20-101386-Elevations Plans-04-09-2020-V1ABCDEFGH370'-0"50'-0"50'-0"60'-0"50'-0"50'-0"50'-0"60'-0"4'-0"4'-0"2'-6"EQ.EQ.EQ.EQ.2'-6"EQ.2'-6"EQ.2'-6"EQ.EQ.4'-0"2'-0"2'-6"EQ.EQ.EQ.EQ.3'-0"EQ.2'-6"EQ.2'-6 1/4"EQ.EQ.2'-6"EQ.EQ.4'-0"EQ.EQ.2'-6"AB50'-0"ABCDEFGH370'-0"50'-0"50'-0"60'-0"50'-0"50'-0"50'-0"60'-0"2'-6"EQ.EQ.4'-0"EQ.EQ.2'-6"4'-0"4'-0"2'-6"EQ.EQ.EQ.EQ.2'-6"EQ.2'-6"EQ.2'-6"EQ.EQ.4'-0"4'-0"2'-6"EQ.EQ.EQ.EQ.2'-6"EQ.2'-6"EQ.2'-6"EQ.EQ.1/16" = 1'-0"NORTH ELEVATION1Nelco Architecture, Inc.Phone:Suite 1300Seattle, WA 98101(206) 408-85001200 Fifth Ave.WWW.NELSONWORLDWIDE.COM Proj. No:Reviewed By:SEAL:CITY STAMP:IRGMS/PM IRG GREENLINEBUILDING AWEYERHAEUSER WAYS SFEDERAL WAY, WA 98001CR.00180070.000 CLIENT:PROJECT:11111 SANTA MONICA BLVD.SUITE 800LOS ANGELES, CA 90025Date:No:Description:Permit Submittal02/05/2020Nelco Architecture, Inc.Phone:Suite 1300Seattle, WA 98101(206) 408-85001200 Fifth Ave.WWW.NELSONWORLDWIDE.COM Proj. No:Reviewed By:SEAL:CITY STAMP:IRGMS/PM IRG GREENLINEBUILDING AWEYERHAEUSER WAYS SFEDERAL WAY, WA 98001CR.00180070.000 CLIENT:PROJECT:11111 SANTA MONICA BLVD.SUITE 800LOS ANGELES, CA 90025Date:No:Description:Permit Submittal02/05/2020GENERAL NOTES:KEY NOTES:1.IG INDICATES INSULATED GLAZING, TYP.2.TG INDICATES TEMPERED GLAZING, TYP.3.TIG INDICATES TEMPERED, INSULATED GLAZING, TYP.4.ALL FIXED INSULATED GLAZING SHALL BE CERTIFIED & LABELED WITH ITS MAX.U-FACTOR OF & SOLAR HEAT GAIN COEFFICIENT BY AN INDEPENDENT AGENCYLICENSED BY THE NFRC, IN COMPLIANCE WITH THE VALUES LISTED ON SHEET CS.5.PJ = PANEL JOINT6.PROVIDE AND COORDINATE "KNOXBOX: LOCATION WITH FIRE DEPARTMENT ANDARCHITECT PRIOR TO INSTALL7.ALL VERTICAL DIMENSIONS ARE FROM FINISHED FLOOR, U.N.O.8.CHANGE IN PAINT COLOR OCCURS AT BACK OF REVEAL, TYP. U.N.O.PAINT LEGEND:1.TILT UP CONCRETE PANEL (PAINT FINISH), TYP.2.PANEL REVEAL, TYP. SEE DETAILS 3/A8.1 AND 4/A8.13.PHENOLIC RESIN PANEL, SIMULATED WOOD GRAIN TEXTURE, ORER 1.5" HATCHANNEL APPLIED TO CONCRETE PANEL; COLOR MIX TBD.4.ANODIZED ALUMINUM STOREFRONT SYSTEM, COLOR: TBD, TYP.5.ALUMINUM DOOR TO MATCH STOREFRONT SYSTEM, TYP. SEE DOORSCHEDULE6.HOLLOW METAL DOOR & FRAME, TYP., PAINT TO MATCH EXISTINGADJACENT WALLS7.LINE OF ROOF BEYOND8.EXTERIOR "WALL PACK" WALL MOUNTED LIGHT FIXTURE, TYP.9.EXTERIOR "SHOE BOX" WALL MOUNTED LIGHT FIXTURE, TYP.10.SURFACE MOUNTED EMERGENCY LIGHT FIXTURE AT EXIT DOOR, TYP.11.PRE-FINISHED METAL COPING, COLOR: TBD12.NOT USED13.PRE-FINISHED METAL CANOPY, COLOR: TBD14.NOT USED15.PRE-FINISHED CONTINUOUS METAL GUTTER: COLOR: TBD WITH PVCDOWNSPOUTS PAINTED PER LEGEND ALONG DOCK ELEVATION. TIGHT-LINE16.NOT USED17.PRE-FINISHED METAL SCUPPER: COLOR: TBD & PAINTED PVC DOWNSPOUTPER LEGEND, SEE DETAIL 11/A8.1, TYP. TIGHT-LINE DOWNSPOUT TO STORMLINE, REFER TO CIVIL DRAWINGS. PROVIDE DOWNSPOUT PROTECTORS ATTRUCK COURT LOCATIONS ONLY, SEE DETAIL 8/A8.118.NOT USED19.SECTIONAL OVERHEAD DRIVE-IN DOOR (INSULATED), PRE-FINISHED,COLOR: TBD, TYP.20.NOT USED21.SECTIONAL OVERHEAD DOCK HIGH DOOR (INSULATED) WITH BUMPERS ANDDOCK SEAL, PRE-FINISHED, COLOR: TBD, TYP.22.NOT USED23.PRE-FAB METAL STAIR AT TRUCK COURT, SEE SITE PLAN24.FOOTINGS PER STRUCTURAL25.FUTURE KNOCK-OUT, PER STRUCTURAL, TYP.26.XX" STEEL CHANNEL, PAINT PER LEGEND27.STEEL TRELLIS, PAINT PER LEGEND28.CONCRETE TILT UP RETAINING WALL, SEE SITE PLAN29.BUILDING ADDRESS: 24" HIGH X 14" THICK DIMENSIONAL NUMBERS. FONT:TREBUCHET MS BOLD, ITALIC. COLOR: TBD30.DAYLIGHT OVERFLOW DOWNSPOUT AT 1'-0" ABOVE FINISH FLOOR WITH"COW TONGUE" DOWNSPOUT NOZZLE.PAINT - PT2TBDPAINT - PT1TBDPAINT - PT3TBDXPAINT - PT4TBDDPJT.O. FINISHED FLOOR0'-0"T.O. PARAPET38'-0"PJHAABOPP.PJT.O. FINISHED FLOOR0'-0"T.O. WINDOW HEAD23'-0"T.O. PARAPET38'-0"18TYP.PJPJPJPJPJPJPJPJPJBOPP.AAOPP.HOPP.18TYP.T.O. FINISHED FLOOR0'-0"T.O. WINDOW HEAD23'-0"T.O. PARAPET38'-0"PJPJPJPJPJPJPJPJPJPJPJHA3.5111222444444441061061111116688899TIGTIGTIGTIGTIGTIGTIGTIGTIGTIGTIGTIG3TYP.3TYP.448883030EXTERIOR ELEVATIONSA3.11/16"=1'-0"NORTH ELEVATION1A3.11/16"=1'-0"SOUTH ELEVATION2A3.11/16"=1'-0"SOUTH NODE ELEVATION3A3.1
1123465789101112131415685'-0"50'-0"50'-0"50'-0"50'-0"50'-0"50'-0"42'-6"50'-0"50'-0"50'-0"50'-0"50'-0"50'-0"42'-6"1011121314156578910685'-0"11234515'-2"EQ.EQ.5'-0"EQ.EQ.15'-1"2'-6"EQ.EQ.15'-1 3/4"3'-9 1/2"EQ.EQ.13'-10 1/2"13'-10 1/2"EQ.EQ.3'-8 1/2"50'-0"50'-0"50'-0"50'-0"50'-0"2'-6"EQ.EQ.15'-1"4'-0"4'-0"3'-9 1/2"EQ.EQ.EQ.EQ.2'-6"EQ.3'-8 3/4"EQ.2'-6"EQ.EQ.50'-0"50'-0"50'-0"50'-0"42'-6"3'-9 1/2"EQ.EQ.4'-0"EQ.EQ.2'-6"2'-6"EQ.EQ.4'-0"EQ.EQ.3'-8 1/2"50'-0"50'-0"50'-0"42'-6"Nelco Architecture, Inc.Phone:Suite 1300Seattle, WA 98101(206) 408-85001200 Fifth Ave.WWW.NELSONWORLDWIDE.COM Proj. No:Reviewed By:SEAL:CITY STAMP:IRGMS/PM IRG GREENLINEBUILDING AWEYERHAEUSER WAYS SFEDERAL WAY, WA 98001CR.00180070.000 CLIENT:PROJECT:11111 SANTA MONICA BLVD.SUITE 800LOS ANGELES, CA 90025Date:No:Description:Permit Submittal02/05/2020Nelco Architecture, Inc.Phone:Suite 1300Seattle, WA 98101(206) 408-85001200 Fifth Ave.WWW.NELSONWORLDWIDE.COM Proj. No:Reviewed By:SEAL:CITY STAMP:IRGMS/PM IRG GREENLINEBUILDING AWEYERHAEUSER WAYS SFEDERAL WAY, WA 98001CR.00180070.000 CLIENT:PROJECT:11111 SANTA MONICA BLVD.SUITE 800LOS ANGELES, CA 90025Date:No:Description:Permit Submittal02/05/2020GENERAL NOTES:KEY NOTES:1.IG INDICATES INSULATED GLAZING, TYP.2.TG INDICATES TEMPERED GLAZING, TYP.3.TIG INDICATES TEMPERED, INSULATED GLAZING, TYP.4.ALL FIXED INSULATED GLAZING SHALL BE CERTIFIED & LABELED WITH ITS MAX.U-FACTOR OF & SOLAR HEAT GAIN COEFFICIENT BY AN INDEPENDENT AGENCYLICENSED BY THE NFRC, IN COMPLIANCE WITH THE VALUES LISTED ON SHEET CS.5.PJ = PANEL JOINT6.PROVIDE AND COORDINATE "KNOXBOX: LOCATION WITH FIRE DEPARTMENT ANDARCHITECT PRIOR TO INSTALL7.ALL VERTICAL DIMENSIONS ARE FROM FINISHED FLOOR, U.N.O.8.CHANGE IN PAINT COLOR OCCURS AT BACK OF REVEAL, TYP. U.N.O.PAINT LEGEND:1.TILT UP CONCRETE PANEL (PAINT FINISH), TYP.2.PANEL REVEAL, TYP. SEE DETAILS 3/A8.1 AND 4/A8.13.PHENOLIC RESIN PANEL, SIMULATED WOOD GRAIN TEXTURE, ORER 1.5" HATCHANNEL APPLIED TO CONCRETE PANEL; COLOR MIX TBD.4.ANODIZED ALUMINUM STOREFRONT SYSTEM, COLOR: TBD, TYP.5.ALUMINUM DOOR TO MATCH STOREFRONT SYSTEM, TYP. SEE DOORSCHEDULE6.HOLLOW METAL DOOR & FRAME, TYP., PAINT TO MATCH EXISTINGADJACENT WALLS7.LINE OF ROOF BEYOND8.EXTERIOR "WALL PACK" WALL MOUNTED LIGHT FIXTURE, TYP.9.EXTERIOR "SHOE BOX" WALL MOUNTED LIGHT FIXTURE, TYP.10.SURFACE MOUNTED EMERGENCY LIGHT FIXTURE AT EXIT DOOR, TYP.11.PRE-FINISHED METAL COPING, COLOR: TBD12.NOT USED13.PRE-FINISHED METAL CANOPY, COLOR: TBD14.NOT USED15.PRE-FINISHED CONTINUOUS METAL GUTTER: COLOR: TBD WITH PVCDOWNSPOUTS PAINTED PER LEGEND ALONG DOCK ELEVATION. TIGHT-LINE16.NOT USED17.PRE-FINISHED METAL SCUPPER: COLOR: TBD & PAINTED PVC DOWNSPOUTPER LEGEND, SEE DETAIL 11/A8.1, TYP. TIGHT-LINE DOWNSPOUT TO STORMLINE, REFER TO CIVIL DRAWINGS. PROVIDE DOWNSPOUT PROTECTORS ATTRUCK COURT LOCATIONS ONLY, SEE DETAIL 8/A8.118.NOT USED19.SECTIONAL OVERHEAD DRIVE-IN DOOR (INSULATED), PRE-FINISHED,COLOR: TBD, TYP.20.NOT USED21.SECTIONAL OVERHEAD DOCK HIGH DOOR (INSULATED) WITH BUMPERS ANDDOCK SEAL, PRE-FINISHED, COLOR: TBD, TYP.22.NOT USED23.PRE-FAB METAL STAIR AT TRUCK COURT, SEE SITE PLAN24.FOOTINGS PER STRUCTURAL25.FUTURE KNOCK-OUT, PER STRUCTURAL, TYP.26.XX" STEEL CHANNEL, PAINT PER LEGEND27.STEEL TRELLIS, PAINT PER LEGEND28.CONCRETE TILT UP RETAINING WALL, SEE SITE PLAN29.BUILDING ADDRESS: 24" HIGH X 14" THICK DIMENSIONAL NUMBERS. FONT:TREBUCHET MS BOLD, ITALIC. COLOR: TBD30.DAYLIGHT OVERFLOW DOWNSPOUT AT 1'-0" ABOVE FINISH FLOOR WITH"COW TONGUE" DOWNSPOUT NOZZLE.PAINT - PT2TBDPAINT - PT1TBDPAINT - PT3TBDXPAINT - PT4TBDGACECAGOPP.OPP.OPP.PJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJT.O. FINISHED FLOOR0'-0"T.O. WINDOW HEAD23'-0"T.O. PARAPET38'-0"18TYP.MATCH LINEMATCH LINE
MATCH LINEMATCH LINE
PJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJ4A3.22A3.23A3.2GA3.51112224444444411111152588888899TIGTIGTIGTIGTIGTIGTIGTIGTIGTIGTIGTIG3TYP.3TYP.3TYP.303030303030303030303030ENLARGED EXTERIORELEVATIONSA3.21/32"=1'-0"WEST ELEVATION1A3.21/16"=1'-0"PARTIAL WEST ELEVATION2A3.21/16"=1'-0"PARTIAL WEST ELEVATION3A3.21/16"=1'-0"PARTIAL WEST ELEVATION4A3.2TIGTIGTIGTIGTIGTIGTIGTIGTIGTIGTIGTIGTIGTIGTIGTIG
1123465789101112131415685'-0"50'-0"50'-0"50'-0"50'-0"50'-0"50'-0"42'-6"50'-0"50'-0"50'-0"50'-0"50'-0"50'-0"42'-6"112346550'-0"50'-0"50'-0"50'-0"42'-6"67891011685'-0"50'-0"50'-0"50'-0"50'-0"50'-0"111213141550'-0"50'-0"50'-0"42'-6"Nelco Architecture, Inc.Phone:Suite 1300Seattle, WA 98101(206) 408-85001200 Fifth Ave.WWW.NELSONWORLDWIDE.COM Proj. No:Reviewed By:SEAL:CITY STAMP:IRGMS/PM IRG GREENLINEBUILDING AWEYERHAEUSER WAYS SFEDERAL WAY, WA 98001CR.00180070.000 CLIENT:PROJECT:11111 SANTA MONICA BLVD.SUITE 800LOS ANGELES, CA 90025Date:No:Description:Permit Submittal02/05/2020Nelco Architecture, Inc.Phone:Suite 1300Seattle, WA 98101(206) 408-85001200 Fifth Ave.WWW.NELSONWORLDWIDE.COM Proj. No:Reviewed By:SEAL:CITY STAMP:IRGMS/PM IRG GREENLINEBUILDING AWEYERHAEUSER WAYS SFEDERAL WAY, WA 98001CR.00180070.000 CLIENT:PROJECT:11111 SANTA MONICA BLVD.SUITE 800LOS ANGELES, CA 90025Date:No:Description:Permit Submittal02/05/2020GENERAL NOTES:KEY NOTES:1.IG INDICATES INSULATED GLAZING, TYP.2.TG INDICATES TEMPERED GLAZING, TYP.3.TIG INDICATES TEMPERED, INSULATED GLAZING, TYP.4.ALL FIXED INSULATED GLAZING SHALL BE CERTIFIED & LABELED WITH ITS MAX.U-FACTOR OF & SOLAR HEAT GAIN COEFFICIENT BY AN INDEPENDENT AGENCYLICENSED BY THE NFRC, IN COMPLIANCE WITH THE VALUES LISTED ON SHEET CS.5.PJ = PANEL JOINT6.PROVIDE AND COORDINATE "KNOXBOX: LOCATION WITH FIRE DEPARTMENT ANDARCHITECT PRIOR TO INSTALL7.ALL VERTICAL DIMENSIONS ARE FROM FINISHED FLOOR, U.N.O.8.CHANGE IN PAINT COLOR OCCURS AT BACK OF REVEAL, TYP. U.N.O.PAINT LEGEND:1.TILT UP CONCRETE PANEL (PAINT FINISH), TYP.2.PANEL REVEAL, TYP. SEE DETAILS 3/A8.1 AND 4/A8.13.PHENOLIC RESIN PANEL, SIMULATED WOOD GRAIN TEXTURE, ORER 1.5" HATCHANNEL APPLIED TO CONCRETE PANEL; COLOR MIX TBD.4.ANODIZED ALUMINUM STOREFRONT SYSTEM, COLOR: TBD, TYP.5.ALUMINUM DOOR TO MATCH STOREFRONT SYSTEM, TYP. SEE DOORSCHEDULE6.HOLLOW METAL DOOR & FRAME, TYP., PAINT TO MATCH EXISTINGADJACENT WALLS7.LINE OF ROOF BEYOND8.EXTERIOR "WALL PACK" WALL MOUNTED LIGHT FIXTURE, TYP.9.EXTERIOR "SHOE BOX" WALL MOUNTED LIGHT FIXTURE, TYP.10.SURFACE MOUNTED EMERGENCY LIGHT FIXTURE AT EXIT DOOR, TYP.11.PRE-FINISHED METAL COPING, COLOR: TBD12.NOT USED13.PRE-FINISHED METAL CANOPY, COLOR: TBD14.NOT USED15.PRE-FINISHED CONTINUOUS METAL GUTTER: COLOR: TBD WITH PVCDOWNSPOUTS PAINTED PER LEGEND ALONG DOCK ELEVATION. TIGHT-LINE16.NOT USED17.PRE-FINISHED METAL SCUPPER: COLOR: TBD & PAINTED PVC DOWNSPOUTPER LEGEND, SEE DETAIL 11/A8.1, TYP. TIGHT-LINE DOWNSPOUT TO STORMLINE, REFER TO CIVIL DRAWINGS. PROVIDE DOWNSPOUT PROTECTORS ATTRUCK COURT LOCATIONS ONLY, SEE DETAIL 8/A8.118.NOT USED19.SECTIONAL OVERHEAD DRIVE-IN DOOR (INSULATED), PRE-FINISHED,COLOR: TBD, TYP.20.NOT USED21.SECTIONAL OVERHEAD DOCK HIGH DOOR (INSULATED) WITH BUMPERS ANDDOCK SEAL, PRE-FINISHED, COLOR: TBD, TYP.22.NOT USED23.PRE-FAB METAL STAIR AT TRUCK COURT, SEE SITE PLAN24.FOOTINGS PER STRUCTURAL25.FUTURE KNOCK-OUT, PER STRUCTURAL, TYP.26.XX" STEEL CHANNEL, PAINT PER LEGEND27.STEEL TRELLIS, PAINT PER LEGEND28.CONCRETE TILT UP RETAINING WALL, SEE SITE PLAN29.BUILDING ADDRESS: 24" HIGH X 14" THICK DIMENSIONAL NUMBERS. FONT:TREBUCHET MS BOLD, ITALIC. COLOR: TBD30.DAYLIGHT OVERFLOW DOWNSPOUT AT 1'-0" ABOVE FINISH FLOOR WITH"COW TONGUE" DOWNSPOUT NOZZLE.PAINT - PT2TBDPAINT - PT1TBDPAINT - PT3TBDXPAINT - PT4TBDFJKLMJKLMJKLNOPMLOPP.OPP.JKMOPP.OPP.OPP.NOPFOPP.PJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJT.O. FINISHED FLOOR0'-0"T.O. PARAPET38'-0"T.O. PARAPET32'-0"TRUCK COURT-4'-0"MATCH LINEMATCH LINE
MATCH LINEMATCH LINE
PJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJPJ4A3.33A3.32A3.3111122210610610619192121212232323111111888888881717173ENLARGED EXTERIORELEVATIONSA3.31/32"=1'-0"EAST ELEVATION1A3.31/16"=1'-0"PARTIAL EAST ELEVATION2A3.31/16"=1'-0"PARTIAL EAST ELEVATION3A3.31/16"=1'-0"PARTIAL EAST ELEVATION4A3.3
45°60°45°95°45°46°46°2'-5 1/2"8'-7 1/2"10'-4 1/2"5'-1 1/2"14'-1"2'-11"13'-0"8'-0"1'-0"21'-0"30'-0"
9'-0"
22'-0"
15'-0"4'-10 1/2"17'-10 1/2"35'-1"33'-0"105°45°35'-1 1/2"22'-11"1'-1"49°46°32'-5 1/2"
26'-11 1/2"84°92°90°95°120°55°45°6
0
°35°8'-3 1/2"TYP.18'-8"TYP.50°50°
16'-0"
TYP.
7'-0"
TYP.
13'-0"
TYP.
120
°13'-0"TYP.18'-7"
TYP.
11'-0"
TYP.
16'-0"
TYP.
8'-0"
TYP.120°6
0
°95°34'-4 1/2"
TYP.
34'-9 1/2"
TYP.60°130°128
°
121
°50°120
°50°7'-8"TYP.10'-2 1/2"TYP.15'-3"TYP.13'-0"
TYP.
7'-0"
TYP.
16'-0"
TYP.
9'-0"
TYP.
15'-0"
TYP.3'-0"
9'-0"
TYP.
18'-0"
TYP.115°110°100°49°49°29'-3 1/2"
TYP.
23'-11 7/8"
TYP.
11'-6 1/2"
TYP.45°45°46°116°45°48°45°95°44°46°46°8'-4 1/2"3'-0"16'-10"10'-4 1/2"5'-1 1/2"5'-10 1/2"11'-0"20'-3"7'-10"30'-0"4 1/2"15'-1"10'-2"
22'-0"105°95°90°84°92°50°16'-10 1/2"21'-0"35'-1"33'-0"35'-1 1/2"22'-11"2'-3 1/2"45°32'-5 1/2"
26'-11 1/2"45°95°46°45°45°50°120°135°135°45°46°10'-4 1/2"6'-11 1/2"3'-0"22'-0"15'-1"10'-3"
7'-8 1/2"20'-3 1/2"
10'-0"11'-0"10'-7 1/2"4 1/2"11'-0"8'-5 1/2"8'-1 1/2"92°84°44°50°105°95°90°46°26'-11 1/2"32'-5 1/2"35'-1 1/2"28'-6"1'-5 1/2"30'-0"33'-0"
35'-1 1/2"
16'-10 1/2"5'-10 1/2"95°130°
6
0
°45°45°45°46°46°44°8'-1 1/2"3'-0"14'-1"9'-0"15'-0"9'-4"33'-0"
21'-0"6'-0"1'-0"4'-10 1/2"13'-0"8'-0"1'-6"35'-1 1/2"
28'-10 1/2"45°105°6
0
°95°35'-1"
17'-10 1/2"90°Nelco Architecture, Inc.Phone:Suite 1300Seattle, WA 98101(206) 408-85001200 Fifth Ave.WWW.NELSONWORLDWIDE.COM Proj. No:Reviewed By:SEAL:CITY STAMP:IRGMS/PM IRG GREENLINEBUILDING AWEYERHAEUSER WAYS SFEDERAL WAY, WA 98001CR.00180070.000 CLIENT:PROJECT:11111 SANTA MONICA BLVD.SUITE 800LOS ANGELES, CA 90025Date:No:Description:Permit Submittal02/05/2020Nelco Architecture, Inc.Phone:Suite 1300Seattle, WA 98101(206) 408-85001200 Fifth Ave.WWW.NELSONWORLDWIDE.COM Proj. No:Reviewed By:SEAL:CITY STAMP:IRGMS/PM IRG GREENLINEBUILDING AWEYERHAEUSER WAYS SFEDERAL WAY, WA 98001CR.00180070.000 CLIENT:PROJECT:11111 SANTA MONICA BLVD.SUITE 800LOS ANGELES, CA 90025Date:No:Description:Permit Submittal02/05/2020Nelco Architecture, Inc.Phone:Suite 1300Seattle, WA 98101(206) 408-85001200 Fifth Ave.WWW.NELSONWORLDWIDE.COM Proj. No:Reviewed By:SEAL:CITY STAMP:IRGMS/PM IRG GREENLINEBUILDING AWEYERHAEUSER WAYS SFEDERAL WAY, WA 98001CR.00180070.000 CLIENT:PROJECT:11111 SANTA MONICA BLVD.SUITE 800LOS ANGELES, CA 90025Date:No:Description:Permit Submittal02/05/2020Nelco Architecture, Inc.Phone:Suite 1300Seattle, WA 98101(206) 408-85001200 Fifth Ave.WWW.NELSONWORLDWIDE.COM Proj. No:Reviewed By:SEAL:CITY STAMP:IRGMS/PM IRG GREENLINEBUILDING AWEYERHAEUSER WAYS SFEDERAL WAY, WA 98001CR.00180070.000 CLIENT:PROJECT:11111 SANTA MONICA BLVD.SUITE 800LOS ANGELES, CA 90025Date:No:Description:Permit Submittal02/05/2020GENERAL NOTES:1.IG INDICATES INSULATED GLAZING, TYP.2.TG INDICATES TEMPERED GLAZING, TYP.3.TIG INDICATES TEMPERED, INSULATED GLAZING, TYP.4.ALL FIXED INSULATED GLAZING SHALL BE CERTIFIED & LABELED WITH ITS MAX.U-FACTOR OF & SOLAR HEAT GAIN COEFFICIENT BY AN INDEPENDENT AGENCYLICENSED BY THE NFRC, IN COMPLIANCE WITH THE VALUES LISTED ON SHEET CS.5.PJ = PANEL JOINT6.PROVIDE AND COORDINATE "KNOXBOX: LOCATION WITH FIRE DEPARTMENT ANDARCHITECT PRIOR TO INSTALL7.ALL VERTICAL DIMENSIONS ARE FROM FINISHED FLOOR, U.N.O.8.CHANGE IN PAINT COLOR OCCURS AT BACK OF REVEAL, TYP. U.N.O.APANELBPANELCPANELEPANELDPANELFPANELPJPJPJPJ FLOOR LINE+/-0'-0" FLOOR LINE+/-0'-0" FLOOR LINE+/-0'-0"KEY NOTES:1.TILT UP CONCRETE PANEL (PAINT FINISH), TYP.2.PANEL REVEAL, TYP. SEE DETAILS 3/A8.1 AND 4/A8.13.PHENOLIC RESIN PANEL, SIMULATED WOOD GRAIN TEXTURE, ORER 1.5" HATCHANNEL APPLIED TO CONCRETE PANEL; COLOR MIX TBD.4.ANODIZED ALUMINUM STOREFRONT SYSTEM, COLOR: TBD, TYP.5.ALUMINUM DOOR TO MATCH STOREFRONT SYSTEM, TYP. SEE DOORSCHEDULE6.HOLLOW METAL DOOR & FRAME, TYP., PAINT TO MATCH EXISTINGADJACENT WALLS7.LINE OF ROOF BEYOND8.EXTERIOR "WALL PACK" WALL MOUNTED LIGHT FIXTURE, TYP.9.EXTERIOR "SHOE BOX" WALL MOUNTED LIGHT FIXTURE, TYP.10.SURFACE MOUNTED EMERGENCY LIGHT FIXTURE AT EXIT DOOR, TYP.11.PRE-FINISHED METAL COPING, COLOR: TBD12.NOT USED13.PRE-FINISHED METAL CANOPY, COLOR: TBD14.NOT USED15.PRE-FINISHED CONTINUOUS METAL GUTTER: COLOR: TBD WITH PVCDOWNSPOUTS PAINTED PER LEGEND ALONG DOCK ELEVATION. TIGHT-LINE16.NOT USED17.PRE-FINISHED METAL SCUPPER: COLOR: TBD & PAINTED PVC DOWNSPOUTPER LEGEND, SEE DETAIL 11/A8.1, TYP. TIGHT-LINE DOWNSPOUT TO STORMLINE, REFER TO CIVIL DRAWINGS. PROVIDE DOWNSPOUT PROTECTORS ATTRUCK COURT LOCATIONS ONLY, SEE DETAIL 8/A8.118.NOT USED19.SECTIONAL OVERHEAD DRIVE-IN DOOR (INSULATED), PRE-FINISHED,COLOR: TBD, TYP.20.NOT USED21.SECTIONAL OVERHEAD DOCK HIGH DOOR (INSULATED) WITH BUMPERS ANDDOCK SEAL, PRE-FINISHED, COLOR: TBD, TYP.22.NOT USED23.PRE-FAB METAL STAIR AT TRUCK COURT, SEE SITE PLAN24.FOOTINGS PER STRUCTURAL25.FUTURE KNOCK-OUT, PER STRUCTURAL, TYP.26.XX" STEEL CHANNEL, PAINT PER LEGEND27.STEEL TRELLIS, PAINT PER LEGEND28.CONCRETE TILT UP RETAINING WALL, SEE SITE PLAN29.BUILDING ADDRESS: 24" HIGH X 14" THICK DIMENSIONAL NUMBERS. FONT:TREBUCHET MS BOLD, ITALIC. COLOR: TBD30.DAYLIGHT OVERFLOW DOWNSPOUT AT 1'-0" ABOVE FINISH FLOOR WITH"COW TONGUE" DOWNSPOUT NOZZLE.XPJPJPJPJPJPJPJPJPJPJPJENLARGED EXTERIORELEVATIONSA3.41/8"=1'-0"PANEL ELEVATIONS1A3.4
60°45°60°35°55°50°50°60°50°6
0
°
22'-0"5'-0"9'-4"17'-11 1/2"9'-4 1/2"16'-0"7'-0"
27'-0"
8'-0"16'-0"35'-4"33'-4 1/2"36'-0"32'-5"95°120°111°60°130°120°35°55°45°120°45°50°50°110°60°9'-5"11'-0 1/2"9'-4"27'-2 1/2"
32'-3"
36'-0"
33'-4 1/2"
22'-0"
27'-0"
35'-4"
16'-0"
16'-0"8'-0"120°95°50°6
0
°
21'-0"50°57°120°60°21'-0"3'-1 1/2"12'-9 1/2"11'-0"
14'-0"
27'-4 1/2"
21'-10"1'-11"108°3'-3 1/2"57°120°92°45°60°57°
6
0
°15'-6 1/2"5'-1 1/2"18'-0"9'-0"5'-3"11'-0"14'-0"110°29'-6"
28'-4 1/2"100°80°65°50°7'-9"18'-0"9'-0"
20'-0"3'-0"
26'-6"110°50°50°18'-4"20'-0"3'-0"21'-0"80°28'-7"57°60°120°12'-10"9'-0 1/2"14'-0"11'-0"23'-9"27'-2 1/2"9'-6 1/2"21'-0"21'-10"18'-0"9'-0"130°130°67°78°18'-0"9'-0"3'-0"20'-0"17'-3"26'-6"100°130°130°3'-0"20'-0"130°50°110°50°50°6'-8"28'-7"Nelco Architecture, Inc.Phone:Suite 1300Seattle, WA 98101(206) 408-85001200 Fifth Ave.WWW.NELSONWORLDWIDE.COM Proj. No:Reviewed By:SEAL:CITY STAMP:IRGMS/PM IRG GREENLINEBUILDING AWEYERHAEUSER WAYS SFEDERAL WAY, WA 98001CR.00180070.000 CLIENT:PROJECT:11111 SANTA MONICA BLVD.SUITE 800LOS ANGELES, CA 90025Date:No:Description:Permit Submittal02/05/2020Nelco Architecture, Inc.Phone:Suite 1300Seattle, WA 98101(206) 408-85001200 Fifth Ave.WWW.NELSONWORLDWIDE.COM Proj. No:Reviewed By:SEAL:CITY STAMP:IRGMS/PM IRG GREENLINEBUILDING AWEYERHAEUSER WAYS SFEDERAL WAY, WA 98001CR.00180070.000 CLIENT:PROJECT:11111 SANTA MONICA BLVD.SUITE 800LOS ANGELES, CA 90025Date:No:Description:Permit Submittal02/05/2020Nelco Architecture, Inc.Phone:Suite 1300Seattle, WA 98101(206) 408-85001200 Fifth Ave.WWW.NELSONWORLDWIDE.COM Proj. No:Reviewed By:SEAL:CITY STAMP:IRGMS/PM IRG GREENLINEBUILDING AWEYERHAEUSER WAYS SFEDERAL WAY, WA 98001CR.00180070.000 CLIENT:PROJECT:11111 SANTA MONICA BLVD.SUITE 800LOS ANGELES, CA 90025Date:No:Description:Permit Submittal02/05/2020Nelco Architecture, Inc.Phone:Suite 1300Seattle, WA 98101(206) 408-85001200 Fifth Ave.WWW.NELSONWORLDWIDE.COM Proj. No:Reviewed By:SEAL:CITY STAMP:IRGMS/PM IRG GREENLINEBUILDING AWEYERHAEUSER WAYS SFEDERAL WAY, WA 98001CR.00180070.000 CLIENT:PROJECT:11111 SANTA MONICA BLVD.SUITE 800LOS ANGELES, CA 90025Date:No:Description:Permit Submittal02/05/2020GPANELHPANELJPANELKPANELLPANELMPANELNPANELOPANELPPANELPJPJPJPJPJ FLOOR LINE+/-0'-0" FLOOR LINE+/-0'-0" FLOOR LINE+/-0'-0"GENERAL NOTES:1.IG INDICATES INSULATED GLAZING, TYP.2.TG INDICATES TEMPERED GLAZING, TYP.3.TIG INDICATES TEMPERED, INSULATED GLAZING, TYP.4.ALL FIXED INSULATED GLAZING SHALL BE CERTIFIED & LABELED WITH ITS MAX.U-FACTOR OF & SOLAR HEAT GAIN COEFFICIENT BY AN INDEPENDENT AGENCYLICENSED BY THE NFRC, IN COMPLIANCE WITH THE VALUES LISTED ON SHEET CS.5.PJ = PANEL JOINT6.PROVIDE AND COORDINATE "KNOXBOX: LOCATION WITH FIRE DEPARTMENT ANDARCHITECT PRIOR TO INSTALL7.ALL VERTICAL DIMENSIONS ARE FROM FINISHED FLOOR, U.N.O.8.CHANGE IN PAINT COLOR OCCURS AT BACK OF REVEAL, TYP. U.N.O.KEY NOTES:1.TILT UP CONCRETE PANEL (PAINT FINISH), TYP.2.PANEL REVEAL, TYP. SEE DETAILS 3/A8.1 AND 4/A8.13.PHENOLIC RESIN PANEL, SIMULATED WOOD GRAIN TEXTURE, ORER 1.5" HATCHANNEL APPLIED TO CONCRETE PANEL; COLOR MIX TBD.4.ANODIZED ALUMINUM STOREFRONT SYSTEM, COLOR: TBD, TYP.5.ALUMINUM DOOR TO MATCH STOREFRONT SYSTEM, TYP. SEE DOORSCHEDULE6.HOLLOW METAL DOOR & FRAME, TYP., PAINT TO MATCH EXISTINGADJACENT WALLS7.LINE OF ROOF BEYOND8.EXTERIOR "WALL PACK" WALL MOUNTED LIGHT FIXTURE, TYP.9.EXTERIOR "SHOE BOX" WALL MOUNTED LIGHT FIXTURE, TYP.10.SURFACE MOUNTED EMERGENCY LIGHT FIXTURE AT EXIT DOOR, TYP.11.PRE-FINISHED METAL COPING, COLOR: TBD12.NOT USED13.PRE-FINISHED METAL CANOPY, COLOR: TBD14.NOT USED15.PRE-FINISHED CONTINUOUS METAL GUTTER: COLOR: TBD WITH PVCDOWNSPOUTS PAINTED PER LEGEND ALONG DOCK ELEVATION. TIGHT-LINE16.NOT USED17.PRE-FINISHED METAL SCUPPER: COLOR: TBD & PAINTED PVC DOWNSPOUTPER LEGEND, SEE DETAIL 11/A8.1, TYP. TIGHT-LINE DOWNSPOUT TO STORMLINE, REFER TO CIVIL DRAWINGS. PROVIDE DOWNSPOUT PROTECTORS ATTRUCK COURT LOCATIONS ONLY, SEE DETAIL 8/A8.118.NOT USED19.SECTIONAL OVERHEAD DRIVE-IN DOOR (INSULATED), PRE-FINISHED,COLOR: TBD, TYP.20.NOT USED21.SECTIONAL OVERHEAD DOCK HIGH DOOR (INSULATED) WITH BUMPERS ANDDOCK SEAL, PRE-FINISHED, COLOR: TBD, TYP.22.NOT USED23.PRE-FAB METAL STAIR AT TRUCK COURT, SEE SITE PLAN24.FOOTINGS PER STRUCTURAL25.FUTURE KNOCK-OUT, PER STRUCTURAL, TYP.26.XX" STEEL CHANNEL, PAINT PER LEGEND27.STEEL TRELLIS, PAINT PER LEGEND28.CONCRETE TILT UP RETAINING WALL, SEE SITE PLAN29.BUILDING ADDRESS: 24" HIGH X 14" THICK DIMENSIONAL NUMBERS. FONT:TREBUCHET MS BOLD, ITALIC. COLOR: TBD30.DAYLIGHT OVERFLOW DOWNSPOUT AT 1'-0" ABOVE FINISH FLOOR WITH"COW TONGUE" DOWNSPOUT NOZZLE.XPJPJPJPJPJPJPJ30302A8.31A8.3ENLARGED EXTERIORELEVATIONSA3.51/8"=1'-0"PANEL ELEVATIONS1A3.5
H35'-0"4'-0"4'-0"1'-0"122'-0"PROPERTY LINE
5'-6"PROPERTY GROUND LEVEL408'-0"15PROPERTY LINE
5'-6"BUILDING GROUND LEVEL401'-3"4'-0"1'-0"RTU4'-0"20'-0"62'-0"LINE OF SIGHT FROM PROPERTY LINELINE OF SIGHT FROM PROPERTY LINERTUPARKING & SIDEWALKDRIVE AISLEUTILITIESLANDSCAPESIDEWALKPRIVATE STREET23'-0"SIDEWALKBUILDING GROUND LEVEL401'-3"SIDEWALKLANDSCAPEPROPERTY GROUND LEVEL405'-3"PARKING STALLS5'-6"
SIDEWALK STREET LEVELLINE OF SIGHT FROM STREET SIDEWALKLANDSCAPEDRIVE AISLENelco Architecture, Inc.Phone:Suite 1300Seattle, WA 98101(206) 408-85001200 Fifth Ave.WWW.NELSONWORLDWIDE.COM Proj. No:Reviewed By:SEAL:CITY STAMP:IRGMS/PM IRG GREENLINEBUILDING AWEYERHAEUSER WAYS SFEDERAL WAY, WA 98001CR.00180070.000 CLIENT:PROJECT:11111 SANTA MONICA BLVD.SUITE 800LOS ANGELES, CA 90025Date:No:Description:Permit Submittal02/05/2020Nelco Architecture, Inc.Phone:Suite 1300Seattle, WA 98101(206) 408-85001200 Fifth Ave.WWW.NELSONWORLDWIDE.COM Proj. No:Reviewed By:SEAL:CITY STAMP:IRGMS/PM IRG GREENLINEBUILDING AWEYERHAEUSER WAYS SFEDERAL WAY, WA 98001CR.00180070.000 CLIENT:PROJECT:11111 SANTA MONICA BLVD.SUITE 800LOS ANGELES, CA 90025Date:No:Description:Permit Submittal02/05/20201/8"=1'-0"SOUTH ENTRY SECTION1A4.011/8"=1'-0"SOUTHWEST ENTRY SECTION2A4.01LINE OF SIGHTSECTIONSA4.01
1 2 3
42'-6"50'-0"
29'-0"
11'-103
4"
7 1/4" THICK 7 1/4" THICK SEE7 1/4" THICK SEE
91
4"
28'-0"28'-0"
12'-0"
AFF
24'-0"
AFF
12'-0"
AFF
24'-0"
AFF
4 4
1
1
2
5
5
5
4
4 5
88
6
6
3
18
AT 6" OC
54
50'-0"
24'-43
4"25'-0"
7 1/4" THICK SEE7 1/4" THICK
12'-0"
AFF
24'-0"
AFF
12'-0"
AFF
24'-0"
AFF
5
5
5
4
85
4
1
4
71
4"71
4"
6 7 8
50'-0"50'-0"
25'-0"25'-0"25'-0"
7 1/4" THICK7 1/4" THICK 7 1/4" THICK SEE
2'-41
4"2'-3"5'-8"12'-0"3'-4"
12'-0"
AFF
24'-0"
AFF
2 2
13 20 17
7
7
7
6 5
8
1'-9"9'-0"3'-6"9'-0"1'-9"
2 2
3
6
6
15 15
20
5
9 10 11 12 13 14
50'-0"50'-0"50'-0"
25'-0"25'-0"25'-0"25'-0"25'-0"25'-0"
7 1/4" THICK SEE 8 7 1/4" THICK SEE 8 7 1/4" THICK SEE 8 7 1/4" THICK SEE 87 1/4" THICK 7 1/4" THICK SEE OPP10
1'-9"
2 211
8 99
6
6
6
6
13
MATCH SPCG
15
MATCH SPCG
1'-9"3'-4"9'-2"9'-0"1'-9" 01/22/20 - 9:21am2180307S-5.0.dwg2215 North 30th Street, Suite 300 Tacoma, WA 98403
253.383.2422TEL 253.383.2572FAX www.ahbl.comWEB
T A C O M A SEATTLE SPOKANE TRI-CITIES
Nelco Architecture, Inc.
Phone:
Suite 1300
Seattle, WA 98101
(206) 408-8500
1200 Fifth Ave.
WWW.NELSONWORLDWIDE.COM
Proj. No:Reviewed By:
SEAL:
CITY STAMP:
IRG
CLR/LAH
IRG GREENLINE
BUILDING A
WEYERHAEUSER WAYS S
FEDERAL WAY, WA 98001
AHBL 2180307.20
CLIENT:
PROJECT:
11111 SANTA MONICA BLVD.
SUITE 800
LOS ANGELES, CA 90025
Date:No:Description:
PERMIT SUBMITTAL 2/03/2019
EAST INTERIOR PANEL ELEVATION
1/8" = 1'-0"
1 SOUTH INTERIOR PANEL ELEVATION
1/8" = 1'-0"
2 EAST INTERIOR PANEL ELEVATION
1/8" = 1'-0"
3
EAST INTERIOR PANEL ELEVATION
1/8" = 1'-0"
4
GENERAL TILT-UP PANEL NOTE:
1.TOLERANCE ON PANEL THICKNESS SPECIFIED SHALL BE PLUS 14" AND MINUS 0".
PANEL THICKNESS IS BASED ON LUMBER FORMS OF 7 12" OR 9 12". REVEALS
SHALL NOT EXCEED 3 4" DEEP AND SHALL BE PLACED AS SHOWN ON THE ARCH
DRAWINGS.
2.THE REINFORCEMENT SHOWN ON THE PANEL ELEVATIONS IS IN ADDITION TO
TYPICAL BARS AT OPENINGS, EDGES, CORNERS, BASE, ETC. OMIT TYPICAL
VERTICAL REINFORCEMENT WHERE MORE CLOSELY SPACED VERTICAL
REINFORCEMENT IS SPECIFIED IN PIERS.
3.PANEL DIMENSIONS ARE TO CENTERLINE OF JOINT OR EDGE OF PANEL
OPENING, UNLESS NOTED OTHERWISE. ALL PANEL CONNECTOR DIMENSIONS
SHOWN ARE TO CENTER LINES OF CONNECTORS UNLESS NOTED OTHERWISE.
4.PROVIDE ADDITIONAL REINFORCING AS REQUIRED FOR LIFTING AND LIFTING
INSERTS.
5.VERTICAL REINFORCEMENT SHALL RUN FULL HEIGHT UNLESS NOTED
OTHERWISE.
6.VERIFY SIZE AND LOCATION OF ALL OPENINGS WITH ARCH DRAWINGS.
7.DO NOT CUT OR DRILL ANY HOLES IN PANELS WITHOUT APPROVAL OF
ENGINEER UNLESS SHOWN OR INDICATED.
8.REINFORCING SHOP DRAWINGS SHALL BE REVIEWED BY THE ENGINEER PRIOR
TO PLACEMENT.
9.DO NOT SCALE PANEL ELEVATIONS. SEE ARCH DWGS FOR BUILDING
DIMENSIONS.
10.SLOPE TOP OF PANELS WHERE REQUIRED PER ARCH DRAWINGS.
11.SEE FOUNDATION PLAN FOR LOCATIONS OF PANELS.
12.UNLESS NOTED OTHERWISE, TILT-UP PANEL ELEVATIONS SHOW PANELS
VIEWED FROM INSIDE OF BUILDING LOOKING TOWARDS BUILDING EXTERIOR.
#5 SLAB DOWELS AT 24" O.C. SEE FOUNDATION DETAIL FOR REQ'D
OPENINGS (12" HOOK INTO PANEL)
(LEG MAY BE UP OR DOWN IN PANEL)
#5 SLAB DOWELS (PER NOTE 8) AT 8" O.C. AT PIER (3 MIN PER PIER). SEE
FOUNDATION DETAIL FOR REQ'D AT OPENINGS
FUTURE OPENING, RUN REINF ABOVE THRU OPENING.
#5 VERT AT 10" OC, CL PNL AND #5 HORIZ AT 16" OC
#5 VERT AT 8" OC, CL PNL AND #5 HORIZ AT 16"OC
PIER: (3) #5 EACH FACE VERTICAL (6 TOTAL) EQ SPACED
PIER: (4) #5 EACH FACE VERTICAL (8 TOTAL) EQ SPACED
PIER: (5) #5 EA FACE VERTICAL (10 TOTAL) EQ SPACE
PIER: (6) #5 EA FACE VERTICAL (12 TOTAL) EQ SPACE
PIER: (7) #5 EA FACE VERTICAL (14 TOTAL) EQ SPACE
PIER: (8) #5 EA FACE VERTICAL (16 TOTAL) EQ SPACE
PIER: (9) #5 EA FACE VERTICAL (18 TOTAL) EQ SPACE
PIER: (10) #5 EA FACE VERTICAL (20 TOTAL) EQ SPACE
PIER: (11) #5 EA FACE VERTICAL (22 TOTAL) EQ SPACE
PIER: (12) #5 EA FACE VERTICAL (24 TOTAL) EQ SPACE
PIER: (13) #5 EA FACE VERTICAL (26 TOTAL) EQ SPACE
PIER: (14) #5 EA FACE VERTICAL (28 TOTAL) EQ SPACE
PIER: (15) #5 EA FACE VERTICAL (30 TOTAL) EQ SPACE
EF - EACH FACE
FOP-FACE OF PANEL
HK - HOOK
CL - CENTERLINE
PANEL X
1
2
3
24"
24"
12" 36"
4
5
6
7
8
9
11
12
13
14
15
16
18
20
19
17
ABBREVIATIONS AND SYMBOLS
#5 VERT AT 10" O.C. EA FACE AND #5 HORIZ AT 16" O.C. STAGGER INSIDE VERTS
TYP REINF ABOVE AND BELOW OPNG #4 AT 18" O.C. VERT AT CL PNL W/ STD 180
DEG HOOK TOP AND BTM AT OPENINGS AND #5 AT 16" O.C. HORIZ.
(1) #5 x 4'-0" DIAG. (TYP) AT OPENING CORNERS (AT SMALL NARROW PIER, BEND
BAR TO FOLLOW EDGE OF PANEL).
(2) #5 AT BOTTOM CORNER
OF SINGLE MAT PANEL
(2) #5 AT EDGE OF PANEL. (GENERAL REQUIREMENT, IN DOUBLE MAT PIERS DO
NOT ADD EXTRA)
(2) #5 AT EDGE OF OPENINGS. VERTICAL RUN FULL HEIGHT. HORIZ RUN 30"
PAST EDGE OF OPENING, STD HK IF PIER LESS THAN 30"
AT PIERS PROVIDE #3 TIES AT 6" O.C. ADJ TO OPENINGS AND FOR 30" ABOVE
AND BELOW OPENING, 48" O.C. ELSEWHERE AND (1) TOP & BTM OF PIER. SEE
PANEL ELEV FOR TIGHTER TIE SPACING WHERE NOTED ON ELEVATION.
21
22
23
24
KEY NOTES
25
10
15 16 17 18 19 20 21 22 23
50'-0"50'-0"50'-0"50'-0"50'-0"
25'-0"25'-0"25'-0"25'-0"25'-0"25'-0"25'-0"25'-0"25'-0"
7 1/4" THICK SEE 8 7 1/4" THICK SEE 8 7 1/4" THICK SEE 8 7 1/4" THICK SEE 8 7 1/4" THICK SEE 8 7 1/4" THICK SEE 87 1/4" THICK SEE 10 7 1/4" THICK SEE 10 7 1/4" THICK SEE OPP10
24 25 26 27
50'-0"50'-0"50'-0"
25'-0"25'-0"25'-0"25'-0"
7 1/4" THICK SEE 8 7 1/4" THICK SEE 8 7 1/4" THICK SEE 8 7 1/4" THICK SEE OPP6 28 29
50'-0"
25'-71
4"24'-43
4"
7 1/4" THICK SEE 4 7 1/4" THICK SEE 5 30 31
50'-0"42'-6"
29'-0"29'-0"
11'-10
7 1/4" THICK SEE 4 7 1/4" THICK SEE OPP2
01/22/20 - 9:21am2180307S-5.0.dwg2215 North 30th Street, Suite 300 Tacoma, WA 98403
253.383.2422TEL 253.383.2572FAX www.ahbl.comWEB
T A C O M A SEATTLE SPOKANE TRI-CITIES
Nelco Architecture, Inc.
Phone:
Suite 1300
Seattle, WA 98101
(206) 408-8500
1200 Fifth Ave.
WWW.NELSONWORLDWIDE.COM
Proj. No:Reviewed By:
SEAL:
CITY STAMP:
IRG
CLR/LAH
IRG GREENLINE
BUILDING A
WEYERHAEUSER WAYS S
FEDERAL WAY, WA 98001
AHBL 2180307.20
CLIENT:
PROJECT:
11111 SANTA MONICA BLVD.
SUITE 800
LOS ANGELES, CA 90025
Date:No:Description:
PERMIT SUBMITTAL 2/03/2019
EAST INTERIOR PANEL ELEVATION
1/8" = 1'-0"
1
EAST INT PANEL ELEV
1/8" = 1'-0"
2 NORTH INTERIOR PANEL ELEVATION
1/8" = 1'-0"
3 EAST INTERIOR PANEL ELEVATION
1/8" = 1'-0"
4
34 35 36 38 39 40 413337
50'-0"60'-0"50'-0"
23'-9"23'-9"23'-9"
9'-0"
23'-9"23'-9"23'-9"23'-9"
8'-1"
9 1/4" THICK 9 1/4" THICK 9 1/4" THICK SEE 34 9 1/4" THICK SEE 34 9 1/4" THICK SEE 35 9 1/4" THICK SEE OPP35 9 1/4" THICK SEE 349 1/4"
THICK SEE 34
5
5
5
4
8
5
4
5
5
5
8
4
12 12
2
2
15
MATCH SPCG
7
7
3
6
2'-5"7'-41
2"
9 1/4" THICK
2
6
6
3 77
13
14
5
9 1/4" THICK
SEE
F4.0F4.0F5.5F4.043 44 45 46 48 49 504247
50'-0"50'-0"50'-0"60'-0"
9'-0"
23'-9"23'-9"23'-9"23'-9"
9'-0"
29'-0"32'-6"
9 1/4" THICK SEE 34 9 1/4" THICK 9 1/4" THICK SEE OPP44 9 1/4" THICK SEE 34 91/4" THICK 9 1/4" THICK SEE 48 9 1/4" THICK
37
9 1/4" THICK
SEE 37
9 1/4" THICK
SEE
91
4"
2 2
2 2
2 2
2'-6"9'-6"5'-0"9'-6"2'-6"
5 8
77 7
5
3
66
66
16 16
22
2 2
2 2
2 2
5 8
77
7
5
3
66
66
16
2822
6" OC
FULL HT
29
55
5
11 5
S4.3
6
S5,8
HSS 8 x 6 x 3/8 FLAT
HSS 8 x 6 x 3/8 FLAT
STEEL COL
9
-
OPP
7
7
-
8
-
8
-
2'-6"9'-6"5'-0"9'-6"6'-9"
9"23'-113
4"
9
-
OPP
2'-6"7'-41
2"4'-61
4"6'-4"3'-01
4"
19
5
5
8
2
2
15
7
7
3
6 2
15
6
32
11'-103
4"
7 1/4" THICK SEE 4
91
4" 01/22/20 - 9:21am2180307S-5.0.dwg2215 North 30th Street, Suite 300 Tacoma, WA 98403
253.383.2422TEL 253.383.2572FAX www.ahbl.comWEB
T A C O M A SEATTLE SPOKANE TRI-CITIES
Nelco Architecture, Inc.
Phone:
Suite 1300
Seattle, WA 98101
(206) 408-8500
1200 Fifth Ave.
WWW.NELSONWORLDWIDE.COM
Proj. No:Reviewed By:
SEAL:
CITY STAMP:
IRG
CLR/LAH
IRG GREENLINE
BUILDING A
WEYERHAEUSER WAYS S
FEDERAL WAY, WA 98001
AHBL 2180307.20
CLIENT:
PROJECT:
11111 SANTA MONICA BLVD.
SUITE 800
LOS ANGELES, CA 90025
Date:No:Description:
PERMIT SUBMITTAL 2/03/2019
SOUTH INTERIOR PANEL ELEVATION
1/8" = 1'-0"
2
SOUTH INTERIOR PANEL ELEVATION
1/8" = 1'-0"
3
EAST INTERIOR PANEL ELEVATION
1/8" = 1'-0"
1
F5.5F4.0F4.0F5.5F51
54 5756555352
42'-6"50'-0"50'-0"50'-0"
38'-6"29'-0"
12'-0"
23'-9"23'-9"23'-9"
9 1/4" THICK SEE OPP50
9 1/4" THICK SEE 9 1/4" THICK SEE 48 9 1/4" THICK SEE 34 9 1/4" THICK SEE 35 9 1/4" THICK SEE OPP35
1
S5.4
6
S5.8
OPP
12'-0"9'-6"5'-0"9'-6"2'-6"
19'-6"
7
FULL HT
16
48
MATCH
SPCG
8
18
FULL HT
4 1/2" OC
19
9 1/4" THICK
SEE OPP37
9"
5
5
11
7
AT 6"OC
14
AT 6"OC
5
S4.3
696459636261605865666768
50'-0"50'-0"50'-0"50'-0"50'-0"
23'-9"
9'-0"
23'-9"23'-9"23'-9"23'-9"
9'-0"
23'-9"
9'-0"
23'-9"23'-9"23'-9"
9 1/4" THICK SEE 34 9 1/4" THICK SEE 34 9 1/4" THICK SEE OPP35 9 1/4" THICK SEE 35 9 1/4" THICK SEE 34 9 1/4" THICK SEE 34 9 1/4" THICK SEE 35 9 1/4" THICK SEE OPP35 9 1/4" THICK SEE 34
9 1/4" THICK
SEE
OPP
37
9 1/4" THICK
SEE 37
9 1/4" THICK
SEE 37
HSS 8 x 6 x 3/8 FLAT
HSS 8 x 6 x 3/8 FLAT
STEEL COL
7
-
7
-
7
-
7
-F5.5F4.0F4.0F5.5F1
S5.4
01/22/20 - 9:21am2180307S-5.0.dwg2215 North 30th Street, Suite 300 Tacoma, WA 98403
253.383.2422TEL 253.383.2572FAX www.ahbl.comWEB
T A C O M A SEATTLE SPOKANE TRI-CITIES
Nelco Architecture, Inc.
Phone:
Suite 1300
Seattle, WA 98101
(206) 408-8500
1200 Fifth Ave.
WWW.NELSONWORLDWIDE.COM
Proj. No:Reviewed By:
SEAL:
CITY STAMP:
IRG
CLR/LAH
IRG GREENLINE
BUILDING A
WEYERHAEUSER WAYS S
FEDERAL WAY, WA 98001
AHBL 2180307.20
CLIENT:
PROJECT:
11111 SANTA MONICA BLVD.
SUITE 800
LOS ANGELES, CA 90025
Date:No:Description:
PERMIT SUBMITTAL 2/03/2019
WEST ENTRY FRAMING ELEVATION
1/8" = 1'-0"
1
WEST INTERIOR PANEL ELEVATION
1/8" = 1'-0"
3
WEST INTERIOR PANEL ELEVATION
1/8" = 1'-0"
2
8079787776757372717074
50'-0"50'-0"50'-0"50'-0"50'-0"
23'-9"23'-9"23'-9"23'-9"
9'-0"
23'-9"23'-9"23'-9"23'-9"
12'-0"
29'-0"
9 1/4" THICK SEE 489 1/4" THICK SEE 34 9 1/4" THICK SEE OPP35 7 1/4" THICK SEE 35 9 1/4" THICK SEE 34 9 1/4" THICK SEE 34 9 1/4" THICK SEE 349 1/4" THICK SEE 35 9 1/4" THICK SEE OPP35
9 1/4" THICK 9 1/4" THICK
SEE 37
9 1/4" THICK
SEE 37
F4.0F5.5F82
81
42'-6"
38'-6"
9 1/4" THICK SEE OPP52
9 1/4" THICK SEE51
9"19'-6"
3
S5.5
6
S5.8
5
S4.3 F5.5F82
42'-6"
9 1/4" THICK SEE51
9"19'-6"
3
S5.5
7
-
HSS 8 x 6 x 3/8 FLAT
HSS 8 x 6 x 3/8 FLAT
7
-
6
S5.8
5
S4.3
F4.0F4.0F5.5F4.0 F4.0
8483
60'-0"
9"32'-6"
9 1/4" THICK SEE OPP50 9 1/4" THICK SEE OPP49
23'-113
4"91
4"
HSS 8 x 6 x 3/8 FLAT
HSS 8 x 6 x 3/8 FLAT
STEEL COL
7
-
7
-
8
-
8
-HSS 8 x 89
-
9
-
6
S5.8
5
S4.3
01/22/20 - 9:21am2180307S-5.0.dwg2215 North 30th Street, Suite 300 Tacoma, WA 98403
253.383.2422TEL 253.383.2572FAX www.ahbl.comWEB
T A C O M A SEATTLE SPOKANE TRI-CITIES
Nelco Architecture, Inc.
Phone:
Suite 1300
Seattle, WA 98101
(206) 408-8500
1200 Fifth Ave.
WWW.NELSONWORLDWIDE.COM
Proj. No:Reviewed By:
SEAL:
CITY STAMP:
IRG
CLR/LAH
IRG GREENLINE
BUILDING A
WEYERHAEUSER WAYS S
FEDERAL WAY, WA 98001
AHBL 2180307.20
CLIENT:
PROJECT:
11111 SANTA MONICA BLVD.
SUITE 800
LOS ANGELES, CA 90025
Date:No:Description:
PERMIT SUBMITTAL 2/03/2019
WEST INTERIOR PANEL ELEVATION
1/8" = 1'-0"
1
WEST INTERIOR PANEL ELEVATION
1/8" = 1'-0"
2 WEST ENTRY FRAMING ELEVATION
1/8" = 1'-0"
3 NORTH INTERIOR PANEL ELEVATION
1/8" = 1'-0"
4
9594939290898887858691 96
50'-0"50'-0"50'-0"50'-0"60'-0"
29'-0"
9'-0"
23'-9"23'-9"23'-9"23'-9"
9'-0"
23'-9"23'-9"23'-9"23'-9"
9'-0"
9 1/4" THICK SEE48 9 1/4" THICK SEE34 9 1/4" THICK SEE34 9 1/4" THICK SEE34 9 1/4" THICK SEE349 1/4" THICK SEE35 9 1/4" THICK SEE359 1/4" THICK SEE OPP35 9 1/4" THICK SEE OPP35
9 1/4" THICK
SEE OPP37
9 1/4" THICK
SEE OPP37
9 1/4" THICK
SEE OPP37
999897 100
60'-0"50'-0"
23'-9"23'-9"23'-9"
8'-1"
9 1/4" THICK SEE34 9 1/4" THICK SEE349 1/4" THICK SEE OPP35
9 1/4" THICK
SEE OPP
9 1/4" THICK
SEE 34
01/22/20 - 9:21am2180307S-5.0.dwg2215 North 30th Street, Suite 300 Tacoma, WA 98403
253.383.2422TEL 253.383.2572FAX www.ahbl.comWEB
T A C O M A SEATTLE SPOKANE TRI-CITIES
Nelco Architecture, Inc.
Phone:
Suite 1300
Seattle, WA 98101
(206) 408-8500
1200 Fifth Ave.
WWW.NELSONWORLDWIDE.COM
Proj. No:Reviewed By:
SEAL:
CITY STAMP:
IRG
CLR/LAH
IRG GREENLINE
BUILDING A
WEYERHAEUSER WAYS S
FEDERAL WAY, WA 98001
AHBL 2180307.20
CLIENT:
PROJECT:
11111 SANTA MONICA BLVD.
SUITE 800
LOS ANGELES, CA 90025
Date:No:Description:
PERMIT SUBMITTAL 2/03/2019
NORTH INTERIOR PANEL ELEVATION
1/8" = 1'-0"
1
NORTH INTERIOR PANEL ELEVATION
1/8" = 1'-0"
2
SECTION
1 1/2" = 1'-0"
1 SECTION
1 1/2" = 1'-0"
4SECTION
1 1/2" = 1'-0"
2 SECTION
1 1/2" = 1'-0"
3
3/4" REVEAL, TYP UNO ON PNL ELEV
LOCATE OFFSET FROM REVEAL
(2) MIN PER PANEL EDGE AT CORNERS
4"11
2"
TYP5/16
1
1
PL 3/8" x 6"x 0'-6"
CLR
2"TYPICAL
AND CAULKING
BACKER ROD
6"
51/4
A706 REBAR
W/ #5 x 5'-6"
BAR 3/8 x 2 1/2 x 0'-5"
INTERIOR FACE
TYPICAL OUTSIDE CORNER CONNECTION
["
INSIDE FACE(2) #5 AT PNEL EDGE
45°
3/4" CHAMFER, TYP
IN LIEU OF TYP HORIZ REINF
TIES PER PANEL ELEVATION
1" CLR TO VERTICAL
TYP AT INSIDE FACE
TYPICAL VERTICAL EDGE REINFORCEMENT
AT CL OF WALL
TYP VERT REINF
REINFORCEMENT
TYPICAL HORIZ.
NUMBER OF VERT REINF
BARS PER PANEL ELEV
(2) #5 VERT TYP
AT PANEL EDGE
(1) #5 x4'-0" AT
EA PLATE
UNLESS IN PIER
WITH TIES
1 12" CLR TO VERT BAR
TYP AT REVEAL
(ONCE WELDED, CORNER TILT BRACES MAY BE REMOVED)
PL 3 8" x 4" x 0'6" W/
(2) 12" DIA x 5" W.H.S.
AT 4" O.C.
PANEL CONT AT
SIM
TYPICAL INSIDE CORNER CONNECTION
11
2"
1
1
PL 1/4" x 2" x 0'-5"
45°
A706 REBAR
6"
L 2 x 2 x 3/8 x 0'-6" W/ #5 x 6'-6"
INTERIOR FACE
INTERIOR FACE3/16 4
PANEL TO PANEL CONNECTION
3/4"
6"CL PANEL45°
51/4
L 2 x 2 x 1/4 x 0'-5"
INTERIOR FACE
11
2"
(2) #5 VERT WHERE SHOWN
ON ELEVATION
(2) MIN PER PANEL EDGE AT CORNERS
(ONCE WELDED, CORNER TILT BRACES MAY BE
REMOVED)
5SEE
FOR
CALLOUTS
IN COMMON
5/16 TYP
5/16 TYP
3/4" CHAMFER TYP
AT EXPOSED EXT
CORNERS
BACKER ROD AND
CAULKING TYPICAL
L 2 x 2 x 3/8 x 0'-6" W/ #5 x 3'-6"
A706 REBAR
(2) MIN BETWEEN PANELS ALONG GRIDS
A, AND O TYPICAL
SECTION
1 1/2" = 1'-0"
5
4"4"
4
"4"
11
2"
3"
5
-
SPACE AT 3'-0"OC
TO ROOF SHTG
1/4
TYP
REBAR
EMBED (2) PL 3
4"x9 1
4"x9 1
4" (BEVEL TO
MATCH EXTERIOR CHAMFER STRIP W/ (3)
#5 x 4'-0" A706 ANGLED BARS AND (2) #5 x
2'6" VERTICAL BARS AT 4" GAGE
5/16
2"2"30°1
2" ELASTAMERIC
BEARING PAD
EMBED (2) PL 3
4"x9 1
4"x9 1
4" (BEVEL TO
MATCH EXTERIOR CHAMFER W/ (3) #5 x
4'0" A706 ANGLED BARS AND (2) #5 x 2'6"
VERTICAL BARS AT 4" GAGE
SECTION
1" = 1'-0"
61'-6"PLAN
1" = 1'-0"
7 PLAN
1" = 1'-0"
8
1/4
TAB TO COL
(FIELD WELD OK)
1
4" CLR
1"TAB PL 5
8"x1 1
2"x0'-6" AT CL COL
COPE BACK TOP OF GIRT 1
2"
AND NOTCH INSIDE FACE TO
ALLOW GIRT TO SLIP OVER
TOP OF TAB
1/4 4
PLAN
1" = 1'-0"
9
FOR CALLOUTS
IN COMMON
SEE 7
-
GIRT TO
TAB
HSS 8x8 CORNER COL PER FDN
PLAN
HSS 8x6 GIRT PER
ELEVATION
HSS 8x6 GIRT PER
ELEVATION
HSS 8x6 GIRT PER
ELEVATION
HSS 10x10 BLDG COL
PER FDN PLAN
(2) KNIFE PL 3
8"x4"x0'6",
CENTER ON FACE OF
GIRT
1/4
3/16
KNIFE TO
COL
EMBED PL 3
4"x6"x0'-9 1
4"
BEVEL EDGE TO
MATCH CHAMFER. (2)
5
8"Øx6" WHS AT 4"
GAGE AT CTR
01/22/20 - 9:21am2180307S-5.0.dwg2215 North 30th Street, Suite 300 Tacoma, WA 98403
253.383.2422TEL 253.383.2572FAX www.ahbl.comWEB
T A C O M A SEATTLE SPOKANE TRI-CITIES
Nelco Architecture, Inc.
Phone:
Suite 1300
Seattle, WA 98101
(206) 408-8500
1200 Fifth Ave.
WWW.NELSONWORLDWIDE.COM
Proj. No:Reviewed By:
SEAL:
CITY STAMP:
IRG
CLR/LAH
IRG GREENLINE
BUILDING A
WEYERHAEUSER WAYS S
FEDERAL WAY, WA 98001
AHBL 2180307.20
CLIENT:
PROJECT:
11111 SANTA MONICA BLVD.
SUITE 800
LOS ANGELES, CA 90025
Date:No:Description:
PERMIT SUBMITTAL 2/03/2019
01/22/20 - 9:21am2180307S-5.0.dwg2215 North 30th Street, Suite 300 Tacoma, WA 98403
253.383.2422TEL 253.383.2572FAX www.ahbl.comWEB
T A C O M A SEATTLE SPOKANE TRI-CITIES
Nelco Architecture, Inc.
Phone:
Suite 1300
Seattle, WA 98101
(206) 408-8500
1200 Fifth Ave.
WWW.NELSONWORLDWIDE.COM
Proj. No:Reviewed By:
SEAL:
CITY STAMP:
IRG
CLR/LAH
IRG GREENLINE
BUILDING A
WEYERHAEUSER WAYS S
FEDERAL WAY, WA 98001
AHBL 2180307.20
CLIENT:
PROJECT:
11111 SANTA MONICA BLVD.
SUITE 800
LOS ANGELES, CA 90025
Date:No:Description:
PERMIT SUBMITTAL 2/03/2019