12-104098 4
Meihan cal
City of Federal Way ` 1 ?�
Community&Econ.Dev.Services Permit #: 12-104098-00-ME
33325 8th Ave S
Federal Way,WA 98003
Ph:(253)835-2607 Fax (253)835-2609 Inspection Request Line: (253)835-3050
Project Name: BANK OF AMERICA
Project Address: 32011 PACIFIC HWY S Parcel Number: 1500500130
Project Description: Demolish existing 20 ton split system and relief fan.Install(2)VAV boxes,(2)7.5 ton split
systems,(1)5-ton split system,(6)exhaust fans,(1)relief fan on roof,(3)electric wall
heaters and new relief in lobby.
Owner Applicant Contractor
BANK OF AMERICA BANK OF AMERICA MACDONALD MILLER FAC SOL INC
100 N TYRON ST 100 N TYRON ST (GENERAL)
CHARLO1 lb NC 28255 CHARLOI lb NC 28255 MACDOFS980RU(12/31/12)
7717 DETROIT AVE SW
SEATTLE WA 98106
Additional Permit Information
Mechanical Valuation 84900.00 Is this an Online or O.T.C.application? No
Mechanical Fixtures
Air Handling Units. 6 Fans 7
PERMIT EXPIRES Sunday, March 17, 2013
Permit Issued on Tuesday, September 18, 2012
I hereby certify that the above information is correct and that the construction on the above described property and
the occupancy and the use will be in accordance with the laws, rules and regulations of the State of Washington
and the City of Federal Way.
Owner or agent: r Date: / Vi/L
° DATE INSPECTOR' AREA AND TYPE C INSPECTION h
2 (13 k VwtaPM( I �o u7clex _ Ou- 4 0 Cove., C6, ) e4.1. 4 'fid
;�
6disCwA4-1-
THIS CARD IS TO MAIN ON-SITE an F
CITY OF' • Construction
In ection Record
Federal Way INSPECTION REQUE TS: (253)835-3050
PERMIT#: 12-104098-00-ME Address: 32011 PACIFIC HWY S
Project: BANK OF AMERICA FEDERAL WAY, WA 98003-6001
Scheduled inspections may be failed if this card is not on-site. DO NOT LOSE THIS CARD. Inspections are listed as close to sequential order as
possible(read left to right,top to bottom). Please schedule inspections as appropriate. Work must not be covered until it is approved. Check with your
inspector if you are unsure about any of the inspections or the inspection sequence. On-going inspections are logged on the back of this card.
❑ Mechanical Rough-in(4165) El Gas Piping(4125) 0 Final-Mechanical(4065)
Approved A proved to release test Approved
By 0_,A -`. Date a_.a)_/Lf , DateZ-1Z— t ,By L' ldn, DateQ _2,L) 1.
El Rough Electrical Final Electrical Right of Way
Approved Approved Approved
By Date By Date By Date
i •
FAC
MacILITDonald-
SOLUTIOMNSiller
Y kg BR
NEBB CERTIFIED
TEST, ADJUST & BALANCE REPORT
FOR
BANK OF AMERICA
WA5-113
7225160
32011 PACIFIC HWY S
FEDERAL WAY, WA 98003
ENGINEER: K ANWAY
HVAC CONTRACTOR: MACDONALD MILLER
THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM
MEASUREMENTS AND FINAL ADJUSTMENTSTHAT HAVE BEEN OBTAINED IN
ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB PROCEDURAL STANDARDS
FOR TESTING, ADJUSTING, AND BALANCING OF ENVIRONMENTAL SYSTEMS. ANY
VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE
NOTED IN THE TEST-ADJUST- BALANCE REPORT PROJECT SUMMARY.
SUBMITTED &CERTIFIED BY:
MR BRIAN WHEELER, NEBB SUPERVISOR REPORT DATE: 02-20-14
Certification Expiration Date: March 31, 2014
FIELD FOREMAN: STEVE BAKER
FIELD TECHNICIAN: ERIC GILBERT
MACDONALD-MILLER FACILITY SOLUTIONS MECHANICAL SERVICES #2661
7717 DETROIT AVENUE SW
SEATTLE,WASHINGTON 98106
PHONE: (206)763-9400 FAX: (206)767-6773
.
•
MacDonald-Miller `
g an
FACILITY SOLUTIONS
ABBREVIATIONS
C11)
AC AIR CONDITIONING UNIT HP HORSEPOWER
BDD BACK DRAFT DAMPER HP HEATPUMP AIR CONDITIONING UNIT
BHP BRAKE HORSEPOWER HWR HEATING WATER RETURN
B.S. BIRD SCREEN HWS HEATING WATER SUPPLY
CEG CEILING EXHUAST GRILLE INACINACCESSIBLE
CRG CEILING RETURN GRILLE LAT (DB) LEAVING AIR TEMP.(DRY BULB)
CFM CUBIC FEET PER MINUTE LAT(WB) LEAVING AIR TEMP.(WET BULB
CHWR CHILLED WATER RETURN LD LINEAR DIFFUS
CHWS CHILLED WATER SUPPLY LWT LEAVING WATERTEMPERATURE
CSD CEILING SUPPLY DIFFUSER MAX MAXIMUM
CWR CONDENSER WATER RETURN MIN MINIMUM
CWS CONDENSER WATER SUPPLY 0 WIDE OPEN DAMPER/AIR PATH
DD DIRECT DRIVE OBD OPPOSED BLADE DAMPER
DP DIFFERENTIAL PRESSURE ODOUTSIDE DIAMETER
DIFF DIFFUSER OSAOUTSIDE AIR
DMPR DAMPER RA RETURN AIR
DNA DATA NOT AVAILABLE REQ'DREQUIRED
DNL DATA NOT LISTED RH RELATIVE HUMIDITY
DNT DATA NOT TAKEN RTU ROOFTOP UNIT
DWDI DOUBLE WIDTH DOUBLE INLET SA SUPPLY AIR
EAT(DB) ENTERING AIR TEMP.(DRY BULB) SPSTATIC PRESSURE
EAT (WB) ENTERING AIR TEMP.(WET BULB) SWG SIDE WALL GRILLE
EC EGGCRATE RETURN SWR SIDE WALL REGISTER
EF EXHAUST FAN SWSI SINGLE WIDTH SINGLE INLET
EG EXHAUST GRILLE T OUTLET NEAREST THERMOSTAT
ESP EXTERNAL STATIC PRESSURE TSP TOTAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE T.P. THERMALLY PROTEC l ED
FPM FEET PER MINUTE T-STAT THERMOSTAT OR SENSOR
FH FUME HooD TYP TYPICAL
GPM GALLONS PER MINUTE 0 VOLTAGE PHASE/DUCT DIAMETER
HF HEPA FILTER V.D. VOLUME DAMPER
. • • ,
CZ> MFACIacDoLITYSOLUnaldTIONS-Miller JL_ -iL-
-
MacDonald Miller Facility Solutions
Calibration Certification 2014
Calibration Calibration Calibration
Instrument Tool# Model# Serial# By Date Due
Rotating
Measurement 1003510 461995 Q342831 Davis Inotek 6/10/2013 6/10/2014
Temperature
Measurement Air 1009459 ADM-860C M13055 Shortridge 1/30/2014 1/30/2015
Temperature NSN
Measurement H2O 80PK-5A Mac 63690 7458111 Davis Inotek 6/11/2013 6/11/2014
Electrical
Measurement 1003918 Fluke 902 94710185 Davis Inotek 6/10/2013 6/10/2014
Temperature
Measurement Air 1009459 ADM-860C M13055 Shortridge 1/30/2014 1/30/2015
Air Velocity
Measurement 1009459 ADM-860C M13055 Shortridge 1/30/2014 1/30/2015
Temperature
Measurement Air 1009459 ADM-880C M13055 Shortridge 1/30/2014 1/30/2015
Humidity 9555P0841032
Measurement 1005875 TSI 9555-P P08410045 TSI 8/27/2013 8/27/2014
Hydronic Pressure
Measurement 1001731 HDM250 W05167 Shortridge 10/8/2013 10/8/2014
Hydronic Differential
Pressure Measurement 1001731 HDM250 W05167 Shortridge 10/8/2013 10/8/2014
•
Bank Of America
CZ) MacDonald-Miller Test and Balance Summary
FACILITY SOLUTIONS WA5-113
Bank Of America
Air Balancing Summary
WAS-113
Job # 7225160
General Notes:
A. The balancing procedures,techniques, and instrumentation were those set forth by the
National Environmental Balancing Bureau.
B. Additional requirements described in the Mechanical Specifications. Testing,Adjusting, and
Balancing were incorporated into the balancing procedures. Any deviations were noted and
approved by the consulting engineer.
C. Prior to TAB work being perform on a system,the following was completed&/or verified by
TAB personnel:
1. Start-up
2. Vibrations springs working and shipping restraints removed
3. DDC controls operational and controlling(verify proper sequence of operations)
4. Ductwork complete
II. Air Systems
A. Fan Unit AHU-01,AHU-02,and AHU-03
1. Observed conditions met in section I. General Notes have been met for this system
2. Supply Fan
a) Read unit for total flow by filter traverse
b) Adjusted fan speed for proper flow
c) Verify functionality of installed electric heat coil
d) Set minimum outside air
e) Recorded operational data
f) Units were balanced as an open area with no outlet design numbers
•
Bank Of America
CZ) MacDonald-Miller Test and Balance Summary
FACILITY SOLUTIONS WA5-113
B. Terminal Unit
1. Observed conditions met in section I. General Notes have been met for this system
2. Variable Air Volume Unit
a) Calibrated VAV boxes by
(1) Reading outlets with flow hood.
b) Proportioned outlets
c) Calibrated minimum set point
d) Verified functionality of installed heater
C. Exhaust Fans
1. Observed conditions met in section I. General Notes have been met for this system
2. Exhaust Fans
a) Read fan inlet for total flow
D. Relief Fan
1. Observed conditions met in section I. General Notes have been met for this system
2. Relief Fan
a) Read discharge of fan for total flow
(1) Fan set to maintain building static pressure
4Z2). NlacDo�d-Miller w
FACILITY SOLUTIONS
Air Handling Unit
PROJECT: Bank Of America WA5-113 DATE:2/20/2014
LOCATION:Federal Way,WA CONTACT:Eric Gilbert
PROJECT#:7225160
SYSTEM/UNIT:AHU-01 Tested By: Eric Gilbert
AREA: Test Date: February 20, 2014
Unit Data Motor Data
Unit ManufacturerYork AHU-01/Suppiv Fan
Unit Model Number NC09000OC6AAA2A Motor Manufacturer A.O.Smith
Unit Serial Number Ni G2031290 Motor Frame 56HZ
Unit Discharge Upblast Motor HP 2 HP
AHU-01 1 SF Filter Bank Motor RPM 1725 RPM
Filter Type Pleated Motor Rated Volts 208 Volts
Filter Quantity-Size 1 4 Motor Phase 3
Filter Dimensions-Size 1 16x25x2 Motor Hertz 60 Hz
Motor FL Amps 6.6 Amps
Test Data Motor Service Factor 1.15
Total Design Airflow 3000 CFM Sheave Data
Total Actual Airflow 2935 CFM
Outside Air Design 500 CFM AHU-01/SupDly Fan
Outside Air Actual 510 CFMMotor Sheave MFG Browning
AHU-01/Supply Fan M tor Sheave Model VP
Motor Volts T1-T2210 Volts Motor Sheave Dia m. 4 in.
Motor Volts T2-T3 211 Volts Motor Sheave Bore 5/8 in.
Motor Volts T1-T3 209 Volts FanSheave MFG Browning
Motor Amps TI 6.60 Amps Fan Sheave Model AK55
Motor Amps T2 6.70 Amps Fan Sheave Diam. 5 1/2 in.
Motor Amps T3 6.60 Amps Fan Sheave Bore 1 in.
Number of Belts 1
Belt Size A44
Sheave Center Line 16 1/4 in.
* Notes
MacDonald-Miller
NEBB Certified TAB Contractor
422Z) MacDoilid-Miller IP
FACILITY SOLUTIONS
Air Handling Unit
PROJECT:Bank Of America WA5-113 DATE:2/20/2014
LOCATION: Federal Way,WA CONTACT: Eric Gilbert
PROJECT#:7225160
SYSTEM/UNIT:AHU-02 Tested By: Eric Gilbert
AREA: Test Date: February 20, 2014
Unit Data Motor Data
Unit Manufacturer York AHU-02/Supply Fan
Unit Model Number NC090C00C6AAA2A Motor Manufacturer A.O.Smith
Unit Serial Number N1 G2031287 Motor Frame 56HZ
Unit Discharge Upblast Motor HP 2 HP
AHU-02/SF Filter Bank Motor RPM 1725 RPM
Filter Type Pleated Motor Rated Volts 208 Volts
Filter Quantity-Size 1 4 Motor Phase 3
Filter Dimensions-Size 1 16x25x2 Motor Hertz 60 Hz
Motor FL Amps 6.6 Amps
Test Data Motor Service Factor 1.15
Total Design Airflow 3000 CFM
Sheave Data
Total Actual Airflow 3045 CFM
Outside Air Design 500 CFM AHU-02/Supply Fan
Outside Air Actual 485 CFM Motor Sheave MFG Browning
AHU-02/Supply Fan Motor Sheave Model VP
Motor Volts T1-T2 210 Volts Motor Sheave Diam. 4 in.
Motor Volts T2-T3 211 Volts Motor Sheave Bore 5/8 in.
Motor Volts T1-T3 209 Volts Fan Sheave MFG Browning
Motor Amps T1 6.60 Amps Fan Sheave Model AK55
Motor Amps T2 6.70 Amps Fan Sheave Diam. 5 1/2 in.
Motor Amps T3 6.60 Amps Fan Sheave Bore 1 in.
Number of Belts 1
Belt Size A44
Sheave Center Line 16 1/4 in.
*Notes
MacDonald-Miller
NEBB Certified TAB Contractor
Miller
, . , 41)
Man
CIII> FACILITYcDoSOLUTIONS-d
Air Handling Unit
PROJECT: Bank Of America WA5-113 DATE:2/20/2014
LOCATION: Federal Way,WA CONTACT: Eric Gilbert
PROJECT#:7225160
SYSTEM/UNIT:AHU-02/VAV-02 Tested By: Eric Gilbert
AREA: Test Date: February 20, 2014
Unit Data Term Box Test Data
Manufacturer Price Max Design CFM 450 CFM
Model Number SDV50808 Max Actual CFM 460 CFM
VAV Address 02 Max Setpoint 450
Box Inlet Size 8" Min Design CFM 150 CFM
Min Actual CFM 145 CFM
Min Setpoint 150
Electric Heat
Rated KW 5 KW
Measured DT 25 Deg F
Design CFM 150 CFM
Measured CFM 145 CFM
Stages SCR
AHU-02/VAV-02 Supply Outlet Summary
System t Unit Area Served T/0 Type of Outlet Size Design Prelim % Pre Final %Final
Reading Type Reading Reading Reading
Outlet-01 Merchant 0 Flowhood CD 10" 250 220 88 255 102
Teller
Outlet-02 Merchant T Flowhood CD 8" 200 225 113 205 103
Teller
Totals: 460 445 99% 460 102%
* Notes
MacDonald-Miller
NEBB Certified TAB Contractor
MacDon
d-Niiiler 410
411a> FACILITY SOLUTIONS
Air Handling Unit
PROJECT: Bank Of America WA5-113 DATE:2/20/2014
LOCATION: Federal Way,WA CONTACT: Eric Gilbert
PROJECT#:7225160
SYSTEM/UNIT:AHU-03 Tested By: Eric Gilbert
AREA: Test Date: February 20, 2014
Unit Data Motor Data
Unit Manufacturer York AHU-03/Supply Fan
Unit Model Number AVG60D3XH21CA Motor Frame 56
Unit Serial Number W1E1020582 Motor HP 3/4 HP
Unit Discharge Upblast Motor RPM 1725 RPM
AHU-03/SF Filter Bank Motor Rated Volts 208 Volts
Filter Type Pleated Motor Phase 1
Filter Quantity-Size 1 1 Motor Hertz 60 Hz
Filter Dimensions-Size 1 20x22x1 Motor FL Amps 7.0 Amps
Test Data
Total Design Airflow 1765 CFM
Total Actual Airflow 1830 CFM
Outside Air Design 150 CFM
Outside Air Actual 165 CFM
AHU-03 I Supply Fan
Motor Volts T1-T2 209 Volts
Motor Amps T1 4.30 Amps
*Notes
MacDonald-Miller
NEBB Certified TAB Contractor
CZ) McDai d-Miller i ' '
FACILUTYa SOLUTIONS
Air Handling Unit
PROJECT: Bank Of America WA5-113 DATE:2/20/2014
LOCATION:Federal Way,WA CONTACT:Eric Gilbert
PROJECT#:7225160
SYSTEM/UNIT:AHU-03/VAV-01 Tested By: Eric Gilbert
AREA: Test Date: February 20, 2014
Unit Data Term Box Test Data
Manufacturer Price Max Design CFM 500 CFM
Model Number SDV50808 Max Actual CFM 505 CFM
VAV Address 01 Max Setpoint 500
Box Inlet Size 8" Min Design CFM 200 CFM
Min Actual CFM 190 CFM
Min Setpoint 200
Electric Heat
Rated KW 5 KW
Measured DT 23 Deg F
Design CFM 200 CFM
Measured CFM 190 CFM
Stages SCR
AHU-03/VAV-01 Supply Outlet Summary
System FUnit Area Served T/O Type of Outlet Size Design Prelim %Pre Final %Final
Reading Type Reading Reading Reading
Outlet-01 Managers T Flowhood CD 10" 250 210 84 245 98
Office
Outlet-02 Managers 0 Flowhood CD 10" 250 225 90 260 104
Office
Totals: 600 436 87% 606: 101%
* Notes
MacDonald-Miller
NEBB Certified TAB Contractor
' I .CZ) d d-Miller III
'
Mac o
FACILITY SOLUTIONS
Fan Unit
PROJECT: Bank Of America WA5-113 DATE:2/20/2014
LOCATION: Federal Way,WA CONTACT: Eric Gilbert
PROJECT#:7225160
SYSTEM/UNIT:EF-01-Janitors Closet Tested By: Eric Gilbert
AREA: Test Date: February 20, 2014
Unit Data Motor Data
Fan Manufacturer Broan Rated Airflow Capacity 80 CFM
Fan Model Number L100 Motor Manufacturer Broan-Nuetone
Motor HP 87 Watt
Test Data Motor RPM 640 RPM
Motor Rated Volts 120 Volts
Total Airflow Design 80 CFM Motor Phase 1
Total Airflow Actual 75 CFM Motor Hertz 60 Hz
Motor FL Amps 1.10 Amps
*Notes
SYSTEM/UNIT:EF-01-Mens Restroom Tested By: Eric Gilbert
AREA: Test Date: February 20, 2014
Unit Data Motor Data
Fan Manufacturer Broan Rated Airflow Capacity 80 CFM
Fan Model Number L100 Motor Manufacturer Broan-Nuetone
Motor HP 87 Watt
Test Data Motor RPM 640 RPM
Motor Rated Volts 120 Volts
Total Airflow Design 80 CFM Motor Phase 1
Total Airflow Actual 85 CFM Motor Hertz 60 Hz
Motor FL Amps 1.10 Amps
*Notes
SYSTEM/UNIT:EF-01-Restroom Tested By: Eric Gilbert
AREA: Test Date: February 20, 2014
Unit Data Motor Data
Fan Manufacturer Broan Rated Airflow Capacity 80 CFM
Fan Model Number L100 Motor Manufacturer Broan-Nuetone
Motor HP 87 Watt
Test Data Motor RPM 640 RPM
Motor Rated Volts 120 Volts
Total Airflow Design 80 CFM Motor Phase 1
Total Airflow Actual 80 CFM Motor Hertz 60 Hz
Motor FL Amps 1.10 Amps
* Notes
MacDonald-Miller
NEBB Certified TAB Contractor
CZ) MacDvld-Miller .
FACILITY SOLUTIONS
Fan Unit
PROJECT: Bank Of America WA5-113 DATE:2/20/2014
LOCATION:Federal Way,WA CONTACT:Eric Gilbert
PROJECT#:7225160
SYSTEM/UNIT:EF-01-Women's Restroom Tested By: Eric Gilbert
AREA: Test Date: February 20, 2014
Unit Data Motor Data
Fan Manufacturer Broan Rated Airflow Capacity 80 CFM
Fan Model Number L100 Motor Manufacturer Broan-Nuetone
Motor HP 87 Watt
Test Data Motor RPM 640 RPM
Motor Rated Volts 120 Volts
Total Airflow Design 80 CFM Motor Phase 1
Total Airflow Actual 75 CFM Motor Hertz 60 Hz
Motor FL Amps 1.10 Amps
* Notes
SYSTEM/UNIT:EF-01-Women's Restroom Tested By: Eric Gilbert
AREA: Test Date: February 20, 2014
Unit Data Motor Data
Fan Manufacturer Broan Rated Airflow Capacity 80 CFM
Fan Model Number L100 Motor Manufacturer Broan-Nuetone
Motor HP 87 Watt
Test Data Motor RPM 640 RPM
Motor Rated Volts 120 Volts
Total Airflow Design 80 CFM Motor Phase 1
Total Airflow Actual 80 CFM Motor Hertz 60 Hz
Motor FL Amps 1.10 Amps
* Notes
SYSTEM/UNIT:EF-01-Women's Restroom Tested By: Eric Gilbert
AREA: Test Date: February 20, 2014
Unit Data Motor Data
Fan Manufacturer Broan Rated Airflow Capacity 80 CFM
Fan Model Number L100 Motor Manufacturer Broan-Nuetone
Motor HP 87 Watt
Test Data Motor RPM 640 RPM
Motor Rated Volts 120 Volts
Total Airflow Design 80 CFM Motor Phase 1
Total Airflow Actual 85 CFM Motor Hertz 60 Hz
Motor FL Amps 1.10 Amps
* Notes
MacDonald-Miller
NEBB Certified TAB Contractor
. CitZ) MacDod-Miller III
FACILITY SOLUTIONS
Fan Unit
PROJECT:Bank Of America WA5-113 DATE:2/20/2014
LOCATION: Federal Way,WA CONTACT:Eric Gilbert
PROJECT#:7225160
SYSTEM/UNIT:EF-02-Breakroom Tested By: Eric Gilbert
AREA: Test Date: February 20, 2014
Unit Data Motor Data
Fan Manufacturer Broan Rated Airflow Capacity 235 CFM
Fan Model Number L250 Motor Manufacturer Broan-Nuetone
Motor HP 166 Watt
Test Data Motor RPM 830 RPM
Motor Rated Volts 120 Volts
Total Airflow Design 235 CFM Motor Phase 1
Total Airflow Actual 225 CFM Motor Hertz 60 Hz
Motor FL Amps 2.10 Amps
*Notes
SYSTEM/UNIT:RF-01 Tested By: Eric Gilbert
AREA: Test Date: February 20, 2014
Unit Data Motor Data
Fan Manufacturer Central Rated Airflow Capacity 8000 CFM
Fan Model Number 27 BI Motor Frame 145T
Fan Serial Number 61992 Motor HP 2 HP
Motor RPM 1740 RPM
Test Data Motor Rated Volts 208 Volts
Motor Phase 3
Total Airflow Design 8000 CFM Motor Hertz 60 Hz
Total Airflow Actual 7865 CFM Motor FL Amps 6.30 Amps
Motor Volts T1-T2 210 Volts
Motor Volts T2-T3 211 Volts Sheave Data
Motor Volts T1-T3 210 Volts
Motor Amps T1 5.00 Amps Motor Sheave Diam. 5 in.
Motor Amps T2 4.20 Amps Fan Sheave Diam. 11 in.
Motor Amps T3 3.90 Amps Number of Belts 1
Belt Size A70
Sheave Center Line 23 1/2 in.
*Notes
MacDonald-Miller
NEBB Certified TAB Contractor
• - -- 104 °98
Fed 'k RECEIVE
Federal Way PERMIT SF MF Ca PL DE EN FP
COMMUNITY DEVELOPMEN 3! o9Ps °6 2012APPLI CATI O N 11).: l 0/4/(?
253-835-2607•FAX 253-835-2609 /
u,w,..,atuo]edr,almrni.oo>n /
CITY OF FEDERAL WAY
CDS
SITE ADDRESS SUITE/UNIT#W
32011 PACIFIC HY S FEDERAL WAY,WA 98003 FL 1
PROJECT VALUATION ZONING ASSESSOR'S TAX/PARCEL#
$ 84,900.00 SEE DWGS 1 5 0 0 5 0 _ 0 1 3 0
TYPE OF PERMIT ❑ BUILDING 0 PLUMBING cil MECHANICAL
0 DEMOLITION 0 ENGINEERING 0 FIRE PREVENTION
NAME OF PROJECT
(TenantName/Homeowner Last Name) BANK OF AMERICA-FEDERAL WAY
DEMO 20 TON SPLIT SYSTEM&RELIEF FAN. INSTALL(2)VAV BOXES. INSTALL(2)7.5 TON
PROJECT DESCRIPTION
Detailed description of work to SPLIT SYSTEMS. INSTALL(1)5-TON SPLIT SYSTEM. INSTALL(6)EXHAUST FANS. INSTALL
be included on this permit only (1)RELIEF FAN ON ROOF. INSTALL(3)ELECTRIC WALL HEATERS. INSTALL NEW RELIEF
GRILLE IN LOBBY.
NAME PRIMARY PHONE
PROPERTY OWNER BANK OF AMERICA
MAILING ADDRESS E-MAIL
100 N TRYON ST
CITY CHARLOTTE STATE ZIP
28255
NAME PHONE
MACDONALD MILLER (206)768-4278
MAILING ADDRESS E-MAIL
CONTRACTOR 7717 DETROIT AVE SW darla.doll@macmiller.com
CITY SEATTLE STATE ZIP FAX
WA 98106
WA STATE CONTRACTOR'S LICENSE# EXPIRATION DATE FEDERAL WAY BUSINESS LICENSE#
MACDOFS980RU 12 / 31 / 12 20-03-100372-00-BL
NAME PHONE
DARLA DOLL (206)768-4278
APPLICANT
MAILING ADDRESS 7717 DETROIT AVE SW E-MAIL
darla.doll@macmiller.com
CITY SEATTLE STATE ZIP FAX
WA 98106
PROJECT CONTACT NAME STEVE HARGROVE PHONE
(The individual to receive and (206)768-4000
respond to all correspondence MAILING ADDRESS E-MAIL steve.hargrove
7717 DETROIT AVE SW
concerning this application) @macmiller.com
CITY SEATTLE STATE ZIP FAX
WA 98106
ALTERNATE CONTACT NAME: PHONE E-MAIL
DARLA DOLL (206)768-4278 darla.doll@macmiller.com
PROJECT FINANCING NAME N/A 0 OWNER-FINANCED
Required value of$5,000 or more
(RCW 19.27.095) MAILING ADDRESS,CITY,STATE,ZIP PHONE
I certify under penalty of perjury that I am the property owner or authorized agent of the property owner.I certify that to the best
of my knowledge, the information submitted in support of this permit application is true and correct.I certify that I will comply with
all applicable City of Federal Way regulations pertaining to the work authorized by the issuance of a permit. I understand that the
issuance of this permit does not remove the owner's responsibility for compliance with local, state, or federal laws regulating
construction or environmental laws.
I further agree to hold harmless the City of Federal Way as to any claim(including costs,expenses,and attorneys'fees incurred in
the investigation and defense of such claim),which may be made by any person, including the undersigned, and filed against the city,
but only where such claim arises out of the reliance of the city, including its officers and employees, upon the accuracy of the
information supplied to the city as a part of this application.
�— 09/06/2012
SIGNATURE: G—�,,.�-, �--- DATE
PRINT NAME: DARLA DOLL
Bulletin#100—January 1,2011 Page 1 of 3 k:\Handouts\Permit Application
•
.
VALUE of MECIIANrcAL WORx $ 84,900.00 (a copy of bid or estimate must be provided)
Indicate how many of each type of fixture to be installed or relocated as part of this project. Do not include existing fixtures to remain.
AIR HANDLING UNITS 7 FANS GAS PIPE OUTLN:lb 6 OTHER(Describe)
AIR CONDITIONER FIREPLACE INSERTS HOODS(Commercial) 3-SPLIT SYSTEMS
BOILERS FURNACES HOT WATER TANKS(Gas) 3-WALL HEATERS
COMPRESSORS GAS LOG SETS REFRIGERATION SYST
DUCTING GAS PIPING WOODSTOVES
Indicate how many of each type of fixture to be installed or relocated as part of this project. Do not include existing fixtures to remain.
BATHTUBS or Tub/Shower Combo) LAVS(Hand Sinks) TOILETS WATER PIPING
DISHWASHERS RAINWATER SYSTEMS URINALS OTHER(Describe)
DRAINS SHOWERS VACUUM BREAKERS
DRINKING FOUNTAINS SINKS(Kitchen/Utility) WATER HEATERS(Electric)
HOSE BIBBS SUMPS WASHING MACHINES TOTAL FIXTURES
1 fit. VORMATIQX
CRITICAL AREAS ON PROPERTY? WATER PURVEYOR SEWER PURVEYOR VALUE OF EXISTING IMPROVEMENTS
EXISTING/PREVIOUS USE LOT SIZE(In Square Feet) EXISTING FIRE SPRINKLER SYSTEM? PROPOSED FIRE SUPPRESSION SYSTEM?
❑Yes o No ❑Yes 0 No
AREA DESCRIPTION(in square feet) EXISTING PROPOSED TOTAL FOR OFFICE USE
E,# EMENT �'
r
FIRST FLOOR(or Mobile Home)
.............................................
SECOND FLOOR
COVERED ENTRY
DECD
GARAGE ❑ CARPORT 0
OTHER(describe) ;
EXISTINGPROPOSED TOTAL '....................................................................... ...............................................................
Area Totals
ESTIMATED SELLING PRICE$ #OF BEDROOMS
AREA DESCRIPTION Area Occupancy Group(s) Construction #of Additional Information
in Square FeetType Stories
STEW BUILDING
ADDITION
AREA DESCRIPTION
Area Occupancy Group(s) Construction #of Additional Information
in Square Feet Type Stories
TOTAL BUILDING
TENANT AREA ONLY 2
PROJECT A�ONLY
Bulletin#100—January 1,2011 Page 2 of 3 k:\Handouts\Permit Application