Loading...
23-103808-HydraulicFireFlow92523Lakehaven WATER & SEWER DISTRICT Hydraulic Model Fire Flow Estimate Request/Reporting Form Requested By: Charles Henry Date: 7/21/23 Location to be Modeled: Existing Hydrant —Near PN 0821049139 LAchaven''A Section Grid: J_7 Intersection: S 308'h St & 14th Ave S Add. Description: See attached map Pressure Zone: 578 Results By: Date: Model Run No.: John Bowma L 7/21/23 Master Water System Model 2007.net FF #442 Condition Pressure (psi) Flow (gpm) Static 45 0 Fire Flow 20 10,300 NOTES: Lakehaven's adopted level of service goals for fire flow rates are 1000 gpm within single family residential areas (including duplexes) and 2500 gpm for multi -family, commercial, industrial areas. Model results depict the theoretical performance of the water system under high demand conditions and are not guaranteed to represent actual system performance. A design professional should be consulted for site specific design purposes. The calculated fire flow capacity in the above table is based on a currently available residual system pressure of 20 psi at the location modeled. The model indicates that Lakehaven's standard maximum allowable velocity of 10 f 1s is exceeded at a fire flow rate above 5100 gpm. Fire flow capacities greater than 5100 gpm may be accommodated through water system improvements. 072123FF 442 - PN O821049139 (Form Update 1/6/17) J7/47 I 1 3J7/32 I I 1 1 I 1 I 1 I I 1 I i 1 1 I 1 J7/6 -------------------- S 308TH LN - J7/30