21-100325-Water System Hydraulic -01-29-2021-V1LAKEHAVEN UTILITY DISTRICT Hydraulic Model Fire Flow Estimate Request/Reporting Form Requested By: Brian Asbury Date: 07/1/16 Location to be Modeled: Proposed "Preferred Freezer" Site (APN 6142600005/6142600200) Lakehaven'/, Section Grid: L/11 Intersection: West of S 33901 St & Weyerhaeuser Way S Add. Description: See attached map; Hyd #3 Pressure Zone: 538 Results By: John Bowman._ Date: 7/19/16 Model Run No.: Master Water System Model 2007.net FF #324 Condition Pressure (psi) Flow (gpm) Static 40 oil Fire Flow 20 4100 NOTES: Lakehaven's adopted level of service goals for fire flow rates are 1000 gpm within single family residential areas (including duplexes) and 2500 gpm for multi -family, commercial, and industrial areas. Model results depict the theoretical performance of the water system under high demand conditions and are not guaranteed to represent actual system performance. A design professional should be consulted for site specific design purposes. The calculated fire flow capacity in the above table is based on a currently available residual system pressure of 20 psi at the location modeled and with a proposed new 12" diameter pipe loop. An 8" diameter pipe loop exceeded Lakehaven's standard maximum allowable velocity of 8 ftls for new pipe at a fire flow rate above 2100 gpm. 071916FF 324 - Preferred Freezer (Form Rev. 12/6/13) (NOTE: Lalcehaven Utility District neither warrants nor guarantees the accuracy of any facility Information provided, Facility locations and conditlons are subject to field verlflea( Ion. PREFERRED FREEZER / ORCA EAY 16.102265-00-UP 0 300 Feet .tr 5/13/2016 BIA