15-101376amide:- 1�oil FiLE 5 May 20, 2015 Jim Ferrell, Mayor Gary Hundrup 32405 12th Avenue South Federal Way, WA 98023 hundrup@comcast.net RE: File #15-101376-00-AD; REVISED RESPONSE TO INQUIRY Critical Areas Assessment, 5418 SW 3151h Street, Federal Way Dear Mr. Hundrup: The City of Federal Way's Community Development Department has received your request for approval of the on -site septic system location at the above -mentioned property. King County Health Department - needs verification from the city that the septic system is in an acceptable location before their department can approve the septic design. The proposed property is located within a Geologically Hazardous Area (GHA), landslide and erosion hazard areas, as depicted on the City's Critical Areas Map. Per Federal Way Revised Code (FWRC) 19.160.010, the Director of Community Development may permit development activities within 25 feet of the GHA if no reasonable alternative exists and only if the development activity will not lead to or create any increased slide, seismic, or erosion hazard. The city received a Geotechnical Recommendations Report, prepared by Robert M. Pride, LLC, dated May 5, 2015, that addresses the septic drain field location. Based on the report, the location of the septic drain field will not create any adverse impacts to the steep slope areas, as long as the geotechnical recommendations are followed. Therefore, the city has no objections to the location of the septic system in regards to the GHA. If you have any questions regarding this letter, please feel free to contact me at 253-835-2641 or becky.chapin@cityoffederalway.com. Sincerely, Becky Ch in L• Associate fanner c: Email: Jarone.Baker@kingcounty.gov Doc CD- 69215 33325 8th Avenue South, Federal Way, WA 98003-6325 (253) 835-7000 • www.cityoffederalway.com Robert M. Pride, LLC Consulting Engineer May 5, 2015 Mr. Gary Hundrup 32405 12th Avenue South Federal Way, WA 98023 Re: Geotechnical Recommendations Proposed Residential Project 5418 SW 315th Street Federal Way, Washington Dear Mr. Hundrup, RESUBMITTED MAY 052015 CITY OF FEDERAL WAY CDS This report summarizes the results of my recent site inspection and engineering assessment of the residential property located on the north side of 315th Street in Federal Way. It is understood that a new residence will be constructed on this property that is currently vacant land, and there will be a septic drain field located at the upper end of this driveway. The purpose of this report is to describe existing subsoil conditions in the area of the proposed septic drainfield, and to provide recommendations for infiltration design. Geologic mapping by Booth, et al along with prior geotechnical studies on this property were used as references for this report. The access driveway leading down from 315th Street is relatively flat at the upper south end where the drain field will be located. According to geologic mapping for this area along Dash Point the property is underlain by Esperance deposits consisting primarily of sands and silty sands. Subsoil conditions were documented with the excavation of test holes on this property that confirm the presence of the Esperance sand deposits. Due to the presence of steep slopes on the north side of this property it has been classified as a landslide and erosion hazard area. Geotechnical Recommendations Based on the results of our site assessment and geotechnical evaluation, the following recommendations have been prepared for the drain field design. The subsoils as exposed in open excavations as documented during my previous site inspection were classified in accordance with the King County Surface Water Design Manual — Table 4.5.2 as follows: Maximum infiltration rates for the "fine sand, loamy sand" should be 25 min/inch for the native soils below the upper compact driveway surface. In my opinion the location of this septic drain field in the upper driveway area will not create any adverse impacts to the steep slope areas located at the northerly end of this property. Robert M. Pride, LLC Page 1 13203 Holmes Point Drive NE Kirkland, WA 98034 Summary Field construction services should be considered an extension of this geotechnical investigation, and are essential to the determination of compliance with the project drawings and specifications. The findings and recommendations of this report were prepared in accordance with generally accepted principles of geotechnical engineering as practiced in the Puget Sound area at the time this report was submitted. We make no warranty, either express or implied. Please call me if you have any questions, or you wish to discuss this report in greater detail. Respectfully, Robert M. Pride, P. E. Principal Geotechnical Engineer dist: (1) Addressee rmp: HundrupResidl Robert M. Pride, LLC Page 2 13203 Holmes Point Drive NE Kirkland, WA 98034 Becky Chapin From: Becky Chapin Sent: Thursday, April 30, 2015 5:59 PM To: 'hundrup@comcast.net' Subject: Geotech Requirements Attachments: 129 Resubmittal Information.doc Hi Gary, Just following up with you regarding the geotechnical report required before the city can approve the septic system location. The property in question is located within a Geologically Hazardous Area, landslide/erosion hazard areas per the City Critical Areas Maps. The city will need to review a revised geotechnical report (addendum to the original report) which includes at least one site visit to verify site conditions. I've included code requirements for the report below. Federal Way Revised Code (FWRC) 19.160 Geologically Hazardous Areas The director of community development may permit development activities, land surface modifications or the installation and maintenance of landscaping normally associated with residential, commercial or park use on or within 25 feet of a geologically hazardous area if no reasonable alternative exists and only if the development activity or land surface modification will not lead to or create any increased slide, seismic or erosion hazard. Before approving any development activity or land surface modification under this section, the city may require the applicant to submit the following information: a. A soils report prepared by a qualified professional engineer licensed in the state which describes how the proposed development will impact each of the following on the subject property and nearby properties: i. Slope stability, landslide hazard and sloughing. ii. Seismic hazards. iii. Groundwater. iv. Seeps, springs and other surface waters. V. Existing vegetation. b. Recommended foundation design and optimal location for roadway improvements. c. Recommended methods for mitigating identified impacts and a description of how these mitigating measures may impact adjacent properties. d. Any other information the city determines is reasonably necessary to evaluate the proposal. • Verification that the septic system location will not lead to or create any increased slide, seismic or erosion hazard. Provide the attached resubmittal form and 2 copies of the geotech report to the Permit Center, reference File# 15-101376-00- AD. Please let me know if you have any questions. Thanks, Becky Chapin Associate Planner R 0ya@ Federal Way 33325 8th Avenue South Federal Way, WA 98003-6325 Phone:253-835-2641 Fax: 253-835-2609 www. cityoffedera lway: corn Becky Chapin From: Becky Chapin Sent: Wednesday, April 29, 2015 2:33 PM To: 'Jarone.Baker@kingcounty.gov' Subject: RE: 3410 SW 315th St, Federal Way - Septic System Location Approval Hi Jarone, I spoke to my Manager, Isaac Conlen, and we will not be able to revise the letter. The applicant will have to submit a revised geotech based on the current site conditions and septic deign to the city for review and then provide a final approval. Will the septic design review be put on -hold while the city conducts this review? The city has the same position on a separate request for Montevista Short Plat, Activity: SU0991266. It's under the preliminary review and we cannot give a definitive answer to the questions asked at this point, per the Public Health letter dated, April 7, 2015. The applicant had a deadline of May 14, 2015 to provide the letter to you or it would be disapproved. However, the city will need more information before we can provide concrete answers. I'm just interested on what the impact to the applicant will be if we cannot issue the letter by the May 14, 2015, date. Thanks, Becky Chapin Associate Planner sue. Federal Way 33325 8th Avenue South Federal Way, WA 98003-6325 Phone:253-835-2641 Fax: 253-835-2609 www.cityoffederalway.com From: Baker, Jarone [mailto:Jarone.Baker@kingcounty.gov] Sent: Wednesday, April 29, 2015 6:47 AM To: Becky Chapin Subject: RE: 3410 SW 315th St, Federal Way - Septic System Location Approval Hi Becky, What the Health Department needs is a yes/no or accepted/rejected answer. Words like "unlikely" or "appears" leave room for a rejection or disapproval at a later date. If the City needs more information from the applicant before a more concrete answer can be given, then we will have to delay our review until this is accomplished. Jarone Jarone Baker, RS Health and Environmental Investigator 11 Community Environmental Health 14350 Southeast Eastgate Way Bellevue, WA 98007-6458 PH: 206-477-8137 FX: 206-296-9792 i a ron e. ba ke r@ ki n gco u nty.gov Waste Water Program From: Becky Chapin fmailto:Becky.Chapin(acityoffederalwaKcom] Sent: Tuesday, April 28, 2015 2:20 PM To: Baker, Jarone Subject: RE: 3410 SW 315th St, Federal Way - Septic System Location Approval Hi Jarone, It is unlikely the city would disapprove the septic design location. Based on what was submitted to the city, we cannot evaluate all the impacts to the GHA. The applicant will have to submit a revised geotech based on the proposed house design when they apply for a building permit. However, if there are any impacts to the critical area they can easily be mitigated based on the geotech report. The septic system location won't be denied, but we don't have all the information to definitively approve the location either. Please let me know if you have any questions, Thanks, Becky Chapin Associate Planner City of Federal Way 33325 8th Avenue South Federal Way, WA 98003-6325 Phone: 253-835-2641 Becky.Chapin cityoffederalway.com From: Baker, Jarone [mailto:Jarone.Baker@king=—DVi.cI Sent: Tuesday, April 28, 2015 8:34 AM To: Becky Chapin Subject: RE: 3410 SW 315th St, Federal Way - Septic System Location Approval Hello Becky, Have you made any decisions on the CAA letter for Gary Hundrup's property at 5410 SW 315th ST — Parcel 321020-0040? Thanks, Jarone From: Baker, Jarone Sent: Tuesday, April 21, 2015 11:13 AM To: Becky Chapin (Becky.Chapin cityorfederalway.com) Subject: FW: 3410 SW 315th St, Federal Way - Septic System Location Approval Hello Becky, Can you revise this CAA letter? In the letter you state..."It appears the location 'of the proposed septic system is acceptable." But then in the next sentence you say..."The city will need to review an updated geo-tech report which addresses the current septic system design in order to determine all potential impacts to the GHA." This verbiage sounds like the approval is not concrete and can be disapproved at a later date. Am I wrong? Thanks, Jarone Jarone Baker, RS Health and Environmental Investigator 11 Community Environmental Health 14350 Southeast Eastgate Way Bellevue, WA 98007-6458 PH: 206-477-8137 FX: 206-296-9792 iarone-bakerLmkingcounty.gov Waste Water Program From: Becky Chapin [maiito:Bec .Cha in ci offederalwa .com] Sent: Thursday, April 02, 2015 10:14 AM To: Baker, Jarone Subject: 3410 SW 315th St, Federal Way - Septic System Location Approval Hi Jarone, I've been in contact with an applicant, Gary Hundrup, who is in the process of purchasing a property contingent on Public Health septic design approval. He applied for septic approval in 2014 and was denied because the property was located within a Critical Area, Geologically Hazardous Area, parcel # 321020-0040. It is my understanding that King County needs a written letter from the city, that we accept the location of the septic improvements. I've attached a letter that hopefully will satisfy that request. Before the applicant applies again for approval with Public Health, I wanted to verify that this letter is acceptable for placement of the septic system on the property. Let me know if you have any questions. Thanks, Becky Chapin Associate Planner City of Federal Way 33325 8th Avenue South Federal Way, WA 98003-6325 Phone: 253-835-2641 Becky.Ch_ a iinn_@cltyoffederalway.com � Federal Way April 2, 2015 Gary Hundrup Via Email: hundrup@comcast.net RE: File #15-101376-00-AD; RESPONSE TO INQUIRY Critical Areas Assessment, 5418 SW 3151h Street, Federal Way Dear Mr. Hundrup: CITY HALL 33325 8th Avenue South Federal Way, WA 98003-6325 (253) 835-7000 www. cityoffederalway.. com Jim Ferrell, Mayor The City of Federal Way's Community Development Department has received your request for approval of the on -site septic system location at the above -mentioned property. King County Health Department needs verification from the city that the septic system is in an acceptable location before their department can approve the septic design. The proposed property is located within a Geologically Hazardous Area (GHA), landslide and erosion hazard areas, as depicted on the City's Critical Areas Map. Per Federal Way Revised Code (FWRC) 19.160.010, the Director of Community Development may permit development activities within 25 feet of the GHA if no reasonable alternative exists and only if the development activity will not lead to or create any increased slide, seismic, or erosion hazard. The site had previously been approved for a Single Family House in 2006. At that time, Robert M. Pride, Inc. provided geotechnical analysis of the site. Based on reports provided by Robert M. Pride, Inc. and subsequent review by the city's consultants, Landau Associates, the site was approved for construction of the home and site improvements. The new proposed house is smaller in size and the location of the septic system has remained the same; therefore, it appears the location of the proposed septic system is acceptable. The city will need to review an updated geotech report which addresses the current septic system design in order to determine all potential impacts to the GHA. The new single family house will require a building permit application including submittal of a revised/addendum to the existing geotech report. At that time, a complete site assessment of all impacts to the GHA will be conducted. If you have any questions regarding this letter, please feel free to contact me at 253-835-2641 or becky.chapin@cityoffederalway.com. Sincerely, b6� Becky Chapin Associate Planner Doc- LD. 68738 Matt Herrera From: hundrup@comcast.net Sent: Thursday, March 19, 2015 7:45 PM To: Matt Herrera Subject: Septic Design for Director of Community Development Attachments: Butz Shaw Residence.pdf; KCH Approved Septic Design 2004.pdf; Septic Design by Jeff Ammon Dec 2014.pdf; Previously Approved Geo Tech Report.pdf To: Director of Community Development Re: Administrative Determination am Gary Hundrup. My wife, Susan, and I, hope to build a one story, single family, 1950 square foot, 2 car garage home, on parcel 321020-004QThe City of Federal Way Building Department had previously approved a one story, single family, 2445 square foot, 3 car garage home on this parcel. The previous approval for a home on this lot was on 8/4/2006, (Permit # 05-103078-00-SF), and was called Butz Shaw Residence (see attached file Butz Shaw Residence). The current owners of the property (Butz/Shaw) did not build a house on the property and are seeking to sell it. We made an offer in November, 2014, to buy the property contingent upon King County Health approving a Septic Design for the site. It was our belief that since a single family building permit had previously been approved for this site, that if King County Health approved a septic design, that we could work with the City of Federal Way to meet the other code requirements for building a home there. Our home placement would be on the same location as shown on the Butz Shaw Residence. Also we would have a smaller home than was originally approved. Currently we are seeking approval from the King County Health Department for an OSS. The Health Department needs written approval from the city for the location of the septic improvements on and near a mapped geologically hazardous area, in particular the placement of the drain field. The current design of the Septic System is nearly identical to the original design that was approved by the Health Department in 2004. (See attached file of KCH approved Se .... Design 2004). The current proposed design is attached as well, (see Septic Design ...on Dec 2014). 1 have also attached the previously approved GeoTech report for the site (see Previously Appr... Tech Report). King County Health needs something in writing from the City of Federal Way, that you accept the location of the septic improvements in relation to the mapped geological hazards. Obviously, it is our hope that the City will approve the location of the septic improvements, so that we can move forward with the purchase of the property and working with the City of Federal Way to design a home that meets all the required codes. Thank you for your time. Gary Hundrup Phone: 253-279-2137 W W Y gyp' 7 �!d a� 8��a aE p g e�aysRa ' 3 2 C � 3 e°� �-gp ° 3 i9 Ill Him O 39e Ig6I6 O yyE 8 q3q3 ®®®i@ 54 +4e5 aSS �4 ySeyS g6 � 0 9 a �� S 3a iae� •-... E @ � e E2 i �e11°e a€€a s Ill Im LL Z 4 rl aa� s ` Hen 9xi . -- tell jil14 .1,11,11-1131 Ilia li :fill ��� ► �e�Y ����1� � LAI i — • ..� 16 'tea ei � ea' 19€glI., E qE l2g � €E MIN 111 .. rw t i 3e8�AaaSaasa�do@.@:B�?Efi 4E� M ®■ � O U ���� K u HIM, py$8= e� a�e~�� I ill" r � o # a $ x - tail % � ■ , , ||� /,f § g F � % § � | d % lip • | | 11 lm 0 F MIRRI I'vilI I ,pnminiui I I' I� 'f iaunniniimi� I r p��llllll�ll ! ; Iltlllllllll�fl�f111 mi�r�mnmum I� � II IuIuII 1■ ■ f ; - ;Clnr�mri�rr�rrri f11"�'� i�ii� - � + � fl nf11111 WIIIIIl�1HI�� erg I i f .� I I A. i .ur'pinmur — I — I I I I �II�ll�flll�'� l \ .a �• ,� G |[ � � K• � � ■; |[ E � �, � � � J § _m____�m_All q � ,§ § fill « @ e Z w kn mew wA4av vrwa nr -.�� .v i. xs r--.� �,mU� Ada saaaut.'dug HORS LION '3lV�S MWTSr-n!�2- saiON -f/c!lnlot s 7v!aN317 N0PD- N1f1GVm '.VVrn 7V-N3� j33NLs HiSie ms 01j7s 33N309S N mb'NS / zing &OrW-So LU J o 0 0 LU a H E �0A A � o 0 o$ o Rim I o 5-N G ��a; �a �J,tii H Hg' vH t g iqM MPH Eli I W11 sz o E a a a s 9 o - -NSLR zoo f at;4 ff � WH 4 gG� R� T 10 62 I�& 2� 6a1°gym mMuM- e I q W B fty " W/,ZjFmg-, z "say SLO FQ/ • so Hvr.rvc a +w roan oroae ao✓wm.a �m.w . _ . ,..ce aw,c a vmv 9971. 1. V QF.Droi s aak. 2 m N0l9NIH9'dm ').V'm l'v'i DIA4 m-, •.: s.I@@UTVug VOHS MiG[e ms mif7l; 30N341S3z1 mt�HS / zing g ' Ig I� a i rEjC 2 sz ��$ K^• m zcr- 3 9 1� � 3Yy zJ: 1 r x 3 ,fti .y s Cyy Y p�cj 'Al �._ ® G nM•Y TE SITE COPY #@@ ata�itaaegg �.�. .y... •®�� a �� off' ngnaygc;le - ___ �w �N m LL S U O V O O�N6I zoxzm 0Z- Y 7 QNa- lilt z I m�a II a�5�a a� Aga a- I HOP � z o O N � Q ev p W L P m ❑ 0 a" 1 0. C.)r ..,� Lu •t �� (A ` 3 � a f 'a i Z K w s. 8 cop" ar, �r o I 2G � S MS s a3�5 QOOMalIM) sls&a ' ;Y ONINtl30 j03 Oq,50.59 N a S021 ,50'BSZ 3 Oq.S0.S9 N SV3W ,6o LSZ D �+ I` 11f1V IIlj Z m II}ll 1S1 0 o� 5qC i VIl1l�lll I 1 I _ � s 1 � Su }i l }%ICI � I 3 ;s o 14 N ZII j ll, I < I 9�4 N l sgo � 4 E��9 oI Io w� Public Health, Seat"ki? � � n � Record I.D. Number Site Design Application Form for Individual On -Site Sewage System (OSS) 0W_` Submit 5 copies of application with 4 copies of plans Department Use Only ATTACH AI ETAILEO ROUT@IOIRECTiONt Approximate /+ ` r MAP FOR LOCATING THE PROPERTY. Site Address: Name and address of property owner ��r-i �J1h L ✓��CD �-J Applicants Street Address 25l `� Name City -zip Code I Phone Last First Designer Street Address � ��� • �� Le City-Zip Code Phone 2_4�0 71 THIS IS NOT A PERMIT PROPERT* INFORMATION: Parcel # (APN) 2: 1 01 111�>) C)14 {0 1 Section: Subdivision Name: gy%.L. 1 Property Size J� f JZ Sq. ft. Acreage: Legal Description Attached ❑ Township: L7_ Il I Range.. La Lot: 13131-1-02] Block: I� Rural Areag] Urban Area ❑ Distance from property line to nearest sewer. - {7 13 1310 A SIGNED O & m SERVICE CONTRACT (IP) I = Individual © Group A Supply 0 Group B Supply and A RECORDER NOTICE ON TITLE Water Supply l REQUIRED AT STUB OUT RELEASE Public Water Supply Name: ID# --{- Sensitive Area: (Y?N) If yes, specify U (L,W,O) L = Landslide W = Wetlands O = Other SYSTEM INFORMATION; New System U Repair Design U Correction of OSS Failure? L�Q Yo Detailed Plans Attached (¢sets) L_ J_j Type of Building I I :tj SF = Single Family MF = Multiple Family COMM = Commercial INST = Institutional Type of System Proposed: I I . — I? I D G = Gravity GP = Gravity with pump M = Mound SF = Sand Filter PD = Pressure Distribution HT = Holding Tank CT = Composting Toilet E = Experimental O = Other Dates Soils Logged: l {'D ] YL514- Soil Logs Data Attached: (Min. 4/1ot) 1 LON Depth to Watertable or Restrictive Layer: ,za:±-Inches Maximum Slope in Drainfield/Reserve Area LPL�,?j % CALCULATIONS: Number of bedrooms: U Total Gallons/Day (450 minimum): Gal. Soil Texture Type (1A--5) L] L Application Rate: Lam Gal/sq ft/day Total Absorption Area: Sq. ft. Trench Width . �a I inches Total Drainfield Length: leg Ft. Septic Tank Size: { \ { O 18 cj.-) -Gal. Garbage Grinder Yt Pump Chamber Size (if needed) bj Gal. Trench Depth (min/max): inches !understand that failure to comply with the Qp6e of KIng County Board of Health Tdo 13 may result in the disapproval of the sewage system beln,4 roposed In this apprication. Non-compliance ms also lead to revocation of my Designee Co tenty slate legal action by the Health Department Designer's Signature' K.C. ID# Date: 1 - FOR HEALTH DEP APPROVED (date): Comments USE ONLY: NOTE: SYSTEM MUST BE INSTALLED BY A KING COUNTY CERTIFIED INSTALLER UNLESS OTHERWISE PROVIDED BY CODE Pre -construction meeting required between designer, installer, builder prior to permit issuance APPROVAL OF THIS DESIGN APPLJGATION IS BASED SOLELY ON INFORMATION PROVIDED IN THS APPLICATION AND DOES NOT CO.ISTITUTE PERMISSION TO BEGIN CONSTRUCTION OF THE PROPOSED SEWAGE DISPQSAL SYSTEM OR ANY OTHER IMPROVEMENTS ON THE SITE. THIS APPROVAL SHALL NOTBE CONSIDERED AN ASSURANCE, EITHER EXPRESSED OR IMPLIED, THAT DEVELOPMENT PERMITS FOR THE SITE WILL BE ISSUED. THIS APPLICATION EXPIRES Two YEARS FROM DATE OF APPROVAL _]ISAPP_R0MED4ate)—--- See attached Site Deficiency Sheet. Arty poison agg6eved by any dO sign ar Tmal order o� dia Health Offirar may file aivri ors app tron lOr appsal to Pie* �iRcer w thin 60 calendar tir n,,, a...:..:,.., rr:wn 1,3 it r R n u rK­for 7 a io _ Ca,w. a n4a8 r nmmwl % rQ i'1 i r Q7 nmr YNN 7M JUL 19 2007 ---EASTGATE ,nr7PnNiU F,NTAL READ. k�vxnw.++uasat 02 OL 91 O4 S f 30 T3TdJ5 spear no oro�-aaal� # l'"973�d'SSO+ISI'i�d a'rr� : xxre s{r-ft./• sLo2 "' --"-'----- EZOB6 NM'nXM'NS?03d"ES HJ:SiS MS ULY] :hl7LLtl,}C17 St fi HZISg 9VSOdSIO MSS SS ajTS-NO tj--aQo id ��.�.� �-.v,� IrTnreTsn 7Y.Tta LR1G 1I t'.F�':flIH H7Li:LLS :I.t+LT�7� T11'M a� f l - A , , MM, + l (AxoiS aAU)1 N 37 V3aLSail �I wooxaas E Y Qasoao-aa , I h Il pema�vaara AVM aAIM '' I73A 7V3NI7 i9Ell aaai ED W-111aZtlM W- woos-UMM WinDTIV1TaaA-MaH %001 _"" SS99MI (oMj)'tVxasVa Z)Aa ,.T ------ (me 44+ s9 NKYJ, dwna xmrTVf) owl 0 ? Mvi Dung NO'I'IVE) 0001 'NOL NO aarmmo018 aa37V16'IVIa3- M073a CT IVILL a3d33Q OI I3110 (w I-TIM SINVI SaM.LOW .UIIVd 3T90S •3I.VNIIXOIad" ally SII 'sI.007I ON'wV0'I ashaa..W SI00II'Aryo'T7VH3,SP.zz 011TODW(UMMaHVII3911. S1009 IN VO•[ \V•L-.LV f? .[[-..ci •AaAIMS 1V0; Is Vol ACNVS!L4f0SR.•Sir fis 'aa Iugadl 'NOLLV37VISDa 01 110INd a3xv UNVS'aMA3Vy0rINV1•AVH0 w+IS-I,L'C 'NOTIOUSNI 1VNIs 01 1101Ida3 aNVS'axK AWVo3 NM08a,.cZb CIS 'a1311haVaQ5NDIAH3SdW SNOLLV'I00'ro0 (M S31AN MOLLY] aNVS'a3N[ APWOI NV172LVW ,-+SS--ii 'sNOLITa Q.NVS'MH AWVO'I NM0811.ELb TIS MIS11 as TIVM MSS3A s3m wwsTiO =v Axwo-t Yr1.LVit<].Z'ac •s•rrv1 j aNr8'[f3ltiAWVO'I NMUSE 0110 T'Is jl4ll sso l'aos ar mwvaa annasax WN3AU IasIOM L51MON S'nvasaNr- TO M i00CIJ! Wi "1wl Inc... v zoTT4D io9=611 [u eNei+ao E e0 Z G600 9Z6TZE # 130ad'sgusI7dd a K SIOI EZ08o h"M xtltA'fYi18U33 'IS H,I,SiE M$ Oi65;xOT,Ltl�O'I 9YRd -e:s IS Tsum S &U-0 ; =oa T IVlbla LvW 3MLOIM1SHH Sll03 VVsaa ni-siaNO lVN1EJRa0 —7 lgAa-1 ca.LvAVOK3 WOLLCM NON ; 1 wrWImYJIL o - IDCM P>�.�en.fl MYIWINIW 2L l'Jfl7.V81LL(L !L d01 Gl91Y11M10 A .� >i3/.O 1106 Wf1W WIW 2L ...... Ta11LOtl94 —7, 13h31 O3TM1lV SN1 ia3lVl .L � QD^S q— v >tLgyd 2131iIA OI13N1NAS —� �_ L�y� �? Yli V NOIL43S lML3Q N7Pa8L11 IroP@IL'ai ala .t^ 107: DI LII1 amu 3ea.t sum Tree as .: sage tSlm) aea a Itai wl T—M w:usrUSM Sea .[ AAOUE[ NMOHS SV 910WHA'IVA L KAVHTIIMualsn173ta iYe�WT.Z� I N� 'II1iL84 USISM Sege loaf dO =GR WM f — Y17R 3L7tl7.'ICJ .e• I SNOTIVO OLZ q xN�z �Isa�s ��I SN07aVO5Y[[ :xSNOTIVO OS6 3y= ar asla>erm.y um� rr Im Yam! u tblk•"Qikil MTVA VVIO oAd a '1070 Ok .T-: 9[7 Y.•SIE'ALv1— I...r IH:LI n6rtw.1 �` !1'W'stsl l.�i'aY pm�mL. \ 5� 61VNL'IOJ 16roLIN T.`$ raL �mn� SVTaola N7-11 ) dVL1[ ALILM VA Invoice #: 4688 GARY HUNDRUP 32405 12TH AVE SW FEDERAL WAY,WA 98023-4914 Amman Septic Designs Inc. 14525 246TH DR SE MONROE, WA 98272 TAX #: 3210200040 PLEASE DETACH AT PERFORATION AND RETURN TOP PORTION WITH CHECK(S) 12/02/2014 Invoice #: 4688 Amman Septic Designs Inc_List Of Charges/Credits DESCRIPTION AMMAN SEPTIC DESIGNS INC PUBLIC HEALTH SEATTLE/KING COUNTY CHARGES CREDITS BALANCE $ 2,000.00 $ 2,000.00 $ 0.00 $ 864.00 $ 864.00 $ 0.00 $ 0.00 PUBLIC HEALTH SEATTLE/KING COUNTY $ 0.00 PAID IN FULL, THANK YOU. Public Health, Seattle and King County " * COVER LETTER ** Record I.D. Number Site Design Application Form for Individual On -Site Sewage System (OSS) ON Submit 5 copies of a2plication with 4 copies of plans) Department Use Only Approximate ATTACH A DETAILED ROUTEIDIRECTION MAP Site Address: 1 5410 SW 315TH ST FOR LOCATING THE PROPERTY. Name and address of property owner I GARY HUNDRUP 32405 12TH AVE SW, FEDERAL WAY,WA,98023-4914 Applicant Street Address 132405 12TH AVE SW, FEDERAL WAY Name HUNDRUP GARY City -Zip Code 952 3-49141 Phone 1 253, 79.2137 Last First 98038 Street Address 114525 246TH DR SE Designer 1 AMMAN IFFF j City -Zip Code IMONROE 98272 jPhonel 360-794-7809 THIS IS NOT A PERMIT PROPERTY INFORMATION: Parcel # (APN) 1 31 2 1 1 0 2 0 0 0 4 1 0 Section: 1 11 0 Subdivision Name: I HEALY PALISADES ADD Property Size: I 1 5 1 9 j 5 1 3 1 3 Sq. ft. Acreage: 1.37 Distance from property line to nearest sewer: L/A FT Water Supply u (IP) = Individual XQ Group A Supply >1000 0 Public Water Supply Name: I TACOMA WATER Sensitive Area: U (Y?N) If yes, specify U (L,W,O) L = Landslide Legal Description Attached ❑x Township:1 21 1 Range: 1 01 3 Lot: I 13,4,5 I I Block:j 1 11J Rural Area ❑ Urban Area B Group A Supply < 1000 Group'B Supply I ID#I I I I I II W = Wetlands O = Other & EROSION SYSTEM INFORMATION: New System u Repair Design U Correction of OSS Failure? UY?N Detailed Plans Attached (4 sets) U Y?N Type of Building IS IF SF = Single Family MF = Multiple Family COMM = Commercial INST = Institutional Type of System Proposed: IJ — P I D G = Gravity GP = Gravity with Pump M = Mound SF = Sand Filter PD = Pressure Distribution HT = Holding Tank CT = Composting Toilet E = Experimental O = Other Dates Soils Logged 1 112 1 110 1 1111 Soil Logs Attached: (Min. 4/Iot) U Y?N Depth to Watertable or Restrictive Layer: 1 61 5 Inches Maximum Slope in Drainfield/Reserve Area 1 01 % CALCULATIONS: Number of Bedrooms: 13 Total Gallons/Day (450 minimum): 1 41 51 0 Gal. Soil Texture Type (1A-5) LJ Application Rate: 1 0.81 Gal/sq ft/day Total Absorption Area: I I 51 61 41 Sq. ft. Trench Width I 36 inches Total Drainfield Length: 1 11 81 8 Ft. Septic Tank Size: 11 51 01 0 Gal. Garbage Grinder U Y?N Pump Chamber Size (if needed) 1 11 51 01 01 Gal. Trench Depth (min/max): 2 1 j/ 2 4 inches I understand that failure to comply with the Code of K County Board of may also lead to revocation of my Designers c 'f )cu 55 ,..y a Designer's Signature: FOR HEALTH DEPA APPROVED (date): Comments 13 may result In the disapproval of the sewage system being proposed in this application. Non-compliance )riate legal action by the Health Department. WA5100100 K.C. ID# 1 I I 1 ��_� Date: 12 15/14 ENT USE ONLY: NOTE;:. SYSTFH MUST BE INSTALLED BY A KING COUNTY CERTIFIED INSTALLER UNLESS OTyt tWJS9 APPROVED BY CODE BY: y ❑ Pre -construction meeting required between designer, installer, builder prior ta-# rrW04suance APPROVAL OF THIS DESIGN APPLICATION IS BASED SOLELY ON INFORMATION PROVIDED IN THIS APPLICATION AND 1361:SrNOIT, ONScLi't'tlYE PERMISSION TO BEGIN CONSTRUCTION OF THE PROPOSED SEWAGE DISPOSAL SYSTEM OR ANY OTHER IMPROVEMENT$ON,"WE S,60H1S APPROVAL SHALL NOT BE CONSIDERED AN ASSURANCE, EITHER EXPRESSED OR IMPLIED, THAT DEVELOPMENT PERMITS FOR THE SITg WILT 9E ISSUED. THIS APPLICATION EXPIRES TWO YEARS FROM DATE OF APPROVAL. DISAPPROVED (date): BY: See attached Site Deficiency Sheet. Any person aggrieved by any decision or final order of the Health Officer may file a written applicallon for appeal to Health Officer within 60 calendar days of the date of the above decision. (Title 13, K.C.B.O.H. Chapter 13.12 - Sewage Review Committee). CS 13.15.97 Rev. 7/21/00 RECEIVED 01 JEM n ye Va T Eds❑❑x�� ZD Mist MM 1 r 1 r 1 r 1111 r r 1 r /lll r 1 r 1 r 1 1 1 r r 3 g d UP �yqyqq EEC! ids' 1rsn yrs Him I a DRIVEWAY yes usr rws scrsa�z ��� wsraiwriQ+ ��" DEPW W u ui W S- N �n 4 aODs S U 13 pS F N N CL Lr) C LI no E �lQ In c 3 VA 0 "1 I 319,18 w tin ! I f I I rw I a��pp wwz I �.r4r^ � I ! � rig 3a 4 f OS If r f r + I y v It ff { f { i f + a? ' l 4 1 ItfV f It i 4 ` 512,43+ r r ++ { 1 V f r r U c W � N cu N^ U1 L M N Q a+ S¢ U I3 +� v N w In O N 0 in o E E Q liriiliifli , I I I I# I 1 I l l y a� •'p I II I l l l l l i l 1 +1 1+ 1+}! 1 1 1 5 5 1 L t l 5 1 L i L U ] � i CO lu of i Lo S- s n O %J r J ° C - I+ i i + r 24' ➢IAM. ACCESS RISERS WITH SECURED LIDS AND GAS TIGHT SEALS (TYP) FINAL GRADE CAffiII UNION/QUICK DISCONNECT TO p➢RAINFIELD LL=Q!G f OAT NOIk114lTi�STEN INFLUENT YALK FROM HOUSE KING COUNTY APPROVED SCREENED OUTLET FILTO 1500 GALLON WATER TIGHT TWO COMPARTMENT SEPTIC TANK MONITORING/CLEANOUT PORT W{PCCTIBII PORT CAP BACKFILL HATER AL PVC HOSE OR L"4 SWEEP ELBOW UNDISTURBED SOILS d� r. 1500 GALLON WATER T.l 4( PUMP TANK f, r� SM3AOCD CAP OR PLUG 12' SANDY LOAM COVER SOIL LAST ORIFICE PRESSURE LATERAL 6' MIN OF WASHED DRAINROCK BELOW PIPE 4' PVC Vllll tMAIN KXF9 EKTUO I'D 901TC9 OF GWVEL TV MONITOR PCHMwl INFILTRATIVE SURFACE 2PEL�F11 IC7 ! . bTfLUAI' P VERTICAL CROSS SECTION,-`- �\ SLOPE _1<0�1 NOT TO SCALE N S0L IKM'n ' VIAL SEP—THIN IXABE SPLITTER MANIFOLD TO ➢RAINFIELD LATERALS WITH LOCKING LID CK VALVES .Y REQUIRED IF TRENCHES ARE ,RADIENT OF MANIFOLD VALVES TRANSPORT PIPE Amman Septic D651gn5, Inc. NOT TO SCALE 14525 246th Dr, SE r.RESSURE DISTRIBUTION Monroe, WA 98272 4360 7194-7809 DPFkf (421) W-6195 C411 WVV.GOTPERIC.CIDY [36W 794-5+09 Fex Anno-an Septic Desigll-as I1AC 14525 2461!1 Drive SE Monroe, WA 98272 Jarone Baker, R.S. Public Health Seattle/King County Site Address: 5410 SW 315t" ST Parcel #: 321020-0040 Owner: Gary Hundrup Activity #: ON 0080774 Jarone, Attached please find our design for the above referenced property which is almost identical to the approved design with the above referenced activity number. The only change is that I have shown a very small cut that was created when the previous owner constructed the driveway. I have dug out the original perk holes. Please let me know if you have any questions and/or need anything else. Thanks for your help! Jeff Amman www.GOTPERK.COM JEFF a GOTPERK.COM (360) 794-7809 District Waiver Request Date December 12, 2014 Attach this request to the application in question Property Address 5410 SW 315TH ST, FEDERAL WAY Parcel Number 321020-0040 Activity Number Name of Person Making Request Jeff Amman Phone Number ( 360 ) 794-7809 Office or (425) 501-5195 Cel Identify relationship to subject property (designer, owner, developer, buildier, etc.) Designer The applicant/designer is requesting a waiver of conditions described below: Reduce the property line setback to five feet. ® Justification: PROPERTY LINE IS CLEARLY DEFINED AND UPGRADIENT. ® Proposed mitigation measures (attach separage page if necessary) Reason this will not be a public health concern: SYSTEM DESIGNED PER TITLE 13. Findings (attach all supporting documentation): Comments from Field Sanatarian: Decision: Conditions of Approval: Person reviewing request for District Waiver Title Signature District Waivers/Eastgate 3/30/00 Date _ _ ii2iO3tf1r£iR 32iU�28Ls 310a3�� 33Uf� 1 szli�a0�58j 309U1 984tl90TFiC7' 32i02NA% s 113 Sipes 31010 :Masi Sin_ 59 102iO3NYDF2 321112001621000209 31022 Sri2 r''lr ll a; ar91i7C�1 iU2{1U1 S 31060 32r02UU1U7 515 6126 3210200214' 321t120U53U 5f341 .51046 3iU42 6i¢¢2 351,f2U0'65 3210260190 R i� 32f02bUi•ff) 51id _'s2iU2U�4HU / 3iii2 53URf � 1;�aW y 5324 r 31050 32fU2UU�1 321026011-5 _+i123 rr � 5129 3210200� 0 5r47 ' ' x �,� 3�iG2U0USd 31fUH 'r F. 5047 O� 321 MOOCH J210206060 S ��. 5132 32iU2UL1fU5 'S � p �� 5129 __�'' _a21U2000d2 u s�+ i12103;USi 6215 32iC1200ii1 sP 5iCi5 55U0 +ai0aG0!110 5323 921020U5GG Sill r 102163903f- j T 32162110064 f i2iU200_JS 3210200390 S3U8 f �ria2ooG�� .3113; S211 313ie �xlrrra9nTs 3210261)OU 3210206710 3210200396 54id 53•i0 532U 3810200UP0 ' rzF 3216260006 32i (j20009U 63UU 6312 r 5221 3_r2 f iu2UU3o0 64221 3210200060 32102006197 rf n)0200382 31331 31-336, 43asfi Paint State Park 3i1U20002U 3210200058 5231 18d61003-f0 s V10200371 5102 31,106 18987OL1059 YDO} 31yTFf 5'� 5 2,13 .31404 5039 Federal Way 3210MV412 5i0U 7G11C1390U2 y 5323 �.,^ ;1d9olGUU-TU 3'lSUd SILM 5 U 111fI$G 5154 54a4 32102w2a13f501 5 iid S3U7 �Q 31524 5108 3142•1 :12302L03ii 32iU2UU193 " 52tJd 315iJ 1H4U7001130 � 5325 5}Ua .3152Y 3iOi -:32102OU32E 1890YOO620 5<fi 3210200350 3i52rJ 521fi 54Gs iG21C13sU15 :31-f44 fS : 32102G0361 iq 542i 5411 _+2102U0332, 53211 11531 52U4 1H9d7UC1U1C1 � 32iU2GU320 32i0200355 Stol 5ii2 5326 101103401E .Y 74v {1a5U 32102OU'V2 534•f _ 1021039U3S' 535fi 321U2UO3•f2 1021039045 C - •3iSa0 5400 5235 510i i 5 f U[i �yL Sd1d Sri."g 311 � 3i57ri iOM39027 31?Ad 2216260317 5353 3171U iU2iU39U46 31136 3i6U5 - 31115'. '11722 102IL12911101 31615 rn -31616 31723 1021039018 6415 -21801 1{]27U39041 10210 9017 F 31 dU5 3rarrr iU21039028 5219 C,t 5202 1.02103904U J1809 11006 31813 JC) 20M King County 318135, 0 397ti The.lnrormatlon Included on oils reap has teen opmpyed by IC1na County sfsN from a vade!y of soumcr. and Is subfacl to change without notice, Kilo Cvunlyy makes nu represcnlelldtls nr warianlies, e><prass a lmp!ted, as to socuracy, camel nets, Wnellnos9, oa lights !o 01e usn W wch Inrorniellofl. Thia 6ocurhenl is na1 intenllaa fpr use a9 a.suf+ruy SN,Ddu,CL'1i111gg Count&q shair not 6a hahe for nrty gallml- apedal, Indirect, indd"Wl, 01 consaquenllal L-9 domagas 117tluding, tu! not 11inllvd to, lost reranuun or lost p[ofl!s rostrift, irwn Ihn use or mfstlsv of the info mat3Dh conlefned on this map- Any sa!n ofKing County Ihfs map orinformapon an Nis map la prunrand a oupl ty tvsilto" pornt!sv on or King County. Data: f llY4r2111a Source,, long County IMAP - Peoparry lnformetten {htip jwwm.rnelroKo.goWGlWMAPI CERTIFICATE ®PNAT'ER AVAILABILITY TAC9MA WATER PROJECT ADDRESS: 6418 SW 316TH ST, FEDERAL WAY, WA 98023-2036 APPLICATION NUMBED: 2000010750 SUBDIVISIONIPROJECT NAME: PROPOSED SFD PARCEL: PA3210200040 FIRE FLOW INFORMATION: FOR ALL RESIDENTIAL PROJECTS. WATER MAINS: * Location of nearest main capable of supplying at least 500 GPM: SW 316TH 3T If not In street at front of property, distance from property to above main Is: N/A feet. HYDRANTS: * Distance from centerline of property frontage to nearest hydrant measured along routes of fire apparatus travel is:120 ± feet. Page 2 THE AMOUNT OF AVAILABLE FIRE FLOW INDICATED ABOVE IS IN ADDITION TO REQUIREMENTS FOR NORMAL DOMESTIC MAXIMUM USE. A WATER SYSTEM VICINITY MAP WHICH SHOWS THE WATER MAINS AND HYDRANTS SERVING THIS PROJECT IS REQUIRED FOR ALL PROJECTS. A contract has not been signed with the applicant for water service. The above Information is an accurate account of the existing or necessary water system facilities. FOR PRELIMINARY SHORT PLAT OR SUBDIVISIONS: We -understand that this document, in absence of a legal contract, constitutes a certification of willingness and ability to provide water service subject to the conditions noted. WATER PURVEYOR:,. CITY OF TACOMA, T.P.U., WATER DIVISION. DATE; 11118/2014 SIGNATURE: 6 TITLE: FOR FINAL S14ORT PLAT, SUBDIVISION, BUILDING PERMIT, SEPTIC DESIGN: WATER MAIN ONLY APPROVED FOR FINAL ACCEPTANCE, NOT PRIVATE CONTRACT ACCEPTANCE We the undersigned water purveyor, certify that we will assume full operational and mali}tenance responsibility for the above water system which has been designed, approved, and installed In accordance with Washington Administrative Code 246.290, RCW 90.44 (Water Rights Permits), Pierce County Code 170.60.165 and 19D.130, and an approved water system comprehensive plan. WATER PURVEYOR: CITY O-� TACOMA, T.P.U., WATER DIVISION. DATE: 1111812014 SIGNATURE: Cr�!��� TITLE: IZ�Ij T This certificate is valid for a period of THREE YEARS from the date of iss tie solely for the specific prope rtylp roject indicated. Changes in the number of lots andlor use will require re -application by the applicant, evaluation by the department and issuance of a new certificate. (Board of Health Resvlut'ion No. 2001-3282 - Land Use Regulations) THE ABILITY TO PROVIDE SERVICE IS DEPENDENT ON PIERCE COUNTY'S WILLINGNESS TO PERMIT THE INSTALLATION WH1CH MAY ENCLUDE CUTTING THE DRIVING SURFACE OF THE STREET. 0004 CD 150 n, °I . 1. 90# 9034 / " 4 ; cn 1 `3I l l I ; sW w 53rd Ave -1Da 10A— 9 IA E—F—G—H a3 s 9A-10A 0082 0500 ' MALY 0064 � q �-�LISADESl ADDS . , sa.nw+a ruw: a.v.a+i•n. �•uaxs+ 3 THRU 5 0040 i Y.=.rw:a3 1oA-11A— � � s 12-13 0089 w ] j+ too Lo 3 I 4-5 5 THRU 8 , I • j 0036 0045 5 THRU 8 I I 0050 8-9A y 11 I 1 0058 a 10A 1 1A-12 & 13 1-2 : I 0077 0090 r oo�o I I f LO s `3 2 & 13 0091 Ac N jOv 'a r� A4rj LO t ] 2 k o 02,56 5 0285`, r ' 2 & 6 tea` 7 0287 0310 10 5076 ftD Kf _, a i 1' 3 =O n y J F'�Y r,• - i 8-9 �"'L V r in 0295 p Syr O—] 0.359 01 ` All oft �A5 S � �U` ; 0352 .? 1V ~ 8-9 0358 ON 7 O ,a } O } 0�-15 r l x ', 6-7 1. 7 8-9 j ... N y, % C1341 elf. 8 0357 Re: Critical Areas - Jeff @ Amman Septic Designs Inc Page 2 of 2 To: Jeff @ Amman Septic Designs Inc Subject: Fwd: Critical Areas Jeff, This is what the city of Federal Way sent me. I believe I can get a more detailed written one if you desire, but that will take them at least 2 weeks. Left me know if is will work for you. Thanks, Gary From: "Matt Herrera" <Matt. He rre ra@cityoffede ra [way. com> To: "hundrup@comcast.net' <hundrup@comcast.net> Sent: Wednesday, November 19, 2014 4:50:40 PM Subject: Critical Areas Gary, Parcel 321020-0040 is shown to contain geologically hazardous areas according to the city's critical areas mapping. I've attached a map generated by the our Geographic Information Systems database which identifies landslide hazards and erosion hazards on the property. It should be noted that although we have the area mapped to contain critical areas, it does not represent an absolute delineation of the on -the -ground conditions, but instead it is used to identify potential hazards which then must be confirmed by a qualified professional at the expense of the project applicant. In this case the qualified professional would be a licensed geotechnical engineer. I hope this helps and let me know if you have any questions. —Matt Matt Herrera, AICP - Senior Planner Community Development 33325 8th Avenue South Federal Way, WA 98003 253.835.2638 (p) / 253.835.2609 (f) Matt.Herrera@cityoffederalway.com cityoffederalway.com https:Houtlook.office365.com/owa/ 12/12/2014 ifill tF, I [I I Se tic System Operating Ca]2acity Versus Design Capacily Tax Parcel #: 321020-0040 The attached septic design was designed for a maximum daily load of 450 gallons per day. Exceeding this amount may result in pre -mature system failure. Daily operation of this system at approximately 90 gallons per bedroom (270 gallons per day) should help extend its effective lifespan with proper maintenance. The attached septic design was designed to process and dispose of "residential grade" sewage which falls within the following ranges: BOD5 130-230 mg/l CBOD5 108-191 mg/1 Total Suspended Solids 49-150 mg/l Oil & Grease 10-25 mg/l Exceeding the above values or consistent use at or near the maximums may result in pre- mature system failure. Please note that Amman Septic Designs Inc and Jeff Amman have only designed the above referenced septic system and approved the installation of said design. Due to factors beyond our control such as abuse, neglect, failure to maintain an Operation and Maintenance contract with a licensed maintainer as required, effluent strengths, water use, additive use (not recommended), etc.... Amman Septic Designs Inc and Jeff Amman do not warrant and/or guarantee the lifespan of this septic system. Proper sewage habits and maintenance are crucial to the longevity of this septic system. Hydraulic Calculation Summary Sheet: Page 12 of Submission Provide basic calculations for evalutaion of any pressure system The following is an example for a PD system Pressure Distribution System Summary Sheet For: 3 4�2e-fI d � `�� Transport Pipe Length Manifold Pipe Length Manifold Type: Central End Lateral Diameter 2j� ft Diameter w Inch ft Diameter 2— Inch Header x Class 5 Class Longest Lateral Length Ft Class Longest Allowed Lateral Length Ft Orifice Size >161 Inch Spacing Ft Total # of Orifices System Flow hate (Orifice Discharge Rate X# of Orifices) 3,5"X P1d Gal/Min(GPM E Friction Losses Transport Pipe Ft Manifold ? Ft Laterals Ft Fittings/Valves —�� Ft Elevation Ft Total Dynamic Head �� Ft Required Pump Capacity 21 Gal/Min(GPM) Total Dynamic Head (TDH) Pump Size Pump Capacity Pump Tank Model !tea Pump Tank (Gal/Per/Inch) Dose Volume �y� Gallons Doses per Day Low Pressure System Requirements (Timed Dosing) Schedule 40 pipe shall be used throughout this system. Orifice diameter is 3/16 inch oriented in the 6:00 position. Lateral diameter is 1.25 inch with upturns at each end with a 6 inch monitoring port accessible from the surface. Transport diameter is 2 inch. 2 inch splitter manifold. Residual head to be set at 24" on all laterals. All orifice spacing to be FOUR foot on center. Dose volume shall be� gallons dosed TWO times/day Rhombus J Timer mechanism to be UL listed and housed in a min. of a NEMA 4 box. Timer to be set at TWELVE hours off, minutes on. Water tight pump chamber with risers to the surface to be a minimum of _f gallons total capacity. pump or equiv. required. —e-7 Total dynamic head = ` feet. Total Drainfield system output = gallons/min. King County Department of Assessments: eReal Property Page 1 of 3 • New Senrch Property Ta. Oil flap This iroperly Otvnary of Terms Area Repmi Pi int Properly Dclail Reference Lin PARCEL DATA n C un Parcel 321020-0040 Name BUTZ RONALD D Site Address Residential Area 052-014 (SW Appraisal District) Property Name Jurisdiction FEDERAL WAY Levy Code 1.1190 Property Type L R Plat Block / Building Number Plat Lot! Unit Number f 1 _ 3 THRU 5 Quarter -Section -Township- Range SE-10-21.3 09aI Description HEALY PALISADES ADD LOT 3 TGW LOTS 4 & 5 LESS S 270 FT OF SO LOTS 4 & 5 LESS N 150 AS PER FEDERAL WAY LOT LINE ELIMINATION #05-105579-00-SU REC #20060920001682 PLat Block: 1 Plat Lot: 3 THRU 5 Highest & Best Use As If I SINGLE FAMILY Vacant 1I_ ~k Highest & Best Use As (unknown) improved Present Use _ T f Vacant(Single-family) 0 Base Land Value SgFt Base Land Value 183.000 90 . Base Land Value Impacted Base Land Valued Date 5/14I2013� , 12014 Base Land Tax Year _Value Land SgFt Acres 1.3r - -• •-• Vlews� - Rainier Territorial AVERAGE Olympics AVERAGE Cascades Seattle Skyline Puget Sound IGOOD Lake Washington Lake Sammamish - I _�__ Fake/River/Creek I Other View Historic Site Current Use i(none) NO No NO NbrBldg Sites ,Adjacent to Golf Fairway Adjacent to GoNobell. Other Deslgna0on Deed Restrictions NO Development Rights Purchased NO _ Easements ^� NO Native Growth Protection Easement NO DNR Lease NO LAND DATA Percentage Unusable Unbuildable _Y�0 INO Restrictive Size Shape -T NO .Zoning _ �! ttRS15.0 _ _ 'Water WATER DISTRICT SewerlSeptic _ • - • (none) Road Access PUBLIC Parking ADEQUATE Street Surface I PAVED Waterfrmni Waterfront Location Waterfront Footage �0 Lot Depth Factor IO Waterfront Bank TidelShore _I Waterfront Restricted Access 'Waterfront Access Rights W I NO Poor quality Proximity Influence Nuisances YES Topography � -_ Traffic Noise Ahport Noise Power Lines �� f NO Other Nuisances ~I NO _ • Problems Water Problems NO nCNO ITran POthoblems YES �^ Frivlrorlmantal Environmental ES Y-_-- Environmental Information Delineation Percentage Type Source study Affected SteepSlopeHazard JURISDICT10NI N 0 BUILDING TAIL ROLL HISTORY Account VOTvvli Tax Omit Lavy AppraF9ad Rppra[sed Appraised NaW r.L..B1eYear earar Code Lend Tmps Tetal Detlnraand imps Tot:f[ Vnluv Vnlee {Sj Va1ne fS) value (5} fS) --�' Hoasam Links vl or Washlnoton Ste o no avenue (Exlen link) as J.n ten tF t32ard a f Ted Appeals (Fxdem link) yard a AvnoalslE ua pistricls Re.van iMao eco dens O Scannedlmave � an mu me d� ocumeM, can nal Ima e plats Notice mailing dat 09/11/2014 http://info.kingeounty. gov/Assessor/eRealProperty/Detail. aspx?ParcelNbr=3210200040 11/24/2014 consult Robert M. Pride, Inc. Engineer September 20, 2005 Mr. Ron Butz 1911 SW Campus Drive #353 Federal Way, WA 98023 Re: Final Geotechnical Review Proposed Residence 5410 SW 315ffi Street Federal Way, Washington RMP Project No. 04-369-ox Dear Mr. Butz, RFl;pl\/F,D, CIS t3ULDING D PT AY This geotechnical review letter covers the final residential plans prepared by Franchini Design Group for your proposed residence at 543o SW 315th Street in Federal Way. Our geotechnical report dated December A, 2004 provided recommendations for foundation and retaining wall design along with a stability analysis of the descending slope below the building pad. This review is based on the most current drawing Sheet A-10 that shows the building pad is in cut at a grade of about 212 feet. Finish floor of the residence is about 223.5 feet, and the northeast and northwest corners of the structure have been moved back from the top of the slope at least ten feet. A retaining wall system will be constructed as part of the garage to support the rear cut slope on the south side of the property. On the basis of our plan review of the current design drawing for the proposed residence, the original pipe pile recommendations for foundation support within ten feet of the slope will not be required. Continuous bearing wall footings are shown to be at least ten feet from the face of the descending slope, and they are in accordance with our recommendations. Construction of this residence will probably take place during the wet weather period, and that will require additional measures to secure this site. Fortunately the onsite soils consist of silty sands that will absorb most rainfall on the pad and slope areas. Normal silt fencing will need to be installed around the outer perimeter of the building pad area, and the access driveway entry should be protected with quarry spalls. Any soil stockpiles should be covered with plastic sheeting until they are either exported from the property, or used as backfill around the foundation walls. As long as conditions as described in our geotechnical report are followed and approved, areas disturbed by construction will be stabilized, the risk of damage to the proposed 13203 Holmes Point Drive NE Kirkland, WA 98034 Phone: 425-814-3970 Fax: 425-814-W72 September 20, 2005 Mr. Ron Butz Page 2 development or to adjacent properties from soil instability will be minimal, and the proposed site excavation will not increase the potential for soil movement. Field inspections will be followed with memos that describe the work accomplished during site excavation, foundation installations, footing subdrains, and wall backfills. Please call me if there are any questions. R pectfully, Hof wAAsk�� C� Robert M. Pride, P. E. x Principal Geotechnical Enginee dist: (2) addressee c��crsr� rmp: ButzResid4 �t7NAL` 13203 Holmes Point Drive NE Kirkland, WA 98034 Phone: •42"14-3970 Fax: 425-814-5672 4 Consulting Robert M. Pride, Inc. Engineer July 21, 2005 Mr. Ron Butz 1911 SW Campus Drive #353 Federal Way, WA 98023 Re: Geotechnical Review Proposed Residence 5410 SW 315th Street Federal Way, Washington RMP Project No. 04-369-01 Dear Mr. Butz, As required by the city of Federal Way we have reviewed the plans dated June 15, 2005 prepared by Franchini Design Group for your proposed residence at 54zo 5W 3-15th Street in Federal Way. It is understood that the footprint of the new residence will be approximately as shown in our December 2004 report except that the main floor elevation will be at 212 feet. Three to five feet of excavation will be required to establish the building pad. Retaining walls are shown to be constructed for support of the slope on the south side of the building pad. These walls are expected to range in height from 4 to 8 feet. Foundations for the northerly side of the house wilt consist of driven pipe piles, while the southerly side will be supported on continuous bearing wall footings. Based on my plan review our geotechnical recommendations are included in the design drawings for this residence. We will provide field inspections services for the foundation and retaining wall installations as recommended in our report. Please call me if there are any questions. Res ecthflly, 4 °F WAB�j� p x Robert M. Pride, P. E. Principal Geotechnical Engi16271 e 1 dirt: W addressee rmp: ButzResid3 - Exptaes � 13203 Holmes Point Drive NE Kirkland, WA 98034 Phone: 42U14-3970 Fax: 425-814-M72 Consulting Robert M. Pride, Inc. Engineer December 18, 2004 Mr. Ron Butz 1911 SW Campus Drive #353 Federal Way, WA 98O23 Re: Proposal for Geotechnical Services Proposed Residence 5410 SW 315th Street Federal Way, Washington RMP Project No. 04-369-ox Dear Mr, Butz, This report presents the results of our site investigation and geotechnical evaluation in support of your proposed residence at 5410 SW 315th Street in the Dash Point area of Federal Way. It is understood that the residence will be a one story wood framed structure with a slab -on -grade floor. Access will by way of a narrow driveway off of 315th Street south of the building pad area. The purpose of this investigation was to determine the geologic soil profile under the property, and to provide engineering recommendations for the design and construction of the residence. A Site Plan and topographic survey prepared by JSH CAD & Design was used as a reference for our study. Site -Investigation A total of five exploratory test pits were dug on the slope and level pad areas to develop a soil profile under the proposed residence. Maximum depth of these test pits was four feet, and their locations are shown on the attached Drawing No.1. In addition an engineering geologist surveyed the entire slope extending from the building pad down to the beach. The presence of relatively uniform glacial deposits down the entire slope did not require the drilling of borings since the exposures were consistent with previous geologic mapping for this area of Federal Way. Each of the exploratory pits dug on the slope showed a thick layer of topsoil and colluvial deposits within the upper 3 to 4 feet. Below the silty sand colluvial soils was the Fsperance formation. consisting of fine to medium silty sands and sands. These glacial deposits were medium dense to dense and extended the full height of the north facing slope on the property. At the base of the slope was the Lawton formation consisting of very stiff to hard silts and sandy silts. No groundwater seepage was observed within the Esperance sand formation. 13203 Holmes Point Dive NE Kirkland, WA 98034 Phone: 425-814-3970 Fax: 425-814-W72 December 18, 2004 Mr. Ron Butz Page 2 Geologic reconnaissance mapping of the slope showed no evidence of deep seated landsliding, erosion gullies or areas of shallow slope failures. The slope was covered with native shrubs and mature trees without evidence of excessive creep of the surficial soils on the slope. Conclusions and Recommendations Ge er On the basis of our geologic and geotechnical site evaluations, the property is considered stable and will provide satisfactory support for the proposed residence. Stability analyses were performed for the building site and they show that the building pad is grossly stable from deep seated sliding with a safety factor in excess of 1.5. A portion of the residence will extend out over the slope, and that will require installing pipe piles to extend the foundation support through the colluvial soils on the slope. Temporary SIvoe Exation Construction of the retaining wall for the attached garage will require temporary slopes to be cut into the steep slope at the south side of the building pad, This slope cut may be on the order of to to 14 feet in height, it is recommended that they be cut at a gradient no steeper than IH:IV. If the height of the temporary cut exceeds ten feet, it is recommended that eco-blocks be placed at the toe of the slope against a slightly inclined backeut. These blocks may remain in place as part of the backfill, or be removed and replace with compacted bacM. All temporary cut slopes should be covered with plastic sheeting and tied down with sandbags during the winter months. Foundatign Regginmendaiaons For continuous bearing wall footings that will be supported on the medium dense to dense native sands, we recommend that they be designed for an allowable bearing value of x5oo psf. This value may be increased by 1/3 to account for temporary seismic or wind loading. Resistance to temporary lateral forces can be provided be a passive value Of 250 pcf. Settlement of these footings should not exceed one inch, and a majority of this settlement will occur during construction of the residence. For that portion of the structure that extends over the slope on the north side of the pad, we recommend the use of four inch diameter Schedule 8o pile piles that will have a design capacity of io tons per pile. These piles must be driven to refusal with an 850# pneumatic hammer mounted on a backhoe. Refusal is based on less than one inch of penetration after three cycles of driving the pipe pile. All piles should be inspected during driving to verify their load carrying capacity. 13203 Holmes Point Drive NE Kirkland, WA 98034 Phone: 42"14-3970 Fa)c 42"145872 December 18, 2004 Mr. Ron Butt Page 3 The tops of the pipe piles should be connected with concrete grade beams along the north wall of the residence. Where the structure extends southerly away from the top of slope, these grade beams should be designed for bearing on the native soils at a minimum distance of io feet from the top of slope at the northwest and northeast corners of the residence. I UP-3 ■ ,.M Concrete retaining walls will be constructed around the southerly side of the garage and driveway where it extends into the slope. Design of these retaining walls should be based on active earth pressures of 35 pcf and 55 pc£ for level and sloping backfill conditions, respectively. Resistance to lateral loads on these walls can be provided by a passive pressure value of 250 pcf. Installation of a perforated subdrain pipe embedded in gravel and wrapped with a geofilter cloth should be accomplished at the base of all retaining walls and perimeter foundation walls. These subdrains should be connected to a tightline for discharge to an approved location. Erosion ConUW Construction on this site will require installation of silt fencing around the lower three sides of the building pad area, and placement of quarry spalls from 315th Street into the driveway access road. Storm water runoff is not expected to be significant from the slope because of the presence of the upper loose sandy colluvial soils which will absorb most of any expected rainfall. The lower level portion of the site consists primarily of well -compacted silty fill that will produce most of the site' runoff. The silt fencing should be anchored at the base with onsite native sand soils to act as a filter for storm water runoff at the north end of the property. Summary We recommend that we be retained to review those portions of the plans and specifications that pertain to foundations and earthwork to determine that they are consistent with the recommendations of this report. Construction monitoring and consultation services should also be provided to verify that subsurface conditions are similar to those encountered during our field exploration. Should conditions be revealed during construction that differ from the anticipated subsurface profile, we will evaluate those conditions and provide alternative recommendations where appropriate. Field construction services should be considered an extension of this initial geotechnical investigation, and are essential to the determination of compliance with the project 13203 Holmes Point Drive NE Kirkland, WA 98034 Phone: 425-814-3970 Fax: 425-814-5672 December 18, 2004 Mr. Ron Butz Page 4 drawings and specifications. Such activities would include site and slope excavations; excavations for foundations and retaining walls; pipe pile installations; subdrain installations; and fill placement and compaction. The conclusions and recommendations presented in this report are based on 1) our interpretation and evaluation of soil conditions on the site, 2) confirmation of the actual subsurface conditions encountered during construction, and 3) the assumption that sufficient observation and testing will be provided during appropriate phases of the work. Our findings and recommendations of this report were prepared in accordance with generally accepted principles of geotechnical engineering as practiced in the Puget Sound area at the time this report was submitted. We make no warranty, either express or implied. Please call me if there are any questions regarding the findings and recommendations of this report. Respectfully, 4VII, f Robert M. Pride, P. E. Principal Geotechnieal dist: (1) addressee enel: Drawing No. i Figure No. 1 rmp: ButzResi& i 13203 Holmes Point drive NE Kirkland, WA 98034 Phone: 42"14-3970 Fax: 425-814.5672 su is, N 3 9 T 5 i.0 3: 0 z LP f rorA —10155 .73 P Ref- "Site Plan" for Butz Residence prepared by JSH CAD & Design dated September 2000 SITE PLAN Proposed Butz Residence Project No. 04-369-bi 5410 SW 315th Street Federal Way, Washington DrawingNo. 1 Robert M. PtMe, Inc. PA"QIdN"a Rnoino" Rt)bek-i: M. Pride, Inc. COecr 5 t ]C At .... . ;w . •;.... .,�__{._,._.�_ Jill �-- ��---- r�-s -.-�..... _ ..�...... _ _..�._ .� .. ,. _ ,. � .. • = F -� 3 I ! .. �. .. .... .. • � .. .. r � ._ _...-� i jam_. . - �... ♦ }•.. .. ;. ... � � - �• ` ._ . ! — f — s. � .. ,.fir • � —4; .� • ; k FROSION AND SEDYMISM CCMROL NOTFS SWE W&WN TO CIII BASIN WM THEVEGETATION IN THIS HILLSME OF DII SM HAVE 1. Approval *fthis Erosion/Sedimentation Control (ESC) plan does not oonstitutcau approval of AREA SKU NOT BE WMaNTOCONTROLRIX rm— Or M1114ge design (i.e. size and location 0fx0Ags, pl*, r".trictors. channels, ' retenrionfacilfdes. utilities, etc.). 2, The implementation of these ESC piano and the construction, maintenance, replacement, and p7diog' 4 ESCfacifides is the responsibility 9f the appli Vcontra�lo until w6n r all. 3. The daries of the clearing limits shown on this plan shall be clearly flagged in the field prior PLAN VIEW dralo�_ to construction. During the construction period. no disturbance -beyond the flagged clewing limits NTS shall be permitted. The flagging shall be maintained by the applicant/cqnhactor for the duration of eua•ayy or ;�*L construction.................... ......... 4. The EISC facilities shown on this plan must be waltructed in c0ftJOncliork with all clearing and grading activities, and in such a matizier as to Insure that sediment laden waterdoes not enter the "case System or violate applicable waterstandards.•ar�... . ............ '5.The ESC facilities shown on th4plan are the minknum requiremerI anticipated site conditions. During the construction Period these ESC facilities shallbe upgraded (i.e. additional su'on ditches and silt fences, etc.) as needed for unexpected storm events. 6.T'rn 9'o" Cf. irof'shall be inspected daffy by the RAPlicant0contractor and maintained as necessary to erguro their continued functioning. PLAN VIEW tomeDram 7. Any area shipped of vegetation, including roadway embankments;where further is NTS 0�e, seeding. mulching, netting, erosion blankets, etc.) =a C 47 tiou o� f4xluo anticipated or a period of 15 days, shall he immediately stabilized with the methods mr1low IS I splash block 8. Any am needing ESC measures, I . not requiring immediate 21teuti0n; shall b* addressed within 15 J days. 9, The F-SC faciNties on inactive sites shall be inspected and maintained a minimum of oftm a month ­..­ .......... or within the 48 hours following a Storm event. '10. At no time shall more than one foot of sediment be allowed to accumulate within a catch basin. trt All catch basins and conveyance lines shall be clearled prior to paving. The cleaning tion of -laden water into the downstreamme mesa cos -A-W ud shall not flush sediment opera I I. Stabilized c&=(XiOn entrances and wash pads shall be installed at the beginning of construction and MaInUcaeO tor the duration of the projecL Additional measures may r be requ ited uired to insure That A OR Paved areas am kept elm for the duration of the project 11 During the time period of November I through Mareh'3 1. all project disturbed areas greater than prier fzWe vvertiow 5,000 squ"e' fee that are left mxworkod for more then 12 bolus, shall be covered by one of the following cover measures: rI sod, or plastic coverin& 13. Any ppm=911 retchion"dele"ricu facilitY used as 4 temPOTary settling basin shall be modified 3le with the necessary erosion control measures and shall provide adequate storage capacity. if the 4'60 or W nedaa washed rad PentuarOnt facilitY is to function ultimately as an infiltration ordispersion system, the facility sh r F_ AR 'r not be used as 3 tWIP012EY settling basic. No underground detention ranks or vaults shall be used as a temporary selling basin, 14- Where seeding for temporary erosion control is required, fast germinating grasses shall be, applied r at an appropriate (aft lie., annual or perennial rye applied at approximately 80 pounds per acre), 15. Where straw mulch for temporary erosion control is required, it shall be applied at a minimum thickness of two inches. 16. Management practices providing significant tree protection shall be provided per Section 22-1568 N A (c) (6) (a-g) of FWCC. INTS DMRBED AS PART OF T10 PROW17. ANY RITURE VMTA71ON OR TREE REMOVAL 15 SUEW TO CITY REGULATIONS FOR ME AM VEGETATION REMOVAL ON STEEp SLOPM alter strip grass — 5' Min 1. NOTE, artle length dirrecs;ohs W min Dee or oc �L F and site timitations, as typicajoysierc 21 min ..kSC-CTION NTS at DATUM ELEV 2O. 00 6' R0r­Q62'1` SETBACK FOUND IRON PIPE IU EDE U.Z—U 1\4 REr%R TO TJR 40'X 2'7RftflE5 .�a ALL MROS)II! 5TOCWLM SWU BE FIRMOTED WIN a?jQ5KM CONTROL W_AE`JJRZ5 TO MEP RA76RX ONTAMM ON 517ID. N N '414.1 Lot: Prior to final building inspecti Frinal EroMon and SedimentaffirAn ContrO inspec"'II LS required 283-BO' Contact erosion control staff for on site evaluation With COntraCtOr/bUilder to discuss site -specific erosion control issues. _Ng_�e t�lon . Call the inspection request fine to schedule 253-835-3050, For question regarding this inspection call Mike Brewer 253-83.5-2,759 Provide wIiioie Rouse ventilatio rt MIN:20'SMArX 3yste111 302,3 0� 1-0 11 Y A40 mi4FAVED To fIPRIMAL T�o�Alir car" EUTRA`N6r;: TO 5r 1145TAUSD 0 WIn ��� ��1I~�►.�.11-1�.�-����I`:..�►I►."�,��"1��.�� ✓J//f /�/J���/// �/��/�//////�,�%���� �.i �/i!%Y:/I/.` ////�����j//11 ro� NO 1100/000111 �?��j %'���s'/`//��J, ! PAP WKVjtjI A_-__ ar ­1 i f ILA ............... SITE SECTION A —A SCALE 1 "=20' under floOr inspection strati be Irequireird prior to of sheathing AIPPrOVed nutl1b. be 'I r. . (UP acts; ravfded f,, �,ft e,'v b . jr? vi,'4iblO 8 su"I POSition a,- ' plainly and legible if'Oni tf,e, Sfree0, Mad fiontitIg tfrc ' I Uoperty. LR!q 3� , _ :Ll CITY OF FEDERAL WAY DEPT OF Cif, 0E-:vELap0AEW 3 O MNIU A � PERMIT#: 05-10307*8-00-5F SS-ptS AA)RG55: ,1A18 5W315f` St reet reet:'f proVCpPROJECT: Kew SFPwt, 130TZ/5HAW.. . DATE- i)28/(A* RATE "W"MrED APPRDYED BY separatek Feft'M W.11y per""`!t "quired FOUND IRON auk PIPE, HELD •N� 4 NED POSITION CITI( ?'14JBI �g Q U-.I-...L Q I NG AREAS • OUILVIN6 FOOTPRINT - 545D W. Fr • ,-zN DRIVEWAY AREA = 6020.0 $0. n • NEW CONCRETE PATIO o 225.0 511 M • TOTAL IM'ERIA016 AREA = nO.0 50. Fr. 0 TOTAL LOT AREA -- -1410,sb so. FT. 0 LOT COVERAGE i24 36 FOUND HUB AND TACK WITH 2' X 2' OFFSET PK NAILS (4--- 8-05) 0 0 0 Q 0 0 Lo m 0 LO LO N 0 (_n LLJ LIJ 0 0 Ln Lf) 0 00 f) 00 L00 `�__ (11--18-04) Aoirlonp 0 20 40 60 1' 20' MONUMENT FOUND AS NOTED REBAR & CAP LS 19635 SET 0 SURVEY PIN FOUND AS NOTED --------- CHAINLINK OR MRE*. FENCI..; B3 x BRICK COLUMN ieaCRE TE I& W RESUBMITTED MAY 0 5 2015 CITY OF FEDERAL WAY CDS . . .. ........ e 5 H I N 6 T 0 N a V -0 )p, -r rr M :03t --i M SET TITLE, —4 CD Z C °8 51TE PLAN co --i E T N U M 6 -n 1 0