18-104799 Mechanical
City of Federal Way Permit #:18-104799-00-ME
Community Development Dept.
33325 8th Ave S
Federal Way,WA 98003 Inspection Request Line: (253)835-3050
Ph:(253)835-2607 Fax(253)835-2609
Project Name: MATTRESS FIRM/CAR TOYS
Project Address: 31610 PACIFIC HWY S Parcel Number:092104 9118
Project Description: Replace an existing 10-ton roof top units with a new 10-ton roof top unit on the same curb.
Owner Applicant Contractor
RHEKI FEDERAL WAY L L C NEW CASTLE MECHANICAL NEW CASTLE MECHANICAL
12013 206TH PL SE 9823 160TH ST E SUITE A NEWCACM924OD(10/7/20)
ISSAQUAH,WA 98027 PUYALLUP WA 98375
9823 160TH ST E SUITE A
PUYALLUP WA 98375
Additional Permit information i
Mechanical Work Valuation? 19000 Is this an Onl' .C.ap. wtion9 Yes
4111)
Air Handling Units 1
COUP • S:Noill4
Subject to field inspection without plans.
PERMIT - - uesday,9 lelpril,2019
Permit Issu , ii rsda ober 11,2018
•
a.
I hereby certify that the above info •Bile rrect and e construction on the above described property
and the occupancy and the use wil ' accordath the laws, rules and regulations of the State of
Wash' .ton and 1 ity of Federal Way.
Owner or agent: . . s/4t/iiV/4,4cDate: /0/li 7,1
ei 1
41 THIS CARD IS TO REMAIN ON-SITE
Fec�era�Way Construction Inspection Record
INSPECTION REQUESTS:(253)835-3050
PERMIT#: 18 104799 00 Address: 31610 PACIFIC HWY S
Project: RHEKI FEDERAL WAY L L C FEDERAL WAY WA 98003-5408
Scheduled inspections may be failed if this card is not on-site. DO NOT LOSE THIS CARD. Inspections are listed as close to sequential order as possible
(read left to right,top to bottom). Please schedule inspections as appropriate. Work must not be covered until it is approved. Check with your inspector if
you are unsure about any of the inspections or the inspection sequence. On-going inspections are logged on the back of this card.
1❑ Mechanical Rough-in(4165) Y❑ Gas Piping(4125) El Final-Mechanical(4065)
Approved Approved to release test Approved
By Date • By Date By Date
0 Rough Electrical 0 Final Electrical ❑ Right of Way
Approved Approved Approved
By Date By Date By Date
Nib,
CITY OF Building Division
3332Fed a ra I WayFederal Eighth, Avenue -63 South
Way,WA 98003-6325
Phone 253-835-2607 Fax 253-835-2609
CORRECTION NOTICE
ADDRESS: 31(40 Qtic_ )4 j S • PERMIT#: ) -- )0/476 ci
1, c. 606 , 2 , 1 - S \ s y54- ,05
2 000 C1-10.& cc move_ i,�n�k i s 9000 cF l
SKr itea\ ,e Q‘..‘‘c'El Dkac— 'f0 Ri^al ✓H•2.c-1,- Tr)sp.
IF YOU HAVE QUESTIONS CALL jy�Ol� (253) 835- 2(e 3 7
WHEN CORRECTIONS HAVE BEEN MADE, CALL (25 ) 835-3050 FOR RE-INSPECTION. SEE BACK OF CARD
FOR DETAILS. NOTE: ELECTRICAL CORRECTIONS ARE REQUIRED TO BE MADE WITHIN 15 DAYS.
1 )
« 4•1
DATE INSPECTOR
DO NOT REMOVE THIS NOTICE
Page of
•
• ,
fiLes
altos • ca,
Carrier
SUBMITTAL
Project
Mattress Firm 10T
Date
Tuesday, August 21, 2018
JFiJim.7
J,,
RECEIVED
OCT 102018
GITY OF FEDERAL WAY
COMMUNITY DEVELOPMENT
•
•
Table Of Contents
Project: Mattress Firm 10T 08/21/2018
Prepared By: 0352PM
10T PHP 3
Unit Report 4
Certified Drawing 5
Performance Summary
Unit Feature Sheet 11
Spec Sheet 12
Packaged Rooftop Builder 1.49i Page 2 of 12
,
10T PHP
Project: Mattress Firm 10T 08/21/2018
Prepared By: 03:52PM
10T PHP
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Unit Feature Sheet
Spec Sheet
Packaged Rooftop Builder 1.49i Page 3 of 12
•
Unit Report For 10T PHP
Project: Mattress Firm 10T 08/21/2018
Prepared By: 03:52PM
Unit Parameters Dimensions(ft.in.)&Weight(lb.)***
Unit Model.. 50TCQD12A2A5-0A0G0 Unit Length* 7'4.125"
Unit Size:_____._._....__ 12(10 Tons) Unit Width 4'11.5"
Volts-Phase-Hertz:_ 208440 Unit Height' 4' 1.375"
Heating Type' Heat Pump **• Total Operating Weight:___.._.___.__ ._.._.1230 lb
Duct Cfg:. .____..._..Vertical Supply/Vertical Return
Two-Stage Cooling Refrigeration Coil Weights and Dimensions are approximate. Weight does
not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes.For exact
dimensions and weights,refer to appropriate product
data catalog.
Lines and Filters
Condensate Drain Line Size' 3/4
Return Air Filter Type' Throwaway
Return Air Filter Quantity' 4
Return Air Filter Size' 20 x 20 x 2
Unit Configuration
Medium Static Option Belt Drive
Al/Cu-Al/Cu
Base Electromechanical Controls
Standard Packaging
2-Speed indoor fan motor controlled by VFD
Warranty information
1-Year parts(STD.)
5-Year Compressor(std.)
No optional warranties were selected.
NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.
Ordering Information
Part Number Description Quantity
50TCQD12A2A5-0A0G0 Rooftop Unit 1
Base Unit
Medium Static Option Belt Drive
None
2-Speed Indoor Fan(VFD)Controller
Accessories
CRHEATER112A00 24.0/29.4/32.0 kW 208/230/240-3-60 Volt Electric Heater 1
CRSINGLE051A00 Single Point Kit 1
CRECOMZR069A01 LOW LEAK-Vertical EconoMi$er 1
Packaged Rooftop Builder 1.49i Page 4 of 12
N
CO 2
-
N N Ul
p a d a x 1 8 m m
=$ =1 a 'a, 'a§ a
ani —` a,ral^l •- t«y N
2i 1
4.
aa _ , 17.7:21 g»Inig
R (II ^a p
O. iri
rf I----x:7.a- -- ,i i itil
ii LI
En Fg ;�
CI giUm
-� (1 I
* I l==#=
..—=— Sia
_ 7--Wig -
ti
g ,'. I a3�Y�
E Y�va
a i , I $`-E i; s�
Iszi
• ay i;I * o
€ "`` :g -§ III 1-
wen _▪ a a E iiI ) coo
RI CO Ce
as ate.
22 )
\ hi co coi
&
4
t
j_
,
,!
.b
. I
8 2
lot
° — . /
a.
R
0
I |/
J
C11
C
22; . . . . • • ) !\
O % --.--V-\z ® ' ca
\
. 2 ,,,17/.
zz ..Fr-
t : / .
0 \\.j . 11
-
•
.
. (� , \ (
k G
_ . k
11-
. \
kEz % Fa
.! k
43
I-
� �
5
_ ■ / $ »
\¢ - sCC
/Q.
0 §
os
[�
CM C4
. t2 &
@°- 0-
' = 1
z\ §
| fl
It !
® / f |!#i |
I / _ \ / !'I; I
f
, < f\ %f | k\ t
w \ : \ / z |
: < . . . � ! ; ;!;II
/i1 1 !® / ill!
`as ii, ® ) it $}
° =® 7itlkk|I| i §
, /
^ \ i!i111111fl1I1I1!
TS
F
1 ` \ |{f f !!i-f{fE , !
0 \ z ` / |�! k ■a2t!§ §! ! !{
°i{ ; W4 ;A4S; ,
. \ / \, �\ / \ / / f
\ \ y . , 0
y 7 ;
& &
k )
.
h (
2
a
o
0-u. 2
•
Performance Summary For 10T PHP
Project: Mattress Firm 10T 08/21/2018
Prepared By: 03:52PM
Part Number:50TCQD12A2A5-0A0G0
ARI EER 11.00
IEER. 12.5
Base Unit Dimensions
Unit Length 88.1 in
Unit Width: 59.5 in
Unit Height. 49.4 in
Operating Weight
Base Unit Weight 1050 lb
Medium Static Option Belt Drive. 15 lb
2-Speed Indoor Fan(VFD)Controller: 20 lb
Accessories
24.0/29.4/32.0 kW 208/230/240-3-60 Volt Electric Heater 45 lb
Single Point Kit 15 lb
LOW LEAK-Vertical EconoMi$er: 75 lb
Total Operating Weight:. 1230 lb
Unit
Unit Voltage-Phase-Hertz. 208-3-60
Air Discharge Vertical
Fan Drive Type. Belt
Actual Airflow. 4000 CFM
Site Altitude 0 ft
Cooling Performance
Condenser Entering Air DB 95.0 F
Evaporator Entering Air DB 80.0 F
Evaporator Entering Air WB 67.0 F
Entering Air Enthalpy. 31.44 BTU/lb
Evaporator Leaving Air DB: 59.6 F
Evaporator Leaving Air WB 57.8 F
Evaporator Leaving Air Enthalpy. 24.87 BTU/lb
Gross Cooling Capacity: 118.20 MBH
Gross Sensible Capacity. 88.11 MBH
Compressor Power Input 10.84 kW
Coil Bypass Factor 0.084
Heating Performance
Outdoor Ambient Temperature. 47.0 F
Entering Air Indoor Coil DB 70.0 F
Leaving Air Indoor Coil DB 96.8 F
Total Heating Capacity. 115.90 MBH
Integrated Heating Capacity: 115.90 MBH
Heating Power Input: 11.27 kW
High Temperature COP. 3.3
Low Temperature COP 2.3
Electric Heating Capacity. 24.00 kW
Unit Leaving Air Temp 115.8 F
Supply Fan
External Static Pressure* 0.80 in wg
Options/Accessories Static Pressure
Electric Heaters: 0.08 in wg
Economizer 0.20 in wg
Total Application Static(ESP+ Unit Opts/Acc.): 1.09 in wg
Fan RPM: 915
Fan Power 2.28 BHP
Packaged Rooftop Builder 1.49i Page 8 of 12
Performance Summary For 10T PHP
Project: Mattress Firm 10T 08/21/2018
Prepared By: 03:52PM,
NOTE:.____....._._.__ _ ._. Selected IFM RPM Range:733-949
Electrical Data
Voltage Range: 187-253
Compressor#1 RLA: 15.6
Compressor#1 LRA 110
Compressor#2 RLA:...___. 15.9
Compressor#2 LRA: 110
Actual Electric Heater kW 24
Electric Heater FLA:. 66.7
Indoor Fan Motor Type MED
Indoor Fan Motor FLA' 10.8
Power Supply MCA 136
Power Supply MOCP(Fuse or HACR)• 150
Disconnect Size FLA: . 132
Disconnect Size LRA. 396
Electrical Convenience Outlet None
Outdoor Fan[Qty/FLA(ea)]• 1 16.2
Electric Heater Number of Stages' 1
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage
Acoustics
Sound Rating 87.0 db
Sound Power Levels,db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 90.7 86.7 88.1
125 Hz 86.1 80.5 90.0
250 Hz 72.8 67.4 85.9
500 Hz 71.9 66.7 83.0
1000 Hz 70.7 65.5 81.6
2000 Hz 67.3 59.8 78.5
4000 Hz 68.2 57.5 76.4
8000 Hz 64.9 51.6 75.5
A-Weighted 77.2 71.0 87.0
Advanced Acoustics
to
filimia- ---: , rie---0 ,,,,,,:,,,),
O
Advanced Accoustics Parameters
1. Unit height above ground' 30.0 ft
2. Horizontal distance from unit to receiver 50.0 ft
3. Receiver height above ground:..._.........._..,._...__ ...__.5.7 ft
4. Height of obstruction' 0.0 ft
5. Horizontal distance from obstruction to receiver:_..0.0 ft
6. Horizontal distance from unit to obstruction' 0.0 ft
Packaged Rooftop Builder 1.49i Page 9 of 12
Performance Summary For 10T PHP
Project: Mattress Firm 10T 08/21/2018
Prepared By: 03:52PM
Detailed Acoustics Information
Octave Band Center Freq.Hz 63 125 250 500 1k 2k 4k 8k Overall
A 88.1 90.0 85.9 83.0 81.6 78.5 76.4 75.5 94.0 Lw
B 61.9 73.9 77.3 79.8 81.6 79.7 77.4 74.4 87.0 LwA
C 55.7 57.6 53.5 50.6 49.2 46.1 44.0 43.1 61.6 Lp
D 29.5 41.5 44.9 47.4 49.2 47.3 45.0 42.0 54.6 LpA
Legend
A Sound Power Levels at Units Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA
C Sound Pressure Levels at Specific Distance from Unit, Lp
D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.
FanCurve
2D -
,000 ,
la ��
Ino
X12 �� �, ••:
N -
a, 10
o,
N A � =�
e - � ��
00 ce �- �� \ � „� �
U) _
N 2.00131-P
-400FiPM
04 �--
I I I I III ]I ] i I I I till-i
m l- 1 1 1 1 .' 1 1 1 1 I l i 1 1 l 1 1
CO 05 10 15 20 25 35 40 45
Atiflow(CFM-thousands)
RPM=915 BHP=2.28 MaximwnRPM=1400 MaximumBHP=3.70
Note:Pleasec ctapplicationengineeiingforselectionsoutsidethesha region.
SC-SystemCurve RP-RatedPoint
Packaged Rooftop Builder 1.49i Page 10 of 12
Unit Feature Sheet for 10T PHP
Project: Mattress Firm 10T 08/21/2018
Prepared By: 03:52PM
Carrier
WeatherMaker- SOTCQ
PACKAGED ROOFTOP HEAT PUMP UNITS
3.4.5,6,7.11,8-112,10 and 12.5 TON S
PERFORMANCE FEATURES
• a,Roc; R•41a' -C'ef'pa'snt
�r • ASi;RAE931ane^aycondo,ant
• SE8Rs•:pt0134 E_Rsupt0 11.2
• ;EEO s:pto 12.2
• r+So=s;.p o 'a^d CO=s.:oto33
• Snpestage coo.nacap. :,w^t' on 04-0-^woes
• -,,a-supecock ngcaoa..t,controon 38.14^woes
• E'cws^itnp :oCos a t0^aostt.Ond an mitt own^:a000'iece Stn
4Sh+R,.E5 Sta^da^dsot;natesan syeo 4 e-o'an
• • =41,1 cpn,t.o4 f"2"1a^.ti^a t0 0:pn:a:$''0 0^.a.-ooze s'.0
'tp 's on 04.12 root s. S-oo y p.Gt+t yp..:rto
'4 sr.e-*cog'on,/
• :.00pe,tu 04no nofn co%'S ono'.a c0'ro30n.^4133.9.S.0;rS
• P9toe IaO er'ero'cans Sono p nta'coca o steno,09,t's tetach
500 no,•s sal sons,;rotation
•
s t
. _. �<..
• ..0.ropcoe'we+ 'g,�.ptos115F 45C•and do.ento25. 4,_.
• S0—state control board 9n1 easy$P 49.4 t ,rn.na 00$'P
• Refnge'antft a^d'4'and.cc "i ato'on t$cn ra'^aa'ent ercve
• FJ'/lnsa'ated C40.n41
• Auto^1at.cnanaaove ,ane us4d.von$oto cnanp4ove me'nnostat
50TCQunits are high-efficiency single-packaged heat pumpunits • Raudnsoca rdance ,tn4-RE Stan 10,ds240;04-05 saes,and
that are pre-wired and pre-charged withPURON(HFC; 343.0-•14;
refrigerant.Electric heat is available as afield-installed accessory. • ces.a^ap.i actoroanta.an ^jer,;v;g s -goo$:0,esS:9105"0 7995
The units are fully factory tested and agency certified. • :'stai P, an;t.'- Canada
MAINTENANCE FEATURES:
• 4ccsspanasAli,eas/VT/haa044
• 'n0v11:st,easy St9Tna,'0 Str,O WOO.faatu'as 0^..':9cCISs oa^,els.
• -,v0-^t^d,sccr404 tu" $P'',tars
• '.00-4ssf.14,SCc433 door
ISHRIE � • 3f 7n':se ten,to- $^^l0:0'i Op",e,con-4 na.,o's$t8=,'ad4 o^9--'
3:;:113:0'latt anj appsC$t0'
• E4c'icv a x13 5 sotto.o'a a ^woo'on 04 ,o oa'woe s
• ,.e^.ra tt'^1na owl;$c.t$Lna Snw4 seat,c" t'0 4sn.00trt^.a
COMIPLI*NT', and S^7p:.ep rontro'.poxar$ngt'xn:
INSTALLATION FEATURES:
• `!1ti•I±:S•oott0n100htr8nt y cao90+-'.;st$'P$'d
• 5na 4 ooin:e4r.n:connectLas
A • =,.J ciannnete'oast'9 t.tn0.��t^
• -:aa lo.a apapta'S 910 :: ,�
ot�;S:e19
A.a GE Rt II lEO.
RELIABILITY FEATURES:
•, • Scro:•.co-10%590'S At" nt4r $ :n.4bra■+.0,3,090 Prot•Ct'on,
• Ct0end$04 ^14 -a^1pe'EL't oef'0St0O$oono oac.
• 24-...o coc-c,,a oro sotto At^reS4t'.404
Cu$ • Pr”oana ,L o'.a:to 9 epo'a•o fan rata
• o.a",en.•ostd con dan54 na:o^S..tlpe^'Vnen.y'i 0'^_atto
pe$^nas
• -case:narge.4'442.O'Otett'0^ anon an•p'tss:'a sarcnas
STANDARD WARRANTY:
• 5•,es'44ctrc'eatars
Certified to ISO 9001 • 5-yea'conloresso'
• 1-.411,0425
1;19n,opt pra..:011,3":444'50 9r$.104
OPTIONS INCLUDE BUT ARE NOT LIMITED TO:
• rot000 RTL Co." a0 .•'i4'..'t 2,'ettD•:}:9'C0ntro
• !;on•fosedd-9unneas:ac'
• ECOnon1sa'po:0ns'pr44ct'o-^1et'1^cs.a^d:20 co^I'o
• CO''501,es.5t9nt Co-oOCOns'0'*,000'$t0'$'0 c0n34'S4'
• r:0t0^11't1P00''$n'loto'sfo'*x09ndej a%41o,1 caoao',,.tj
• 4CCI550n,e4Ct'A Rest fie:d-+natl.40 opt0'0','
• S'lokt o0tector5-Su0o,ri Re:.'"a:'
• ^.ge0$ Ca3Spa'e'S
Packaged Rooftop Builder 1.49i Page 11 of 12
•
Spec Sheet for 10T PHP
Project: Mattress Firm 10T 08/21/2018
Prepared By: 03:52PM
Packaged Rooftop Builder 1.49i Page 12 of 12
ir
0.101.1011.0 NO TOUINIVRIMMIN ANWI1.1•1110 REVISIONS
REV. DESCRIPTION DATE APPROVED
Attn: Tag: 1 RUAL DRAWING 9/22/06
-- 171N78^ 2 CHANGED HEIGHT TO 16" 2/10/10 MING
Approval:
MIL
SUPPLY AIR
,,
I RETURN AIR
39 1'411
38
114 - UNCOVER O EXISTING CURB LAYOUT i�
•
,L_ 551/2
Imo--41 15/14"
...-
77"77^
SUPPLY
I
} 921/4"
81 314` I +RETURN 16114" 59 7118"
Jt S
/ 39 1d" 21/d"��L 21/1" 10
I/ I ! 11
57" I 78 1?' I
L3`
MA MEAR16J6.1 emcee wT6 ..s 1-3595-4005
CURB SHOWN IS CDI STANDARD CONFIGURATION 33259 n4A.,NNoa
Note: CDI RESERVES THE RIGHT TO CHANGE LAYOUT
1.1.5"ADDED TO OLD CURB 0.0 norm— INweea.r.P.w.r.1o.2m01:ao/Pr,i.....QUOTE#:
2.MATERIAL:18 pa GALVANIZED STEEL WITHOUT NOTIFICATION.IF CURB IS NEEDED INA RMu,.,�,y1y y1R1� la Wim,,,
3.GASKET PROVIDED WITH CURB DIFFERENT CONFIGURATION CDI MUST BE NOTIFIED VI".Ar,= "TUR 001. A"r ei,K°10RrvEn.RTYLERN GSM t�5py.gpDS `
4.INSULATION 1"1 V2 LB DENSITY PRIOR TO PLACING AN ORDER. %ALL WITH If Q7 9/O.6 MIN .;�_CDI gra -. -400 earn 1 e 9
RECEIVED PERMIT APPLICATION
CITY OF
Federal Way OCT 10 2018 PERMIT CENTER+33325 8th Avenue South+Federal Way,WA 98003-6325
253-835-2607+FAX 253-835-2609+pennitcenter Icityoffederalway.com
CITY OF FEDERAL WAY
COMMUNITY DEVEL.1_61OPMENT
PERMIT NUMBER ` _ j 7 9 _
v TARGET DATE
SITE ADDRESS SUITE/UNIT 9
31610 Pacific Hwy S (Mattress Firm)
PROJECT VALUATION ZONING ASSESSOR'S TAX/PARCEL�f
19,000 CC-C _L A_ - 2
TYPE OF PERMIT 0 BUILDING 0 PLUMBING iXMECHANICAL 0 DEMOLITION 0 ENGINEERING 0 FIRE PREVENTION
NAME OF PROJECT Mattress Firm roof top unit replacement
PROJECT DESCRIPTION Replace existing 10 ton roof top unit with new 10 ton roof top
Detailed description of work to
be included on this permit only
NAME PRIMARY PHONE
PROPERTY OWNER INQADDi PrjPral Way, LTE RESS E-MAIL
CITY STATE ZIP
NAME PHONE
New Castle Mechanical 253-503-7390
MAILING ADDRESS E-MAIL
CONTRACTOR 9823 160th St E Suite A stephanie.newcastle@comcast.net
CITY STATE ZIP FAX
Puyallup WA 98375
WA STATE CONTRACTOR'S LICENSE i EXPIRATION DATE FEDERAL WAY BUSINESS LICENSE M
NEWCACM924OD 10i 7 / 18 20-13-101510-00-BL
NAME k PRIMARY PHONE
Stephanie Givens 253-686-6061
APPLICANT MAILING ADDRESS E-MAILE-MA
9823 160th St E Suite A Stephanie.newcastlefgcomcast.ne;
CITY STATE ZIP FAX
Puyallup W4 98375
NAME PRIMARY PHONE
PROJECT CONTACT see above
(The individual to receive and MAILING ADDRESS E-MAIL
respond to all correspondence
concerning this application) emir STATE ZIP FAX
PROJECT FINANCING NAME EX OWNER-FINANCED
When value is$5,000 or more MAILING ADDRESS,CITY,STATE,ZIP PHONE
(RCW 19.27.095)
I certify under penalty of perjury that I am the property owner or authorised agent of the property owner.I certify that to the best
of my knowledge, the information submitted in support of this permit application is true and correct.I certify that I will comply with
all applicable City of Federal Way regulations pertaining to the work authorised by the issuance of a permit. I understand that the
issuance of this permit does not remove the owner's responsibility for compliance with local, state, or federal laws regulating
construction or environmental laws.
I further agree to hold harmless the City of Federal Way as to any claim(including costs,expensesand attorneys'fees incurred in
the investigation and defense of such claim),which may be made by any person,including the undersigned,and flied against the city,
but only where such claim arises out of the reliance of the city, including its officers and employees, upon the accuracy of the
information supplied to t city as a part of this applic tion.
SIGNATURE: G GG �I/Ki DATE
/ �/�/
1
PRINT NAME: Stephanie Givens
Bulletin#100—January 29,2016 Page 1 of 2 k:\Handouts\Permit Application
VALUE OF MECHANICAL WORK
MECHANICAL PERMIT $ 19,000
Indicate how many of each tape of facture to be installed or relocated as part of this project.Do not include existing factures to remain.
AIR HANDLING UNITS FANS GAS PIPE OUTLETS OTHER(Describe)
1 AIR CONDITIONER FIREPLACE INSERTS HOODS(Commercial)
BOILERS FURNACES HOT WATER TANKS(Gaa)
COMPRESSORS GAS LOG SETS REFRIGERATION SYST
DUCTING GAS PIPING WOODSTOVES
VALUE OF PLUMBING WORK
PLUMBING PERMIT
Indicate how many of each type of fixture to be installed or relocated as part of this project.Do not include existingfxtu•-s to remain.
BATHTUBS(or Tub/Shower Combo) LAVS(Hand Sinks) TOILETS WA • PIPING
DISHWASHERS RAINWATER SYSTEMS URINALS P HER(Describe)
DRAINS SHOWERS VACUUM BREAKERS
DRINKING FOUNTAINS SINKS(Kitchen/Utility) WATER HEATERS(Electric)
HOSE BIBBS SUMPS WASHING MACHINES TOTAL FIXTURES
GENERAL INFORMATION
CRITICAL AREAS ON PROPERTY? WATER PURVEYOR SEWER PURVEYOR VALUE OF EXISTING IMPROVEMENTS
EXISTING/PREVIOUS USE LOT SIZE Da Square Feet) EXISTING FIRE SPRINKLE- SYSTEM? PROPOSED FIRE SUPPRESSION SYSTEM?
a Yes ❑ 'o ❑Yes ❑ No
RESIDENTIAL - NEW OR ADDITION
AREA DESCRIPTION(in square feet) EXISTING PROPOS TOTAL FOR OFFICE USE
BASEMENT
FIRST FLOOR(or Mobile Home)
SECOND FLOOR
COVERED ENTRY
DECK
GARAGE 0 CARPORT 0OTHER(describe)
Area Totals EXISTING PROPOSED TOTAL
NEW HOMES ONLY" -
ESTIMATED SELLING PRIC #OF BEDROOMS
COMMERCIAL-.''EW/ADDITION
AREA DESCRI- •N Area Occupancy Group(s) Construction #of Additional Information
Square FeetType Stories
NEW : $ •ma
• •ITION
COM RCIAL-REMODEL/TENANT IMPROVEMENTS
- DESCRIPTION Area OccupancyGroup(s) Construction #of Additional Information
Square Feet 1 Type Stories
AL BUILDING
TENANT AREA ONLY
PROJECT AREA ONLY
Bulletin#100—January 29,2016 Page 2 of 2 k:\Handouts\Permit Application