THE PROJECT PREMISES
AND SHALL BE LEFT IN A CLEAN (BROOM FINISH) CONDITION AT ALL TIMES
BY EACH TRADE AS THEY PERFORM THEIR OWN PORTION OF THE WORK.
42. TOWER NETWORK CARRIER DOES NOT GUARANTEE ANY PRODUCTS, FIXTURES,
AND/OR ANY EQUIPMENT NAMED BY A TRADE OR MANUFACTURER. GUARANTEE
OR WARRANTY THAT MAY BE IN EFFECT IS DONE SO THROUGH THE COMPANY
OR MANUFACTURER PROVIDING THE PRODUCT, FIXTURE, AND/OR EQUIPMENT
ONLY: UNLESS SPECIFIC RESPONSIBILITY IS ALSO PROVIDED BY THE
CONTRACTOR/SUBCONTRACTOR IN WRITTEN FORM.
43. CAUTION! CALL BEFORE YOU DIG! BURIED UTILITIES EXIST IN THE AREA
AND UTILITY INFORMATION SHOWN MAY NOT BE COMPLETE. CONTACT
THE ONE -CALL UTILITY LOCATE SERVICE A MINIMUM OF 48 HOURS PRIOR
TO CONSTRUCTION. 1-800-227-2600.
44. CONTRACTOR TO REPLACE AND/OR REROUTE ANY EXISTING UNDERGROUND
UTILITIES ENCOUNTERED DURING TRENCHING AND GENERAL CONSTRUCTION.
45. WHEN APPLICABLE, CONTRACTOR IS RESPONSIBLE TO CALL, COORDINATE AND
MAKE ARRANGEMENTS FOR ROW AND/OR PRIVATE PROPERTY LOCATE
MODIFICATION CONSTRUCTION; BASED ON SPECIFIC SITE REQUIREMENTS.
46. SEE CIVIL DRAWINGS FOR ADDITIONAL SITE INFORMATION.
47. CONTRACTORS TO DOCUMENT ALL WORK PERFORMED WITH PHOTOGRAPHS AND
SUBMIT TO TOWER NETWORK CARRIER ALONG WITH REDLINED CONSTRUCTION SET.
48. CONTRACTOR SHALL DOCUMENT ALL CHANGES MADE IN THE FIELD BY
MARKING UP (REDLINING) THE APPROVED CONSTRUCTION SET AND
SUBMITTING THE REDLINED ALONG WITH PHOTOGRAPHS PER NETWORK
CARRIER REQUIREMENTS.
49. GENERAL CONTRACTOR IS TO COORDINATE ALL POWER INSTALLATION
WITH POWER COMPANY AS REQUIRED. CONTRACTOR TO REPORT POWER
INSTALLATION COORDINATION SOLUTION(S) TO NETWORK CARRIER
REPRESENTATIVE, PROJECT CONSTRUCTION MANAGER AND ARCHITECT.
50. ANY SUBSTITUTIONS OF MATERIALS AND/OR EQUIPMENT, MUST BE
APPROVED BY TOWER NETWORK CARRIER CONSTRUCTION MANAGER.
51. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR AND SHALL REMEDY
ALL FAULTY, INFERIOR, AND/OR IMPROPER MATERIALS, DAMAGED GOODS,
AND/OR FAULTY WORKMANSHIP FOR ONE (1) YEAR AFTER THE PROJECT IS
COMPETE AND ACCEPTED UNDER THIS CONTRACT; UNLESS NOTED OTHERWISE
IN THE CONTRACT BETWEEN THE OWNER AND THE CONTRACTOR.
(EXCEPTION) THE ROOFING SUBCONTRACTOR SHALL FURNISH A MAINTENANCE
AGREEMENT FOR ALL WORK DONE, COSIGNED BY THE GENERAL CONTRACTOR,
TO MAINTAIN THE ROOFING IN A WATERTIGHT CONDITION FOR A PERIOD OF
TWO (2) YEARS STARTING AFTER THE DATE OF SUBSTANTIAL COMPLETION OF
THE PROJECT, UNLESS OTHERWISE WRITTEN IN THE CONTRACT BETWEEN THE
OWNER AND THE CONTRACTOR.
52. THE CONTRACTOR SHALL PROVIDE ADEQUATE PROTECTION FOR THE SAFETY
OF THE OWNER'S EMPLOYEES, WORKMEN, AND ALL TIMES DURING THE
CONSTRUCTION OF THE PROJECT.
53. THE CONTRACTOR SHALL BE REQUIRED TO PAY FOR ALL NECESSARY PERMITS
AND/OR FEES WITH RESPECT TO THE WORK TO COMPLETE THE PROJECT.
BUILDING PERMIT APPLICATIONS SHALL BE FILED BY THE OWNER OR HIS
REPRESENTATIVE. CONTRACTOR SHALL OBTAIN PERMIT AND MAKE FINAL
PAYMENT FOR SAID DOCUMENT.
54. NOT USED
55. TOWER NETWORK CARRIER WILL REVIEW AND APPROVE SHOP DRAWINGS AND
SAMPLES FOR CONFORMANCE WITH DESIGN CONCEPT. TOWER NETWORK
CARRIER PROJECT APPROVAL OF A SEPARATE ITEM SHALL NOT INCLUDE
APPROVAL OF AN ASSEMBLY IN WHICH THE ITEM FUNCTIONS.
56. ALL ANTENNAS MOUNTED ON ROOF SUPPORT FRAMES TO BE PROVIDED BY
TOWER NETWORK CARRIER COMMUNICATIONS.
57. CONTRACTOR TO PROVIDE TRENCH AS REQUIRED TO INSTALL BOTH
ELECTRICAL AND TELEPHONE UNDERGROUND CONDUITS (#40 PVC) PER S.C.E.
WORKORDER. BACKFILL WITH CLEAN SAND AND COMPACT TO THE
SATISFACTION OF THE DISTRICTS INSPECTOR. REPLACE FINISH GRADE WITH
MATCHING MATERIALS (GRASS, ASPHALT, CONCRETE, ETC.)
58. CONTRACTOR TO PROVIDE HEAVY STEEL
PLATES AT OPEN TRENCHES FOR
SAFETY AND TO PROTECT EXISTING GROUND SURFACES FROM HEAVY
EQUIPMENT UTILIZED DURING CONSTRUCTION.
59. CONTRACTOR TO PATCH AND REPAIR ALL GROUND SURFACES WITHIN THE
CONSTRUCTION AREA AS NECESSARY TO PROVIDE A UNIFORM SURFACE AND
MAINTAIN EXISTING SURFACE DRAINAGE SLOPES.
60. CONTRACTOR TO REPLACE LANDSCAPE VEGETATION THAT WAS DAMAGED DUE
TO CONSTRUCTION, AND TO MODIFY REMAINING IRRIGATION LINES TO
OPERATING CONDITION, PROVIDING FULL COVERAGE TO IMPACTED AREAS.
61. IN THE CASE OF ROOFTOP SOLUTIONS FOR EQUIPMENT AND/OR ANTENNA
FRAMES WHERE PENETRATION OF EXISTING ROOFING MATERIALS OCCUR,
THE GENERAL CONTRACTOR SHALL COORDINATE WITH BUILDING OWNER AND
BUILDING ROOFING CONTRACTOR OF RECORD FOR INSTALLATION, PATCH,
REPAIR OR ANY AUGMENTATION TO THE ROOF, AND HAVE THE WORK
GUARANTEED UNDER THE ROOFING CONTRACTOR'S WARRANTY FOR MOISTURE
PENETRATION OR AND OTHER FUTURE BREACH OF ROOFING INTEGRITY.
62. IN THE CASE OF ROOFTOP SOLUTIONS WITH THE INSTALLATION OF ANTENNAS WITHIN
CONCEALED (SHROUDED) SUPPORT FRAMES OR TRIPODS, THE GENERAL CONTRACTOR
SHALL COORDINATE WITH THE FRP DESIGNER/FABRICATOR TO ENSURE THAT THE FINAL
FRP SHROUD IS SIMULATING (IN APPEARANCE) DESIGNATED EXISTING EXTERIOR
BUILDING FACADE MATERIALS, TEXTURES, AND COLORS. THE CONTRACTOR SHALL
FURTHERMORE ENSURE THE USE OF COUNTERSUNK FASTENERS IN ALL FRP
CONSTRUCTION. WHEN PHOTOSIMULATIONS ARE PROVIDED, THE CONTRACTOR SHALL
ENSURE THAT FINAL CONSTRUCTION REPRESENTS WHAT IS INDICATED IN
PHOTOSIMULATION. SHOP DRAWINGS SHALL BE PROVIDED TO THE GENERAL
CONTRACTOR, CONSTRUCTION COORDINATOR, AND ARCHITECT PRIOR TO FABRICATION
AND CONSTRUCTION.
63. IN THE CASE OF ROOFTOP SOLUTIONS FOR EQUIPMENT AND/OR ANTENNA FRAMES
WHERE ANCHORING TO A CONCRETE ROOF SLAB IS REQUIRED, CONTRACTORS SHALL
CONFIRM (PRIOR TO SUBMITTING BID) WITH CONSULTING CONSTRUCTION COORDINATOR
AND ARCHITECT THE PRESENCE OF POST TENSION TENDONS WITHIN THE ROOF SLAB -
RESULTING FROM AN UNDOCUMENTED DESIGN CHANGE IN THE EXISTING BUILDING
"AS -BUILT DRAWING SET" - HAVING INDICATED AN ORIGINAL DESIGN SOLUTION OF
REINFORCED CONCRETE W/ EMBEDDED STEEL REBAR. IN THE EVENT POST TENSION
SLAB SOLUTION IS PRESENT, CONTRACTOR SHALL INCLUDE PROVISIONS FOR X-RAY
PROCEDURES (INCLUDED IN BID) FOR ALL PENETRATION AREAS WHERE ANCHORING
OCCURS.
64. GENERAL & SUB CONTRACTORS SHALL USE STAINLESS STEEL METAL LOCKING TIES FOR
ALL CABLE TRAY TIE DOWNS AND ALL OTHER GENERAL TIE DOWNS (WHERE
APPLICABLE). PLASTIC ZIP TIES SHALL NOT BE PERMITTED FOR USE ON TOWER
NETWORK CARRIER PROJECTS. RECOMMENDED MANUFACTURE SHALL BE: PANDUIT CORP.
METAL LOCKING TIES MODEL NO. MLT4S-CP UNDER SERIES-304 (OR EQUAL). PANDUIT
PRODUCT DISTRIBUTED BY TRIARC.
65. NOT USED.
SYMBOLS:
x GRID REFERENCE
DETAIL REFERENCE
ELEVATION REFERENCE
-:------------..... -- SECTION REFERENCE
_ ......................__.... CENTERLINE
- PROPERTY/LEASE LINE
- - MATCH LINE
`.._.._._....__........._....______ WORK POINT
Cll:Z�1�1�DZK�P►��I�I� •
------- - TELEPHONE CONDUIT
-- ELECTRICAL CONDUIT
___.......... COAXIAL CABLE
OVERHEAD SERVICE
CONDUCTORS
GROUT OR PLASTER
-_
BRICK
'fflll0/OIf
(E) MASONRY
... ................................. y ..... .
CONCRETE
EARTH
Tt=Tr=r�n Sri 1
GRAVEL
PLYWOOD
? .,2=2
SAND
WOOD CONTINUOUS
WOOD BLOCKING
STEEL
'::�T/�!'TllrTll
)
NEW
EXISTING
-
NEW ANTENNA
EXISTING ANTENNA
GROUND ROD
GROUND BUS BAR
MECHANICAL GRND. CONN.
CADWELD
GROUND ACCESS WELL
ELECTRIC BOX
TELEPHONE BOX
LIGHT POLE
FND. MONUMENT
SPOT ELEVATION
SET POINT
REVISION
at&t
Your world. Delivered.
PACIFIC TELECOM SERVICES,
LLC
882 REGISTERED
RC T CT
j ICHARD B. HALL.
STATE bF WASHINGTO,'
EXPIRATION DATE OF THE
LICENSE: 08/20/13
�
N
cf)
LLl
O
00
J� cn
N
<
n
O
J
Q
W
r�
0
W
LL.
REVISIONS
NO.
DATE
DESCRIPTION
INITIAL
A
12/07/11
ISSUED FOR PCD REVIEW
RC
0
04/04/12
ISSUED FOR FINAL CONSTRUCTION
RLD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
SHEET TITLE
GENERAL NOTES & SYMBOLS
SHEET NUMBER
G-1
I Ht INI-UKMAI IUN UUIN IAINtU IN r11J �)t I Ur UUIVJ I KUL I IUIV UUUUIVILIV 1 3 IJ r r1\Ur'FCIL I/\m T Of I14H1 UFCL. NIV I UDC- UFC UIJULUJUFCL U I nLF\ n 11V I n/-11 VVnIUn FCLL-\I LJ I U Uh(\RILFR JCfCVII.CJ IJ 3 1 RIU I Li r'KUrlInI I LU.
LEGEND
NOTE:
PROPOSED AT&T LTE ANTENNAS/MOUNT
— —
SUBJECT BOUNDARY LINE
AND MOUNTING HARDWARE TO BE PAINTED
i
TO MATCH EXISTING SITE CONDITIONS.
—
RIGHT-OF-WAY CENTERLINE
i
RIGHT—OF—WAY LINE
I I I
— — — — — — — — — — — — —
ADJACENT BOUNDARY LINE
SECTIONAL BREAKDOWN LINE
OHP OHP
OVERHEAD POWER LINE
UV;\ ..............
BURIED POWER LINE
BURIED GAS LINE
OHT OHT
OVERHEAD TELEPHONE LINE
...... J G 7 - --
BURIED TELEPHONE LINE
W W W W
BURIED WATER LINE
SS —SS -SS—
BURIED SANITARY SEWER
SD —SD —SD-
BURIED STORM DRAIN
DITCH LINE/FLOW LINE
AT&T PROPOSES TO MODIFY EXISTING UNSTAFFED
TELECOMMUNICATIONS FACILITY BY REMOVING AN EXISTING ANTENNA
ROCK RETAINING WALL
MOUNT AND RELOCATING (3) EXISTING ANTENNAS TO A NEW ANTENNA
' MOUNT EXTENSION
. . . .
VEGETATION LINE
WITH THE ADDITION OF (3) LTE PANEL ANTENNAS
(3) TMA'S. PLUS THE ADDITION OF (6) RRH UNITS, (6) DIPLEXERS
— x — x — x — x — x —
CHAIN LINK FENCE
r F�� MOUNTED TO A NEW H-FRAME ALONG WITH (1) LTE EQUIPMENT RACK
j • MOUNTED WITHIN EXISTING AT&T EQUIPMENT ROOM LOCATED BETWEEN
- -' -
WOOD FENCE
B,
STORAGE DOORS #152 AND #149
— x — x — x — x — x —
BARBED WIRE/WIRE FENCE
i S
S7.
TRANSFORMER
FIRE HYDRANT
0 LIGHT STANDARD
N GATE VALVE
POWER VAULT
® WATER METER
\\ `• ,
® UTILITY BOX
� FIRE STAND PIPE
\
UTILITY POLE
❑ CATCH BASIN, TYPE
E POLE GUY WIRE@
CATCH BASIN, TYPE II
Ka GAS VALVE
SIGN
EXISTING AT&T VEHICULAR ACCESS AND PARKING PARCEL NUMBER:
❑O GAS METER
0BOLLARD
" ..s\. \ VIA EXISTING ASPHALT DRIVE (CALL AHEAD TO 1221039088, 1221039087
1 COORDINATE W/ STORAGE FACILITY OWNER)
TELEPHONE VAULT
MAIL BOX
A-4 \ \
2
° TELEPHONE RISER
234.21 SPOT ELEVATION
LEGAL DESCRIPTION:
A 4 EXISTING BUILDING ACCESS DOOR
_ \\ PARCEL A:
EXISTING ° THAT PORTION OF THE
'
WEST 135 FEET OF THE SOUTHEAST
QUARTER OF THE NORTHEAST QUARTER OF SECTION 12,
STORAGE TOWNSHIP 21 NORTH,
�
RANGE 3 EAST, W.M., LYING SOUTHWESTERLY OF COUNTY ROAD NO 980 J.M. ERCHINGER
(
' UNITS � ROAD, AS CONVEYED BY DEED RECORDED UNDER RECORDING
1 1.�
NO. 980310) AND NORTH OF THE FOLLOWING
". a a \, DESCRIBED LINE;
TAX LOT N 0.
1221039088
TAX LOT NO.
1221039087
TY LINE N88'55'44"W 817.30'
TAX LOT N0.
1221039025
BEGINNING AT A POINT ON THE EAST LINE OF SAID WEST 135 FEET WHICH IS 80 FEET SOUTH OF THE
SOUTHWESTERLY MARGIN OF SAID COUNTY ROAD; THENCE WEST AT RIGHT ANGLES TO SAID EAST LINE 135 FEET TO
THE EST LINE OF SAID SOUTHEAST QUARTER OF THE NORTHEAST QUARTER AND THE TERMINUS OF THE LINE HEREIN
DESCRIBED.
SITUATE IN THE COUNTY OF KING, STATE OF WASHINGTON.
PARCEL B:
AN UNDIVIDED HALF INTEREST IN THE FOLLOWING DESCRIBED PROPERTY:
THE WEST 165 FEET OF THAT PORTION OF THE SOUTHEAST QUARTER OF THE NORTHEAST QUARTER OF SECTION 12,
TOWNSHIP 21 NORTH, RANGE 3 EAST, W.M., LYING SOUTHWESTERLY OF COUNTY ROAD NO. 980 AS CONVEYED BY
DEED RECORDED UNDER RECORDING NO. 980310;
EXCEPT THAT PORTION LYING NORTH OF A LINE RUNNING WEST AT RIGHT ANGLES FROM A POINT ON THE EAST
LINE OF THE WEST 135 FEET OF SAID SUBDIVISION WHICH IS 80 FEET SOUTH OF THE SOUTHWESTERLY MARGIN OF
SAID COUNTY ROAD NO. 980, TO THE WEST LINE OF SAID SOUTHEAST QUARTER OF THE NORTHEAST QUARTER.
SITUATE IN THE COUNTY OF KING, STATE OF WASHINGTON.
PARCEL C:
AN UNDIVIDED HALF INTEREST IN THE FOLLOWING DESCRIBED PROPERTY:
THE EAST 135 FEET OF THE WEST 300 FEET OF THAT PORTION OF THE SOUTHEAST QUARTER OF THE NORTHEAST
QUARTER OF SECTION 12, TOWNSHIP 21 NORTH, RANGE 3 EAST, W.M., LYING SOUTHEASTERLY OF COUNTY ROAD NO.
980 (ERCHINGER ROAD, 21 ST PLACE SOUTHWEST AS CONVEYED BY DEED RECORDED UNDER RECORDING NO.
980310).
SITUATE IN THE COUNTY OF KING, STATE OF WASHINGTON.]
PARCEL D:
AN UNDIVIDED HALF INTEREST IN THE FOLLOWING DESCRIED PROPERTY:
THAT PORTION OF THE SOUTHEAST QUARTER OF THE NORTHEAST QUARTER OF SECTION 12, TOWNSHIP 21 NORTH,
RANGE 3 EAST W.M., LYING SOUTHWESTERLY OF COUNTY ROAD NO. 980 (21 ST AVENUE SOUTHWEST AS CONVEYED
BY DEED RECORDED UNDER RECORDING NO. 980310;)
EXCEPT THE WESTERLY 300 FEET THEREOF;
SITUATED IN THE COUNTY OF KING, SATED OF WASHINGTON
VICINITY MAP
North to be determined by
site survey (if possible).
24"x36" SCALE: 1 " = 40'-0" SITE PLAN 1
1 1 "x 17" SCALE: 1 " = 80'-0" 40 20 0 40'
. rn1� nr n�11 �nnnlrn
at&t
Your world. Delivered.
PACIFIC TELECOM SERVICES,
LLC
8828- 'REGISTERED
fARCHI
CT
i 1` 1
ICH : RID B. HA
ATE OF WASHINGT� '
L
EXPIRATION DATE OF THE
LICENSE: 08/20/13
F�
N
(n
WI
O
00
Q
N
O
J
Q
W
�
W
W
F�
REVISIONS
NO.
DATE
DESCRIPTION
INITIAL
A
12/07/11
ISSUED FOR PCD REVIEW
RC
0
04/04/12
ISSUED FOR FINAL CONSTRUCTION
RLD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
SHEET TITLE
SITE PLAN
SHEET NUMBER
A-1
I 11 IIVr VrCIVIHIIVIV i.vIVIHIIVCV IIV II-IIJ JLI _IF I.iVIVJII\VIiIIVIV VVVVIVILIVIJ IJ rl\Vrl\IL li11\I UI IVfII VI\L. /'"11V1 I YYI IIVII 1\LLfII LJ IV V 1\1\I LI\ JLI\VIVLJ IJ JII\IVILI I-f\1JF_lIDIICV.
EXISTING AT&T (8) VERTICAL CONDUITS
Al EXISTING UTILITY P'
EXISTING AT&T PAD Mc
EXISTING AT&T FIBER
EXISTING AT&T EQUIPN
EXISTING AT&T FIBER
EXISTING AT&T BBU C
EXISTING AT&T PPC C
EXISTING AT&T A/C C
EXISTING AT&T UMTS
EXISTING 3'—O" WIDE
HOLLOW METAL DOOR
EXISTING AT&T TELCO
EXISTING (2) AC UNIT'
EXISTING AT&T DISTRIE
]STING OVERHEAD POWER LINE
ISTING EDGE OF SIDEWALK
(STING AT&T PANEL ANTENNA
TOTAL, (1) PER SECTOR TO
REMOVED AND RELOCATED
ISTING 53'-6" HIGH
LITY POLE
ISTING AT&T ANTENNA MOUNT
BE REMOVED
ISTING OVERHEAD TELCO LINE
STING OVERHEAD POWER LINE
STING AT&T UNDERGROUND COAXIAL
BLE CONDUITS TO ANTENNAS
STING AT&T DOG HOUSE
STING AT&T UTILITY RACK
STING COAX CABLE
RTS (3) TOTAL
STING TREE
STING AT&T GPS ANTENNA
UNTED AT EXISTING H—FRAME
STING BUILDING
STING AT&T (2) GSM CABINETS
DOORS REMOVED
24"x36" SCALE: 3/4" = 1'-0"
1 1 "x17" SCALE: 3/8" = 1'-0" 1' 6" 0" 1'
EXISTING EQUIPMENT &ANTENNA PLAN 1
at&t
Your world. Delivered.
PACIFIC TELECOM SERVICES,
LLC
8828 �2EGISTERED
i
ARCHITECT-
ki RD B. HALL
`STATE 0f WASHINGTON
s
EXPIRATION DATE OF THE
LICENSE: 08/20/13
CN
O
00
w 0-)
U
07 <
N
J
Q
ry
O LLl
h� r� w
LL
REVISIONS
NO.
DATE
DESCRIPTION
INITIAL
A
12/07/11
ISSUED FOR PCD REVIEW
RC
0
04/04/12
ISSUED FOR FINAL CONSTRUCTION
RLD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
SHEET TITLE
EXISTING EQUIPMENT & ANTENNA PLAN
SHEET NUMBER
A-2
FHE INFORMATION CONIAINtU IN I lt5 5LI Ur UUIN� NUUIlulu UUUUIVIIENIJ I� MNUI-'NILIANT bT IN/AIUNL. HINT U-)L UN UIJI.LUJUNl UInlr< Irl/-\IN inHi wrn'-,n mr-LfiIL3 1v l,/1FWME-F\ JGFCVII,CJ 13 JIFCIUILt r MUnIC711LU.
5 PROPOSED AT&T LTE ANTENNA
F- (1 PER SECTOR, 3 TOTAL,
EXISTING AT&T (8) VERTIC
AT EXISTING UTILITY POLE
EXISTING AT&T PAD MOUN
EXISTING AT&T FIBER RACI
EXISTING AT&T EQUIPMENT
NOTE:
PROPOSED AT&T LTE ANTENNAS/MOUNT
AND MOUNTING HARDWARE TO BE PAIN]
TO MATCH EXISTING SITE CONDITIONS.
EXISTING AT&T FIBER PAN
EXISTING AT&T BBU CABIN
EXISTING AT&T PPC CABIN
EXISTING AT&T A/C CONTI
EXISTING AT&T UMTS CABI
EXISTING 3'-0" WIDE
HOLLOW METAL DOOR
PROPOSED AT&T (6) 1-5
CABLES ROUTED ON EXIST
INTERIOR CABLE TRAYS (F
EXISTING (2) AC UNITS AE
EXISTING AT&T TELCO BO/
1 PROPOSED LTE EQUIPMEN'
A-5 MOUNTED ON PROPOSED
PROPOSED AT&T (2) DC I
FIBER RUN ROUTED ON E:
INTERIOR CABLE TRAYS (F
EXISTING AT&T DISTRIBUTIC,IN I /1In-
STING OVERHEAD POWER LINE
STING EDGE OF SIDEWALK
)POSED AT&T LTE ANTENNA 6
PER SECTOR, 3 TOTAL) F_
OCATED EXISTING AT&T PANEL
'ENNA (3) TOTAL, (1) PER SECTOR
STING 53'-6" HIGH
_ITY POLE
)POSED AT&T ANTENNA MOUNT 4
-6
)POSED AT&T TMA'S 2
1NTED BELOW ANTENNA
PER SECTOR, 3 TOTAL)
STING OVERHEAD TELCO LINE
IPOSED AT&T LTE ANTENNA 6
PER SECTOR, 3 TOTAL) F_
;TING OVERHEAD POWER LINE
'POSED AT&T (6) 1-5/8" COAX CABLES
ITED WITHIN EXISTING U.G. CONDUITS
TING AT&T UNDERGROUND COAXIAL
LE CONDUITS TO ANTENNAS
TING AT&T DOG HOUSE
TING AT&T UTILITY RACK
POSED AT&T GPS ANTENNA
INTED AT EXISTING H-FRAME F-
TING TREE
TING COAX CABLr
TS (3) TOTAL
POSED (3) PORT WAVEGUIDE
NTED BELOW EXISTING
TING AT&T GPS ANTENNA
NTED AT EXISTING H-FRAME
TING BUILDING
TING AT&T (2) GSM CABINETS
DOORS REMOVED
POSED AT&T 70OMHZ RRH UNIT 3 4
;KED MOUNTED AT PROPOSED
RAME (1 PER SECTOR, 3 TOTAL) A-5 F-
POSED AT&T DIPLEXERS STACKED 3 1
NTED AT PROPOSED H-FRAME
'ER SECTOR, 6 TOTAL) A-5 F-
POSED AT&T AWS RRH UNIT r T"V 3
:KED MOUNTED AT PROPOSED
RAME (1 PER SECTOR, 3 TOTAL) A-5 F-
24%36" SCALE: 3/4" = 1'-0"
1 1 %17" SCALE: 3/8" = V-0" 1, 6" 0" -,' PROPOSED EQUIPMENT & ANTENNA PLAN 1
x
at&t
Your world. Delivered.
PACIFIC TELECOM SERVICES,
LLC
8828
EGISTERED
VA RCHIT T
ICHARD B. HALL
STATE OF WASHINGT*
s
EXPIRATION DATE OF THE
LICENSE: 08/20/13
F�
�
N
(n
LIJ
O
O
00
0)
U)
N
<
O
J
Q
W
LLJ
h�
REVISIONS
NO.
DATE
DESCRIPTION
INITIAL
A
12/07/11
ISSUED FOR PCD REVIEW
RC
0
04/04/12
ISSUED FOR FINAL CONSTRUCTION
RLD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
SHEET TITLE
PROPOSED EQUIPMENT & ANTENNA PLAN
SHEET NUMBER
A-3
I Ht IIVrUKMHI IUIN I UN ININLU ITV I r7IJ JL I Ur I.UIVJ I uk-, i IUIV VUL UIVICIV I J IJ r-mkJr'RIC IHrC I D I IV/"\I URL. /11V 1 UJL UI\ VIJI LVJVI\L U I I ILI\ 11V 11 YYI IIUI I I\LL I LJ V Vnl\I\ILI\ JLI\V IULJ IJ J I RIU I L I rf\UF-IIDI 1 LV.
NOTE:
PROPOSED AT&T LTE ANTENNAS/MOUNT
AND MOUNTING HARDWARE TO BE PAINTED
TO MATCH EXISTING SITE CONDITIONS.
��
I
JJ
JJ
24"x36" SCALE: 1/8" = 1'-0" PROPOSED SOUTHEAST ELEVATION 2 24"x36" SCALE: 1/8" = 1'-0" EXISTING SOUTHEAST ELEVATION 1
11"x17" SCALE: 1/16" = 1'-0" 8' 6' 4' 2' 0" 8' 11"x17" SCALE: 1/16" = 1'-0" 8' 6' 4' 2' 0" 8'
at&t
Your world. Delivered.'.
PACIFIC TELECOM SERVICES,
LLC
8828 R GISTERED
4 RCHITECT
C
_
(CHARD B. HALL
STATE7iPWASHINGTON
EXPIRATION DATE OF THE
LICENSE: 08/20/13
N
(n
LIJ
O
CO
0-)
Q
W
�
N
O
J
Q
cr-
W
n
0
W
LL
1�
REVISIONS
NO.
DATE
DESCRIPTION
INITIAL
A
12/07/11
ISSUED FOR PCD REVIEW
RC
0
04/04/12
ISSUED FOR FINAL CONSTRUCTION
RLD
NOT FOR CONSTRUCTION UNLESS
LABELED AS CONSTRUCTION SET
SHEET TITLE
EXISTING & PROPOSED SOUTHEAST ELEVATION
SHEET NUMBER
A-4