15-106276 - Building.//.. - Commercial
City o&Federal.Dev. y
S Permit #: 15-106276-00-CO
Community&Econ.Dev.Services
33325 8th Ave S
Federal Way,WA 98003 Inspection Request Line: (253) 835-3050
Ph:(253)835-2607 Fax (253)835-2609 p q
Project Name: FREEDOM FITNESS
Project Address: 1320 S 324TH ST Unit A-Ill Parcel Number: 150050 0070
Project Description: TI-Interior tenant improvement work to include construction of partition walls to create
offices, restroom and storage space.Plumbing and mechanical by separate permits.
Owner Applicant Contractor Lender
FREEDOM FITNESS INC TERESA FORTINO VELOTTA CONSTRUCTION CO OWNER IS LENDER
15830 1ST AVE S SUITE B-107 HELIX DESIGN GROUP INC
BURIEN WA 98148-3305 6021 12TH ST E VELOTCC053N8(9/27/16)
TACOMA WA 98424 100 290TH AVE SE
FALL CITY WA 98024
Census Category: 437 - Commercial alt/add/conversion
Includes: #1 #2 #3 #4
Occupancy Class: A-3
Construction Type: Type V-B
Occupancy Load: 76
Floor Area(sq.ft.) 4,324 0 0 0
Additional Permit Information
Building Pre-con.Meeting Required? No Existing Sprinkler System in Building? Yes
Mechanical to be Included9 No Number of Stories 1
Permit for Building Shell Only9 No Plumbing to be Included? No
Proposed Structure Valuation 140000.00 Special Inspection(s)Required9 No
New/Additional Sq.Feet-Total 0 Occupancy#1 -Use Gymnasium
No Fixtures Associated With This Permit !!
PERMIT EXPIRES Saturday, August 27, 2016
Permit Issued on Monday, February 29, 2016
I hereby certify that the above information is correct and that the construction on the above described property and
the occupancy and the use w be in accordance with the laws, rules and regulations of the State of Washington
• • of Federal Way.
Owner or ageitt>._. �' 1�� Date: ,-2
7 /(/
C.M..
_ TE INSPECTOR AREA AND TYPE OF INSPECTION
“2;,---(0 fy. ,A, --51A \)/
-- .- cr IA , � � ,X ,
-z5--ILS
® ' THIS CARD IS TO REMAIN ON-SITE
CITY OF Construction Inspection Record
Feder 1 Way INSPECTION REQUESTS: (253)835-3050
PERMIT#: 15-106276-00-CO Address: 1320 S 324TH ST Unit A-111
Project: FREEDOM FITNESS INC FEDERAL WAY, WA 98003
Scheduled inspections may be failed if this card is not on-site. DO NOT LOSE THIS CARD. Inspections are listed as close to sequential order as
possible(read left to right,top to bottom). Please schedule inspections as appropriate. Work must not be covered until it is approved. Check with your
inspector if you are unsure about any of the inspections or the inspection sequence. On-going inspections are logged on the back of this card.
0 Initial Erosion Control(4365) D Footings/Setback(4110) ElRe-steel(4215)
To be done prior to breaking ground Approved to place concrete Approved to place concrete or grout
By Date By Date By Date
El Slab/Concrete Floor(4255) 0 Underfloor Framing(4285) El
Floor Sheathing(4105)
Approved to place concrete Approved to sheath floor Approved to install flooring
By Date By Date By Date
'
1-1 Fire/Draft Stops(4095) ❑ Interim Erosion Control(4370) ,'''''' " .,,,,m g. (MI —
Prior to scheduling a Frmiang inspection;
Approved Approved Electrical,Plumbing&Mechanical Rough-in and
Fire/Draft Stop inspections must be signed-off and
By Date By Date
approved. IBC 109.3.4
El Framing(4120)
[I-fl Insulation (4150) ❑Gypsum Wallboard Nailing(4130)
Approved to insulate Approved to install wallboard Approved to install mud&tape
B Date _Z (_ 6, ��,_,__-- Date _„--_--7- _ (/, By kj Date 3130( it.
Suspended Ceiling Grid (4265) 0 Final- S KF&R(4060) El
Final-Planning
Approved to drop tile Approved Approved
By Date By . Date By Date
Final Erosion Control(4375) El Final-Building(4050)
Approved Approved
By Date By �� Date 3 N.--1 ka
•
❑ Rough Electrical Final Electrical Right of Way
Approved Approved Approved
By Date By Date By Date
P^:
EN(,,
March 16, 2016
Paul Velotta
Velotta Construction Co., Inc.
100 290th Avenue SE
Fall City WA 98024
RE: Freedom Fitness Exterior Stud Wall Evaluation,Federal Way WA
Dear Paul:
PSM, Inc. completed a site visit to review concerns of the north exterior wood stud wall framing at a
future Freedom Fitness site (1320 S 324th Street,Federal Way WA).
The intent of this letter is to provide documentation and a summary of our review, including conclusions
based on visual observation and recommendations regarding repairs if necessary to restore the north
wall.
The purpose of our site visit was to examine the existing conditions of the north wood exterior wall
framing and to provide a structural repair solution if needed. The existing building structure consists of
a Berkley type roof framing system with exterior wood perimeter walls. The existing exterior north wall
construction consists of plywood sheathing, 2x6 wood studs, &wood header beams at door openings.
The wall is supported below on the existing concrete foundation footing. The exterior north wall in
question supports 3ft. of tributary roof framing.
Photo shows partial north wood wall
171 woof framing. Damage occurs at
1
numerous wall studs. Damage to studs
consists of prior notches and bored holes
at various locations along the height of
the studs.
Ten stud framing locations of the
exposed wall framing were identified as
needing to be repaired. The studs in
question were marked while on site and
are to be repaired as recommended.
2200 6TH AVENUE, #601 WWW.PSM-ENGINEERS.COM PHONE 206-622-4580
SEATTLE WASHINGTON 98121 USA FAX 206-622-0422
J
Ad
•
Recommended Repairs:
Ten stud framing locations (numbered and identified while on site) are to be repaired. The following is
a summary of the existing framing per location and the recommended repair for each location. All new
lumber to be added shall be Douglas-Fir Type#1 material.
-Stud Framing Location#1
Existing Framing:
DBL 2x6 studs are not fully supported at base and a number of existing bored holes.
Recommended Repair:
Add 2x bearing blocking around PVC piping at bottom of wall and add Simpson MSTC66 strap
from the added bearing blocking to existing stud.
-Stud Framing Location#2
Existing Framing:
Single 2x6 stud is not fully supported at base and a number of existing bored holes near toward
the interior face of wall.
Recommended Repair:
Add partial height 2x4 at each side of existing stud. The new 2x4s are to be against the existing
plywood and should be nailed to the existing framing with (2)l Od nails at 6"oc.
-Stud Framing Location#3
Existing Framing:
Double 2x6 stud has a number of notches and (4) existing bored holes.
Recommended Repair:
Add partial height 2x4 at each side of existing studs. The new 2x4s are to be against the existing
plywood and should be nailed to the existing framing with (2)10d nails at 6"oc.
-Stud Framing Location#4
Existing Framing:
Triple 2x6 stud has a number of notches and existing bored holes. (2) of the existing studs are
not fully supported at the base.
Recommended Repair:
Add 2x bearing blocking at base. Add partial height 2x4 at each side of existing studs. The new
2x4s are to be against the existing plywood and should be nailed to the existing framing with
(2)l Od nails at 6"oc.
•
'r
-Stud Framing Location#5
Existing Framing:
Double 2x6 stud has a number of notches and existing bored holes. (1) of the existing stud is not
fully supported at the base.
Recommended Repair:
Add 2x bearing blocking at base. Add partial height 2x4 at each side of existing studs. The new
2x4s are to be against the existing plywood and should be nailed to the existing framing with
(2)l Od nails at 6"oc.
-Stud Framing Location#6
Existing Framing:
Double 2x6 stud has a number of notches and existing bored holes.
Recommended Repair:
Add partial height 2x4 at each side of existing studs. The new 2x4s are to be against the existing
plywood and should be nailed to the existing framing with (2)l Od nails at 6"oc.
-Stud Framing Location#7
Existing Framing:
Single 2x6 stud with 2x4 blocking has numerous notches and bored holes.
Recommended Repair:
Add partial height 2x4 at each side of existing studs (Flat side of 2x along face of existing
plywood). The new 2x4s are to be against the existing plywood and should be toe-nailed to the
existing framing with (2)l Od nails at 6"oc.
-Stud Framing Location#8
Existing Framing:
Single 2x6 stud with 2x4 blocking has numerous notches and bored holes.
Recommended Repair:
Add partial height 2x4 at each side of existing studs (Flat side of 2x along face of existing
plywood). The new 2x4s are to be against the existing plywood and should be toe-nailed to the
existing framing with (2)l Od nails at 6"oc.
-Stud Framing Location#9
Existing Framing:
Single 2x6 stud with 2x4 blocking has numerous notches and bored holes.
Recommended Repair:
Add partial height 2x4 at each side of existing studs (Flat side of 2x along face of existing
plywood). The new 2x4s are to be against the existing plywood and should be toe-nailed to the
existing framing with (2)10d nails at 6"oc.
' : >8 lI 'it
-Stud Framing Location#10
Existing Framing:
Double 2x6 stud blocking has numerous notches and bored holes.
Recommended Repair:
Existing piping is to be moved away from this location. Add partial height 2x4 at each side of
existing studs (Flat side of 2x along face of existing plywood). The new 2x4s are to be against
the existing plywood and should be toe-nailed to the existing framing with (2)10d nails at 6"oc.
Framing locations and recommended repairs were communicated to General Contractor while on site
and are to be installed as recommended.
Please contact us for any questions or clarifications.
,,J4 -f4.
Sincerely, vihVID sr
PSM, Inc. G 01.WAS,r .
,i7.A...gler,re ir"------ 4
4,. ,
, , ,. _
. _ i„ .., _. „.„ .,..„
. ,
-, . ..„ ,. ,
Robert Cruz, P.E. lA
Project Manager
• 0
111C1,::01F
PER Mg!
Federal Way
V DEC 112015
5 z7(:-,i.
1 7 J 5
FEDERAL WAYPERMIT NUMBER —
_ — _ _ CDGET DATE
SITE ADDRESS SUITE/UNIT#
1 Sao 4. 38,4-- ) 44- A- -1. i i
PROJECT VALUATION ZONING ASSESSOR'S TAX/PARCEL#
$ ► 01000 8N t 6 0 0 5 0 _ o o 7 0
TYPE OF PERMIT ❑ BUILDING ❑ PLUMBING ❑ MECHANICAL ❑ DEMOLITION ❑ ENGINEERING ❑ FIRE PREVENTION
NAME OF PROJECT fi/,G m ) :7 ./7)C ��-
PROJECT DESCRIPTION p. =4". .�f L A4•4_. ..� 1t.lAl�
Detailed description of work to •
be included on this permit only
NAME PRIMARY PHONE
Pfl �o� a�� • s�oo
PROPERTY OWNER MAILING A D RSS E-MAI
SSS u Int �d• 4 /a 7
CIT • SigA ZIP_/ / ! g
PHONE
NAME �5- ,,,IN
MAILING ADDRESS E-MAIL
CONTRACTOR
CITY STATE ZIP FAX
WA STATE CONTRACTOR'S LICENSE# EXPIRATION DATE FEDERAL WAY BUSINESS LICENSE#
���///��� `y'• / / A 1 I�, Q
NA HONE
//l / /O''t/ . -/D 3 7
APPLICANT M ILING ADDRmth 4.. E-MAIL
CITE-+ l) AjfE ZIP _ ji. FAX
PROJECT CONTACT NAME 7- t.- /A._ i�G�/ "r'n PR I 3�v i O - 7D 71
(The individual to receive and AILING ADDR S ifflAi/1/Iµ�, eh
-aM/AIL'�
respond to all correspondence706al ��� siC��x :����y •44
concerning this application) J,�'3i XtIn)' sTgT>� zI oty. FAX
NAME ��
PROJECT FINANCING ❑ OWNER-FINANCED
Required value of$5,000 or more MAILING ADDRESS,CITY,STATE,ZIP PHONE
(RCW 19.27095)
I certify under penalty of perjury that I am the property owner or authorized agent of the property owner. I certify that to the best
of my knowledge, the information submitted in support of this permit application is true and correct. I certify that I will comply with
all applicable City of Federal Way regulations pertaining to the work authorized by the issuance of a permit. I understand that the
issuance of this permit does not remove the owner's responsibility for compliance with local, state, or federal laws regulating
construction or environmental laws.
I further agree to hold harmless the City of Federal Way as to any claim(including costs, expenses, and attorneys'fees incurred in
the investigation and defense of such claim), which may be made by any person, including the undersigned, and filed against the city,
but only where such claim arises out of the reliance of the city, including its officers and employees, upon the accuracy of the
information supplied to the city as a part of this application. , l
SIGNATURE: a� kixidiyr
DATE /v / / /S
PRINT NAME: 7-ere-Qt.- I J kV
Bulletin#100—October 26,2015 Page 1 of 3 k:AHandouts\Permit Application
'MECHANICAL
t S
VALUE OF MECHANICAL WORK
MECHANICAL PERMIT •�, S $
Indicate how many
ofeach type of fixture o be installed or relocated as part of this project. Do not include existing fixtures to remain.
AIR HANDLING UNITS FANS GAS PIPE OUTLETS OTHER(Describe)
AIR CONDITIONER FIREPLACE INSERTS HOODS(Commercial)
BOILERS FURNACES HOT WATER TANKS(Gas)
COMPRESSORS GAS LOG SETS REFRIGERATION SYST
DUCTING GAS PIPING WOODSTOVES
VALUE OF PLUMBING WORK
PLUMBING PERMITDq-64-Kel,
$
Indicate how many of each type offix re to be installed or relocated as part of this project. Do not include existing fixtures to remain.
BATHTUBS(or Tub/Shower Combo) LAVS(Hand Sinks) TOILETS WATER PIPING
DISHWASHERS RAINWATER SYSTEMS URINALS OTHER(Describe)
DRAINS SHOWERS VACUUM BREAKERS
DRINKING FOUNTAINS SINKS(Kitchen/utility) WATER HEATERS(Electric)
HOSE BIBBS SUMPS WASHING MACHINES TOTAL FIXTURES
GENERAL INFORMATION
CRITICAL AREAS ON PROPERTY? WATER PURVEYOR SEWER PURVEYOR VALUE OF EXISTING IMPROVEMENTS
.1rao /Wildit t7r0t&ho U4i4 *10, 500
EXISTING/PREVIOUS USE LOT SIZE(In Square Feet) EXISTING FIRE SPRINKLER SYSTEM? PROPOSED FIRE SUPPRESSION SYSTEM?
1(.tM2
44i. 'las I /' r. XYes ❑ No ❑Yes$iNo
RESIDENTIAL - NEW OR ADDITION
AREA DESCRIPTION(in square feet) EXISTING PROPOSED TOTAL FOR OFFICE USE
BASEMENT
FIRST FLOOR(or Mobile Home)
SECOND FLOOR
COVERED ENTRY
DECK
GARAGE ❑ CARPORT ❑
OTHER(describe)
EXISTING PROPOSED TOTAL
Area Totals
**NEW HOMES ONLY**
ESTIMATED SELLING PRICE$ # OF BEDROOMS
COMMERCIAL—NEW/ADDITION
AREA DESCRIPTION Area in Occupancy Group(s) Construction #of Additional Information
Square Feet Type Stories
NEW BUILDING
ADDITION
COMMERCIAL—REMODEL/TENANT IMPROVEMENTS
AREA DESCRIPTION Area in Occupancy Group(s) Construction #of Additional Information
Square Feet Type Stories
TOTAL BUILDING 0146/ 26`
TENANT AREA ONLY Ott 3913A 03 '
'�l
PROJECT AREA ONLY k (/it A3 Ve I