20-104486 -Drawings-11-12-2020-V134512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureK. LANGLOISMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.31230PERMIT SETMMA Clinic11/10/2020Federal WayFederal Way, WA 98003 8466Karsea M. LangloisSTATE OF WASHINGTONREGISTEREDARCHITECTT0.0PROJECT INFORMATION:INDEX TO DRAWING SET:GRAPHIC SYMBOLS:PROJECT TEAM:ARCHITECT:OWNER:FACILITY CONTACTS:PROJECT INFO /INDEX / SITEPLANMECHANICAL:PROJECT DESCRIPTION:ELECTRICAL:STRUCTURAL:VICINITY MAPSITE PLAN(NOT TO SCALE)RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 202020-104486 -Drawings-11-12-2020-V1 Electrical/IS&TCloset101-22CleanSupply/Equip. Room101-23ExamRoom #10101-32ExamRoom #8101-31Biohazard/SoiledHolding101-11Registration101-03Waiting101-02ADAPublicToilet101-04MA WorkStations101-16WCAlcove101-01AProviderOffice101-15Lab101-07EntryVestibule101-01ExamRoom #7101-35ExamRoom #6101-30ExamRoom #1101-25ExamRoom #3101-24ADAPatientToilet101-08BariatricExamRoom #2101-20Med.Dist.Room101-18ConsultRoom #1101-26Print101-29ASupervisor'sOffice101-13ProviderOffice101-17ExamRoom #11101-33ExamRoom #9101-34ExamRoom #5101-36StaffLounge101-09LabWaiting101-06AVitalsArea #1101-05ABariatricExamRoom #4101-21VitalsArea #2101-14ADrawStation #2101-07BLabCheck-in101-02AConsultRoom #2101-37DrawStation #1101-07AADAPatientToilet101-27ADAPatientToilet101-28InfantScale101-29BPrint101-19AHall101-29Hall101-19Hall101-05Hall101-14Hall101-06ADAStaffToilet101-10EVSCloset101-12Print101-29CUtility101-10A60X2460X2460X2448X2448X2448X2448X2448X2448X2448X2448X2460X2460X2460X2460X2454X1854X1854X1860X2460X2448X2448X24LIFE SAFETY PLANSCALE: 1/4" = 1'-0"5,427 GSFCODE LEGENDBUILDING CODE DATAGENERAL NOTESFLOOR PLAN KEY NOTESEXITSDHSTFDHEXITFFEXITFFEXIT126 SF IS&T CLOSET4,854 NSF / 100 = 49 OCCUPANTS- 12 SF EVS CLOSET5,427 SF GSF182 SF CLEAN SUPPLY233 SF RESTROOMS20 SF HW CLOSETOCCUPANCY LOAD CALCULATION34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureK. LANGLOISMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.31230PERMIT SETMMA Clinic11/10/2020Federal WayFederal Way, WA 98003 8466Karsea M. LangloisSTATE OF WASHINGTONREGISTEREDARCHITECTLIFE SAFETYPLANA0.1RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 DETAILED FLOOR PLAN: DEMOLITIONSCALE: 1/4" = 1'-0"5,427 GSFGENERAL NOTESDEMOLITION PLAN KEYED NOTESLEGEND34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureK. LANGLOISMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.31230PERMIT SETMMA Clinic11/10/2020Federal WayFederal Way, WA 98003 8466Karsea M. LangloisSTATE OF WASHINGTONREGISTEREDARCHITECTFLOOR PLAN:DEMOLITIONA1.1RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 Electrical/IS&TCloset101-22CleanSupply/Equip. Room101-23ExamRoom #10101-32ExamRoom #8101-31Biohazard/SoiledHolding101-11Registration101-03Waiting101-02ADAPublicToilet101-04MA WorkStations101-16WCAlcove101-01AProviderOffice101-15Lab101-07EntryVestibule101-01ExamRoom #7101-35ExamRoom #6101-30ExamRoom #1101-25ExamRoom #3101-24ADAPatientToilet101-08BariatricExamRoom #2101-20Med.Dist.Room101-18ConsultRoom #1101-26Print101-29ASupervisor'sOffice101-13ProviderOffice101-17ExamRoom #11101-33ExamRoom #9101-34ExamRoom #5101-36StaffLounge101-09LabWaiting101-06AVitalsArea #1101-05ABariatricExamRoom #4101-21VitalsArea #2101-14ADrawStation #2101-07BLabCheck-in101-02AConsultRoom #2101-37DrawStation #1101-07AADAPatientToilet101-27ADAPatientToilet101-28InfantScale101-29BPrint101-19AHall101-29Hall101-19Hall101-05Hall101-14Hall101-06ADAStaffToilet101-10EVSCloset101-12Print101-29CUtility101-10ALEGENDDETAILED FLOOR PLAN: PROPOSEDSCALE: 1/4" = 1'-0"5,427 GSFGENERAL NOTESKEYED NOTES49'-0" RADIUS34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureK. LANGLOISMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.31230PERMIT SETMMA Clinic11/10/2020Federal WayFederal Way, WA 98003 8466Karsea M. LangloisSTATE OF WASHINGTONREGISTEREDARCHITECTFLOOR PLAN:PROPOSEDA2.1RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 Electrical/IS&TCloset101-22CleanSupply/Equip. Room101-23ExamRoom #10101-32ExamRoom #8101-31Biohazard/SoiledHolding101-11Registration101-03Waiting101-02ADAPublicToilet101-04MA WorkStations101-16WCAlcove101-01AProviderOffice101-15Lab101-07EntryVestibule101-01ExamRoom #7101-35ExamRoom #6101-30ExamRoom #1101-25ExamRoom #3101-24ADAPatientToilet101-08BariatricExamRoom #2101-20Med.Dist.Room101-18ConsultRoom #1101-26Print101-29ASupervisor'sOffice101-13ProviderOffice101-17ExamRoom #11101-33ExamRoom #9101-34ExamRoom #5101-36StaffLounge101-09LabWaiting101-06AVitalsArea #1101-05ABariatricExamRoom #4101-21VitalsArea #2101-14ADrawStation #2101-07BLabCheck-in101-02AConsultRoom #2101-37DrawStation #1101-07AADAPatientToilet101-27ADAPatientToilet101-28InfantScale101-29BPrint101-19AHall101-29Hall101-19Hall101-05Hall101-14Hall101-06ADAStaffToilet101-10EVSCloset101-12Print101-29CUtility101-10A60X2460X2460X2448X2448X2448X2448X2448X2448X2448X2448X2460X2460X2460X2460X2454X1854X1854X1860X2460X2448X2448X24LEGENDEQUIPMENT PLANSCALE: 1/4" = 1'-0"5,427 GSF34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureK. LANGLOISMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.31230PERMIT SETMMA Clinic11/10/2020Federal WayFederal Way, WA 98003 8466Karsea M. LangloisSTATE OF WASHINGTONREGISTEREDARCHITECTEQUIPMENTPLANA3.1EQUIPMENT NOTES:RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 Electrical/IS&TCloset101-22CleanSupply/Equip. Room101-23ExamRoom #10101-32ExamRoom #8101-31Biohazard/SoiledHolding101-11Registration101-03Waiting101-02ADAPublicToilet101-04MA WorkStations101-16WCAlcove101-01AProviderOffice101-15Lab101-07EntryVestibule101-01ExamRoom #7101-35ExamRoom #6101-30ExamRoom #1101-25ExamRoom #3101-24ADAPatientToilet101-08BariatricExamRoom #2101-20Med.Dist.Room101-18ConsultRoom #1101-26Print101-29ASupervisor'sOffice101-13ProviderOffice101-17ExamRoom #11101-33ExamRoom #9101-34ExamRoom #5101-36StaffLounge101-09LabWaiting101-06AVitalsArea #1101-05ABariatricExamRoom #4101-21VitalsArea #2101-14ADrawStation #2101-07BLabCheck-in101-02AConsultRoom #2101-37DrawStation #1101-07AADAPatientToilet101-27ADAPatientToilet101-28InfantScale101-29BPrint101-19AHall101-29Hall101-19Hall101-05Hall101-14Hall101-06ADAStaffToilet101-10EVSCloset101-12Print101-29CUtility101-10ALEGENDREFLECTED CEILING PLANSCALE: 1/4" = 1'-0"GENERAL NOTESKEYED NOTESLEGENDSPALIGNALIGNALIGNALIGNALIGNALIGNCLCLCL34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureK. LANGLOISMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.31230PERMIT SETMMA Clinic11/10/2020Federal WayFederal Way, WA 98003 8466Karsea M. LangloisSTATE OF WASHINGTONREGISTEREDARCHITECTREFLECTEDCEILING PLANA4.1RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 1MOUNTING HEIGHTS (TYPICAL)34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureK. LANGLOISMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.31230PERMIT SETMMA Clinic11/10/2020Federal WayFederal Way, WA 98003 8466Karsea M. LangloisSTATE OF WASHINGTONREGISTEREDARCHITECTTYPICALMOUNTINGHEIGHTSA6.0RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 Waiting Room (101-02)SCALE: 3/8" = 1'-0"2Registration (101-03)SCALE: 3/8" = 1'-0"3MultiCare Family MedicineADA Public Toilet (101-04)SCALE: 3/8" = 1'-0"4Entry (101-01) / Wheelchair Alcove (101-01A)SCALE: 3/8" = 1'-0"134512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureK. LANGLOISMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.31230PERMIT SETMMA Clinic11/10/2020Federal WayFederal Way, WA 98003 8466Karsea M. LangloisSTATE OF WASHINGTONREGISTEREDARCHITECTINTERIORELEVATIONSA6.1EQUIPMENT NOTES:RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 Lab (101-07)SCALE: 3/8" = 1'-0"7Vitals Area (101-05A)SCALE: 3/8" = 1'-0"5ADA Patient Toilet (101-08)SCALE: 3/8" = 1'-0"8Draw Station #1 (101-07A) / Draw Station #2 (101-07B)SCALE: 3/8" = 1'-0"7ADraw Station #2 (101-07B)SCALE: 3/8" = 1'-0"7BDraw Station #1 (101-07A)SCALE: 3/8" = 1'-0"7A34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureK. LANGLOISMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.31230PERMIT SETMMA Clinic11/10/2020Federal WayFederal Way, WA 98003 8466Karsea M. LangloisSTATE OF WASHINGTONREGISTEREDARCHITECTINTERIORELEVATIONSA6.2EQUIPMENT NOTES:RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 Staff Lounge (101-09)SCALE: 3/8" = 1'-0"9Staff Lounge (101-09)SCALE: 3/8" = 1'-0"9ADA Staff Toilet (101-10)SCALE: 3/8" = 1'-0"10Biohazard / Soiled Workroom (101-11)SCALE: 3/8" = 1'-0"1134512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureK. LANGLOISMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.31230PERMIT SETMMA Clinic11/10/2020Federal WayFederal Way, WA 98003 8466Karsea M. LangloisSTATE OF WASHINGTONREGISTEREDARCHITECTINTERIORELEVATIONSA6.3EQUIPMENT NOTES:RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 EVS Closet (101-12)SCALE: 3/8" = 1'-0"12Hall and Vitals Area (101-14 & 101-14A)SCALE: 3/8" = 1'-0"14MA Work Stations (101-16)SCALE: 3/8" = 1'-0"16Medication Distribution Room (101-18)SCALE: 3/8" = 1'-0"1834512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureK. LANGLOISMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.31230PERMIT SETMMA Clinic11/10/2020Federal WayFederal Way, WA 98003 8466Karsea M. LangloisSTATE OF WASHINGTONREGISTEREDARCHITECTINTERIORELEVATIONSA6.4EQUIPMENT NOTES:RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 Bariatric Exam Room #2 (101-20)SCALE: 3/8" = 1'-0"20Printer Alcove (101-19A)SCALE: 3/8" = 1'-0"19APrinter Alcove (101-19A)19AExam Room #1 (101-25) / All Exam Rooms Similar, Except as NotedSCALE: 3/8" = 1'-0"2534512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureK. LANGLOISMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.31230PERMIT SETMMA Clinic11/10/2020Federal WayFederal Way, WA 98003 8466Karsea M. LangloisSTATE OF WASHINGTONREGISTEREDARCHITECTINTERIORELEVATIONSA6.5EQUIPMENT NOTES:RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 ADA Patient Toilet (101-27)SCALE: 3/8" = 1'-0"27ADA Patient Toilet (101-28)SCALE: 3/8" = 1'-0"28Infant Scale Alcove (101-29B)SCALE: 3/8" = 1'-0"29B34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureK. LANGLOISMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.31230PERMIT SETMMA Clinic11/10/2020Federal WayFederal Way, WA 98003 8466Karsea M. LangloisSTATE OF WASHINGTONREGISTEREDARCHITECTINTERIORELEVATIONSA6.6EQUIPMENT NOTES:RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 DOOR SCHEDULETYPICAL DOOR - JAMBTYPICAL DOOR - HEAD21GENERAL NOTESCODED NOTESLEGENDDOOR TYPESDOOR FRAMESF-1ATYPICALBSURFACE-MOUNTED SLIDING BARN DOORBarn doors RO:Slab = 4'-4"Opening = 4'-0"andSlab = 3'-4"Opening = 3'-0"ENTRY DOORCO-1O-2Barn doors are AD Systems Sliders34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureK. LANGLOISMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.31230PERMIT SETMMA Clinic11/10/2020Federal WayFederal Way, WA 98003 8466Karsea M. LangloisSTATE OF WASHINGTONREGISTEREDARCHITECTDOORSCHEDULE, &DETAILSA7.0RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 FINISH SCHEDULEGENERAL NOTESCODED NOTESABBREVIATIONSMATERIALS LIST 34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureK. LANGLOISMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.31230PERMIT SETMMA Clinic11/10/2020Federal WayFederal Way, WA 98003 8466Karsea M. LangloisSTATE OF WASHINGTONREGISTEREDARCHITECTFINISHSCHEDULEA7.1RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 CROSS TEEMAIN RUNNERPARALLEL TO MAIN RUNNER,12 GA SPLAYED BRACEWIRES, TYPICALVERTICAL STRUT COMPRESSION POST TOSTRUCTURE ABOVE 12'-0" OC EACH WAY,START 6'-0" MAXIMUM FROM EDGE OF CEILINGAROUND PERIMETER - SEE STRUCTURALMIN (4) TURNSIN 1-1/2"MINIMUM 12 GA WIRE4'-0" OC, MAXIMUMLAY-IN BOARD, SEEROOM FINISH SCHEDULEPOP RIVETCROSS TEEMAXIMUM OUT OF PLUMB 1:6 - IF GREATERPROVIDE COUNTER-SLOPING WIRES6CEILING HEIGHTSPREADER BARUNATTACHED WALLAMAIN RUNNERS & CROSS TEESBATTACHED WALLC8"MAXIMUM3/4" MINMAIN RUNNERAT 4'-0" OC, MAXMINIMUM (3) TURNS IN 1-1/2"NOTE:CEILING MEMBERS MAY BE ATTACHEDTO NO MORE THAN (2) ADJACENT WALLSSEISMIC BRACINGDPARALLEL TO CROSS TEE45° MAX45° MAX45° MAX45° MAX2"HEAVY DUTY SYSTEMPARALLEL TOMAIN RUNNERPARALLEL TOCROSS TEEARMSTRONGBERC2 CLIPNOTE:SEISMIC BRACING ONLYREQUIRED IN SEISMICCATEGORIES D, E & F3" MAX3" MAXLATERAL FORCE BRACING:1. Provide lateral force bracing at 12'-0" o.c. (maximum) and begin nofarther than 6 feet from walls2.Seismic splay wires are to be four 12-gage wires attached to the mainbeam. Wires are arrayed 90 degrees from each other and at an anglenot exceeding 45 degrees from the plane of the ceiling.3.Seismic splay wires shall be attached to the grid and to the structurein such a manner that they can support a design load of not less than200 pounds or the actual design load, with a safety factor of 2,whichever is greater4."Powder-driven shot-in-anchors"PAF's), when used for seismicapplication as part of the prescriptive path in seismic designcategories D, E and F, shall have an ICC-ES approval for the seismicapplications and shall require "special inspection" irrespective of thetype of occupancy category the structure is in. PAF anchors forkicker wires (splayed wires installed for purposes other than seismicrestraint) are exempt from this requirement.5.Splay wires are to be within 2 inches of the connection of the verticalstrut to suspend ceiling.6.Rigid bracing may be used in lieu of splay wires.7.Vertical struts must be positively attached to the suspension systemsand the structure above.8.The vertical strut may be EMT conduit, metal studs or a proprietarycompression post.2" MINSPREADER BARS:1.Spreader (spacer) bars shall be used to prevent the ends of the mainbeams and cross tees at perimeter walls from spreading open duringa seismic event. Perimeter wires shall not be in lieu of spreader bars.2.Spreader bars are not required at perimeters where runners areattached directly to closure angles.3.Wire tying is an acceptable alternative to spreader bars.4.Spreader bars are not required if a 90 degree intersecting cross ormain is within 8 inches of a perimeter wall.5.Where substantiating documentation has been provided to the localjurisdiction, perimeter clips may be used to satisfy the requirementsfor spreader bars.WALL MOLDINGS:1.Wall moldings (perimeter closure angles) are required to have ahorizontal flange 2 inches wide. One end of the ceiling grid shall beattached to the wall molding, the other end shall have a 34 inchclearance from the wall and free to the side.2.Where substantiating documentation has been provided to the localjurisdiction, perimeter clips may be used to satisfy the requirementsfor the 2-inch closure angle.3.The grid shall be attached at two adjacent walls (pop rivets orapprove method). Soffits extending to a point at least level with thebottom plane of the grid and independently supported and laterallybraced to the structure above are deemed to be equivalent to walls.HANGER (SUSPENSION) WIRES:1.Hanger and perimeter wires must be plumb within 1 in 6 unlesscounter sloping wires are provided.2.Hanger wires shall be 12 gage and spaced 4 feet on center or 10gage and spaced 5 feet on center.3.Any connection device at the supporting construction shall becapable of carrying not less than 100 pounds.4.Powder-driven shot-in anchors (PAFs) are an approved method ofattachment for hanger wires.5.Terminal ends at each main beam and cross tee must be supportedwithin 8 inches of each wall with a perimeter wire.6.Wires shall not attach or bend around interfering material orequipment. A trapeze or equivalent device shall be used whereobstructions preclude direct suspension. Trapeze suspensions shallbe a minimum of back-to-back 114 inch cold-rolled channels for spansexceeding 48 inches.ELECTRICAL FIXTURES:1.Light fixtures weighing less than 10 pounds shall have one 12 gagehanger wire connected from the fixture to the structure above. Thiswire may be slack.2.Light fixtures weighing more than 10 pounds and less than 56 poundsshall have two 12 gage wires attached at opposing corners of thelight fixture to the structure above. These wires must be taut.3.Pendant mounted fixtures shall be directly attached from thestructure above using a 9 gage wire or an approved alternate supportwithout using the ceiling suspension system for direct support.4.Tandem fixtures may utilize common wires.MECHANICAL SERVICES:1.Terminals or services weighing 20 pounds, but not more than 56pounds, must have two 12 gage wires connecting them to the ceilingsystem hangers or the structure above. These wires may be slack.2.Terminals or services weighing more than 56 pounds must beindependently supported directly to the structure above. These wiresmust be taut.SEISMIC SEPARATION JOINTS: Not ApplicableSPRINKLERS:1.For ceilings without rigid bracing, sprinkler head penetrations shallhave a 2 inch oversize ring, sleeve or adapter through the ceiling tileto allow free movement of at least 1 inch in all horizontal directions.Flexible head design that can accommodate 1 inch free movementshall be permitted as an alternate.14ACOUSTICAL CEILING - TYPICALSCALE: 1-1/2" = 1'-0"13DETAIL AT CEILING TEESCALE: 1-1/2" = 1'-0"KEYED NOTES:GENERAL NOTES:5ADA DOOR - MANEUVERING SPACESCALE: 3/8" = 1'-0"4INTERIOR PARTITION TYPE 1: NR1WALL TYPESSCALE: 1/2" = 1'-0"GENERAL WALL TYPE NOTESINTERIOR PARTITION TYPE 1: PARTIAL HEIGHT1.1INTERIOR PARTITION TYPE 2: NR2INTERIOR PARTITION TYPE 3: PARTIAL HEIGHT31TYPICAL INTERIOR WALLSCALE: 1" = 1'-0"FULL HEIGHT PARTITIONSCALE: 1-1/2" = 1'-0"26PARTITION - TYPICAL SILLSCALE: 1-1/2" = 1'-0"PARTITION - TYPICAL PENETRATIONSSCALE: 1-1/2" = 1'-0"710TYP. FIBER REINFORCED LAMINATE WAINSCOTSCALE: 1-1/2" = 1'-0"TYP. VERTICAL JOINTNOT TO SCALE34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureK. LANGLOISMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.31230PERMIT SETMMA Clinic11/10/2020Federal WayFederal Way, WA 98003 8466Karsea M. LangloisSTATE OF WASHINGTONREGISTEREDARCHITECTWALL TYPES,DETAILSA8.0RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 BACKING PLATEBACKING PLATE HTS. AT CABS.1920TYPICAL CABINETS3SINK BASE CABINET11OVERHEAD CABINET16BASE CABINET1234512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureK. LANGLOISMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.31230PERMIT SETMMA Clinic11/10/2020Federal WayFederal Way, WA 98003 8466Karsea M. LangloisSTATE OF WASHINGTONREGISTEREDARCHITECTDETAILSA8.1RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 S1.1STRUCTURALGENERAL NOTES34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureRTCMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.20011-0164MMA ClinicFederal WayFederal Way, WA 98003818 Stewart Street, Suite 1000 Seattle, Washington 98101 P: (206) 332-1900 www.dci-engineers.com CIVIL / STRUCTURAL © ® FOR PERMIT These drawings are sufficiently complete for submission to the jurisdiction having authority for permit. The Contractor shall not use these drawings for construction until Contractor receives written approval for use in construction by the jurisdiction having authority and DCI Engineers.PERMIT SET11/10/2020PROFESSIONAL ENGI NE E RSTRUCTURAL ENGI NEE RRECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 S1.2STRUCTURALSPECIAL INSPECTIONSLEGEND AND ABBREVIATIONS34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureRTCMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.20011-0164MMA ClinicFederal WayFederal Way, WA 98003818 Stewart Street, Suite 1000 Seattle, Washington 98101 P: (206) 332-1900 www.dci-engineers.com CIVIL / STRUCTURAL © ® FOR PERMIT These drawings are sufficiently complete for submission to the jurisdiction having authority for permit. The Contractor shall not use these drawings for construction until Contractor receives written approval for use in construction by the jurisdiction having authority and DCI Engineers.PERMIT SET11/10/2020ABBREVIATIONSDRAWING LEGENDPROFESSIONAL ENGI NE E RSTRUCTURAL ENGI NEE RRECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 NLEVEL 1 - PLANTYPICAL NON-BEARING WALL (PER ARCH)PLAN NOTES:S2.1STRUCTURALPLAN- LEVEL 134512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureRTCMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.20011-0164MMA ClinicFederal WayFederal Way, WA 98003818 Stewart Street, Suite 1000 Seattle, Washington 98101 P: (206) 332-1900 www.dci-engineers.com CIVIL / STRUCTURAL © ® FOR PERMIT These drawings are sufficiently complete for submission to the jurisdiction having authority for permit. The Contractor shall not use these drawings for construction until Contractor receives written approval for use in construction by the jurisdiction having authority and DCI Engineers.PERMIT SET11/10/2020PROFESSIONAL ENGI NE E RSTRUCTURAL ENGI NEE RRECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 NLEVEL 1 - RCP (ROOF FRAMING) PLANXref PT4C000077-58363Xref PT4C000076-58362Xref PT4C000075-58361Xref PT4C000067-58360 Xref PT4C0 00077 -58 363Xref PT4C0 00076 -58 362Xref PT4C0 00075 -58 361Xref PT4C0 00067 -58 360 Xref PT 4C0000 77- 58363Xref PT 4C0000 76- 58362Xref PT 4C0000 75- 58361Xref PT 4C0000 67- 58360 Xref PT 4C0000 77- 58363Xref PT 4C0000 76- 58362Xref PT 4C0000 75- 58361Xref PT 4C0000 67- 58360Xref PT4C000077-58363Xref PT4C000076-58362Xref PT4C000075-58361Xref PT4C000067-58360 Xref PT4C0 00077 -58 363Xref PT4C0 00076 -58 362Xref PT4C0 00075 -58 361Xref PT4C0 00067 -58 360 Xref PT 4C0000 77- 58363Xref PT 4C0000 76- 58362Xref PT 4C0000 75- 58361Xref PT 4C0000 67- 58360 Xref PT 4C0000 77- 58363Xref PT 4C0000 76- 58362Xref PT 4C0000 75- 58361Xref PT 4C0000 67- 58360PLAN NOTES:S4.1STRUCTURALPLAN- LEVEL 1 RCP(ROOF FRAMING)34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureRTCMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.20011-0164MMA ClinicFederal WayFederal Way, WA 98003818 Stewart Street, Suite 1000 Seattle, Washington 98101 P: (206) 332-1900 www.dci-engineers.com CIVIL / STRUCTURAL © ® FOR PERMIT These drawings are sufficiently complete for submission to the jurisdiction having authority for permit. The Contractor shall not use these drawings for construction until Contractor receives written approval for use in construction by the jurisdiction having authority and DCI Engineers.PERMIT SET11/10/2020PROFESSIONAL ENGI NE E RSTRUCTURAL ENGI NEE RRECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 5OPENING IN EXISTING CMU WALL - 3'-4" MAXIMUMELEVATIONCONSTRUCTION SEQUENCE:SECTIONNOTE:12TYPICAL BOTTOM TRACK DETAIL8TYPICAL NONBEARING WALL TOP TRACK ATTACHMENT TO CONCRETE SLAB OR METAL DECK6BRACE ATTACHMENT AT NON-LOAD BEARING WALLNOTE:SECTION3TYPICAL WALL PENETRATIONS ATINTERIOR NON-BEARING WALLS7TYPICAL TRACK SPLICENOTE:4TYPICAL JAMB STUD DETAILNOTE:WELDED OPTIONSCREWED OPTION34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureRTCMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.20011-0164MMA ClinicFederal WayFederal Way, WA 98003818 Stewart Street, Suite 1000 Seattle, Washington 98101 P: (206) 332-1900 www.dci-engineers.com CIVIL / STRUCTURAL © ® FOR PERMIT These drawings are sufficiently complete for submission to the jurisdiction having authority for permit. The Contractor shall not use these drawings for construction until Contractor receives written approval for use in construction by the jurisdiction having authority and DCI Engineers.PERMIT SET11/10/2020S8.1STRUCTURALDETAILSPROFESSIONAL ENGI NE E RSTRUCTURAL ENGI NEE RRECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 84x TO 4x CONNECTION1SHEATHING CONNECTION AT OPENING2TYPICAL MECH UNIT CONNECTION4PARTIAL PLANTYPICAL FRAMING AT MECH UNITPLAN34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureRTCMARKDATEDESCRIPTIONPROJECT NAME:10 NOVEMBER 2020SHEET TITLE:SHEET #:PROJECT NO.20011-0164MMA ClinicFederal WayFederal Way, WA 98003818 Stewart Street, Suite 1000 Seattle, Washington 98101 P: (206) 332-1900 www.dci-engineers.com CIVIL / STRUCTURAL © ® FOR PERMIT These drawings are sufficiently complete for submission to the jurisdiction having authority for permit. The Contractor shall not use these drawings for construction until Contractor receives written approval for use in construction by the jurisdiction having authority and DCI Engineers.PERMIT SET11/10/2020S8.2STRUCTURALDETAILSPROFESSIONAL ENGI NE E RSTRUCTURAL ENGI NEE RRECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 GENERAL NOTES,ABBREVIATIONSAND SHEET INDEXM0.034512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003LGMECHANICAL SHEET INDEXM0.0GENERAL NOTES, ABBREVIATIONS AND SHEET INDEXM0.1LEGENDM2.0MECHANICAL SCHEDULESMD3.1MECHANICAL DEMOLITION PLANMD3.3MECHANICAL DEMOLITION ROOF PLANM3.1HVAC ZONING PLANM3.2HVAC PLANM3.3MECHANICAL ROOF PLANM7.1MECHANICAL DETAILSM8.1MECHANICAL SEQUENCE OF OPERATIONSABBREVIATIONSAAIR, AMPACUAIR CONDITIONING UNITAFFABOVE FINISHED FLOORAHUAIR HANDLING UNITALALUMINUM, ACOUSTICAL LININGARRGTARRANGEMENTATMATMOSPHEREBCBLOWER COILBDDBACKDRAFT DAMPERBFFBELOW FINISHED FLOORBFPBACKFLOW PREVENTERBHPBRAKE HORSEPOWERBLDGBUILDINGBOBBOTTOM OF BEAMBODBOTTOM OF DUCTBOSBOTTOM OF STEELBTUHBRITISH THERMAL UNITS PER HOURCAPCAPACITYCCCOOLING COILCDCEILING DIFFUSERCFMCUBIC FEET PER MINUTECHRCHILLED WATER RETURNCHSCHILLED WATER SUPPLYCICAST IRONCLGCEILING, COOLINGCNTFGL CENTRIFUGALCOCLEANOUTCONCCONCRETECONDCONDENSATECONTCONTINUE, CONTROLCOMPCOMPRESSORCOPCOEFFICIENT OF PERFORMANCECPCIRCULATING PUMPCRUCONDENSATE RETURN UNITCUCONDENSING UNITCU FTCUBIC FEETCVCONSTANT VOLUMECVTRCONVERTERCWCOLD WATERCWRCONDENSER WATER RETURNCWSCONDENSER WATER SUPPLYdBDECIBELSDBDRY BULBDCVADOUBLE CHECK VALVE ASSEMBLYDEGDEGREEDFDRINKING FOUNTAINDIDE-IONIZEDDIADIAMETERDMPRDAMPERDNDOWNDSDOWNSPOUTEEXISTINGEAEXHAUST AIREATENTERING AIR TEMPERATUREEERENERGY EFFICIENCY RATINGEFEXHAUST FANEFFEFFICIENCYEGEXHAUST GRILLEELELEVATIONEQUIPEQUIPMENTESPEXTERNAL STATIC PRESSUREEWTENTERING WATER TEMPERATUREEXHEXHAUSTEWCELECTRIC WATER COOLEREXISTEXISTINGEXPEXPANSIONEXTEXTERIOR, EXTERNALFFAHRENHEIT, FIRE LINEFDFIRE DAMPER, FLOOR DRAINFDCFIRE DEPARTMENT CONNECTIONFLAFULL LOAD AMPSFLRFLOORFLTRFILTERFMFLOW METERFOBFLAT ON BOTTOMFOFLAT OVALFOTFLAT ON TOPFPMFEET PER MINUTEFPSFEET PER SECONDFSDFIRE SMOKE DAMPERFTFEET, FAN TERMINALFVFACE VELOCITYGAGAGEGALGALLONSGALVGALVANIZEDGPMGALLONS PER MINUTEHHUMIDIFIER, HEIGHTHBHOSE BIBBHCHEATING COILHDHEADHEXHEAT EXCHANGEHOAHAND-OFF-AUTOMATICHPHORSEPOWER, HEAT PUMPHPSHIGH PRESSURE STEAMHTGHEATINGHWHOT WATERHWCHOT WATER CIRCULATINGHWPHOT WATER PUMPHWRHEATING WATER RETURNHWSHEATING WATER SUPPLYHZHERTZIDINSIDE DIAMETER, INDIRECT DRAINIEINVERT ELEVATIONIHINTAKE HOODININCHINITINITIALINTINTERIORIPLVINTEGRATED PART LOAD VALUEKWKILOWATTKWHKILOWATT HOURSLLENGTHLATLEAVING AIR TEMPERATURELBPOUND, LINEAR BARLBSPOUNDSLDLINEAR DIFFUSERLWTLEAVING WATER TEMPERATUREMAXMAXIMUMMBHTHOUSAND BTU PER HOURMCAMINIMUM CIRCUIT AMPACITYMDMANUAL DAMPERMECHMECHANICALMFRMANUFACTURERMINMINIMUMMOCPMAXIMUM OVER CURRENT PROTECTIONMODMOTOR OPERATED DAMPERMTRMOTORNCNORMALLY CLOSEDNEGNEGATIVENICNOT IN CONTRACTNONUMBER, NORMALLY OPENNTSNOT TO SCALEOAOUTDOOR AIROCON CENTERODOUTSIDE DIAMETEROPNGOPENINGORDOVERFLOW ROOF DRAINORLOVERFLOW RAIN LEADERPPUMP, PLUMBINGPDPRESSURE DROPPHPHASEPOCPOINT OF CONNECTIONPOSPOSITIVEPRPUMPED RETURNP/TPRESSURE/TEMPERATUREPVCPOLYVINYL CHLORIDEQTYQUANTITYRARETURN AIRRDROOF DRAINREFREFERENCEREQDREQUIREDRFRETURN FANRGRETURN GRILLERHRELIEF HOOD, RELATIVE HUMIDITYRLRAIN LEADERRPBFPREDUCED PRESSURE BACKFLOWPREVENTERRPMREVOLUTIONS PER MINUTESSOILSASUPPLY AIRSDSTORM DRAIN, SMOKE DAMPERSENSSENSIBLESEERSEASONAL ENERGY EFFICIENCY RATINGSFSUPPLY FAN, SQUARE FEETSGSUPPLY GRILLESLSOUNDLININGSPSTATIC PRESSURESPRSPRINKLERSSSTAINLESS STEEL, SANITARY SEWERSTPSTANDPIPETTHERMOSTATTEMPTEMPERATURETGTRANSFER GRILLETODTOP OF DUCTTOTTOTALTPTRAP PRIMER, TOTAL PRESSURETSPTOTAL STATIC PRESSURETUTERMINAL UNITTYPTYPICALUHUNIT HEATERUONUNLESS OTHERWISE NOTEDVVENT, VOLTVAVALVEVAVVARIABLE AIR VOLUMEVELVELOCITYVFDVARIABLE FREQUENCY DRIVEVTRVENT THROUGH ROOFWWASTE, WATER, WATT, WIDTHWBWET BULBWGWATER GAGEWHWATER HEATER, WALL HYDRANTWTRWATERGENERAL NOTES1.THE SCOPE OF THE MECHANICAL WORK CONSISTS OF WORK SHOWN ON THE PLANS AND AS DESCRIBED IN THESPECIFICATIONS. IN CASE OF CONFLICT, THE SPECIFICATIONS SHALL GOVERN. PROVIDE A COMPLETE &FUNCTIONAL SYSTEM.2.PERFORM ALL WORK IN ACCORDANCE WITH LOCAL CODES AND ORDINANCES. OBTAIN AND PAY FOR ALLREQUIRED PERMITS AND PAY FOR ALL FEES REQUIRED BY AUTHORITIES HAVING JURISDICTION. PAY ALLROYALTIES OR FEES REQUIRED IN CONNECTION WITH THE USE OF PATENTED DEVICES AND SYSTEMS.3.REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR GENERAL CONSTRUCTION INCLUDING LOUVERS,CONCRETE EQUIPMENT PADS, FLASHING DETAILS, ETC. REFER TO ARCHITECTURAL DRAWINGS FOR ROOMELEVATIONS, LOCATE MECHANICAL DEVICES SUCH AS TEMPERATURE SENSORS, HUMIDISTATS, PANELS, ETC.SO THAT THEY DO NOT CONFLICT WITH GENERAL CONSTRUCTION (WAINSCOT, DOOR HARDWARE, ETC.) NORWITH ELECTRICAL SYSTEM (LIGHT SWITCHES, SPEAKERS, OUTLETS, ETC.).4.COORDINATE WITH OTHER TRADES:A.REFER TO ELECTRICAL DRAWINGS AND CONFIRM ELECTRICAL CHARACTERISTICS SHOWN FORMECHANICAL EQUIPMENT (VOLTAGE, PHASE, HZ, ETC). MATCHES THAT OF THE MECHANICAL EQUIPMENTPROVIDED.B.PROVIDE ADEQUATE CLEARANCE OF MECHANICAL WORK FROM ELECTRICAL EQUIPMENT. MAINTAINMINIMUM ACCESS OF 6-INCHES ABOVE CABLE TRAYS AND 18-INCHES TO THE SIDE OF CABLE TRAYS.CLEARANCE ABOVE CABLE TRAY SHOULD BE 1/2 THE WIDTH AND NOT LESS THAN 6-INCHES WHENRUNNING PARALLEL WITH CABLE TRAY. AND NOT LESS THAN 6-INCHES WHEN RUNNING PERPENDICULARTO THE CABLE TRAY.5.ARRANGE EQUIPMENT SO THAT ACCESS CLEARANCES INDICATED BY DRAWINGS, REQUIRED BY CODES, ORRECOMMENDED BY MANUFACTURER ARE PROVIDED.6.INSTALL MATERIALS AND SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND ACCEPTEDSUBMITTALS. INSTALL MATERIAL IN PROPER RELATION TO ADJACENT CONSTRUCTION AND WITH UNIFORMAPPEARANCE FOR EXPOSED WORK.7.THOROUGHLY EXAMINE ALL AREAS WHERE EQUIPMENT, DUCTWORK, AND PIPING WILL BE INSTALLED ANDREPORT ANY CONDITION THAT PREVENTS THE PROPER INSTALLATION OF THE MECHANICAL WORK.8.COMPLY WITH WASHINGTON STATE ENERGY CODE SECTION C408.1.3 DOCUMENTATION REQUIREMENTSINCLUDING ALL LOCAL JURISDICTION AMENDMENTS. INCLUDE THE DEVELOPMENT OF CONSTRUCTION ANDAS-BUILT DRAWINGS, PROJECT MANUALS, AND SYSTEM BALANCING REPORTS.9.PURSUANT TO SECTION C408.1.3 OF THE WASHINGTON STATE ENERGY CODE, THE HVAC CONTROL SYSTEMSHALL BE TESTED TO ENSURE THAT THE CONTROL DEVICES, EQUIPMENT AND SYSTEMS ARE CALIBRATED,ADJUSTED, AND OPERATE IN ACCORDANCE WITH THE APPROVED PLANS AND SPECIFICATIONS. SEQUENCES OFOPERATION SHALL BE FUNCTIONALLY TESTED TO ENSURE THEY OPERATE IN ACCORDANCE WITH THEAPPROVED PLANS AND SPECIFICATIONS.10.THE COMMISSIONING SPECIFICATION, INCLUDING ALL FUNCTIONAL TEST PROCEDURES, SHALL BE PROVIDEDAND ENFORCED BY THE CONTRACTOR.11.PROVIDE SEISMIC RESTRAINT IN ACCORDANCE WITH IBC AND ASCE STANDARD 7. SUBMIT CALCULATIONS BYLICENSED STRUCTURAL ENGINEER. PRODUCTS MAY CONFORM TO SMACNA SEISMIC RESTRAINT GUIDELINES.12.PROVIDE A SINGLE SUBMITTAL OF ALL MECHANICAL EQUIPMENT AS SPECIFIED. AS A MINIMUM, SUBMITPRODUCT DATA FOR ALL EQUIPMENT AND FIXTURES LISTED IN ACCOMPANYING SCHEDULES FOR APPROVAL.13.USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITHMANUFACTURER'S INSTRUCTIONS.14.ARRANGEMENT OF SYSTEMS INDICATED ON THE DRAWINGS IS DIAGRAMMATIC, AND INDICATES THE MINIMUMREQUIREMENTS FOR PLUMBING AND MECHANICAL WORK. ADJUST TERMINAL UNIT LOCATIONS, BASED ON FIELDMEASUREMENTS, TO AVOID INSTALLATION ABOVE DESKS. SITE CONDITIONS SHALL DETERMINE THE ACTUALARRANGEMENT OF THE WORK. TAKE FIELD MEASUREMENTS BEFORE PREPARING SHOP DRAWINGS, OBTAINAPPROVAL OF SHOP DRAWINGS BEFORE BEGINNING FABRICATION. BE RESPONSIBLE FOR ACCURACY OFDIMENSIONS AND LAYOUT. OVERHEAD PIPING AND DUCTWORK SHALL BE ARRANGED TO OBTAIN MAXIMUMHEAD ROOM.15.CLEAN AND PROTECT WORK FROM DAMAGE. RESTORE DAMAGED FINISHES. COVER ENDS OF PIPING ANDDUCTWORK NOT ACTIVELY BEING WORKED ON.16.MODIFY AND EXTEND EXISTING SERVICE TO ACCOMMODATE NEW WORK. RELOCATE EXISTING COMPONENTSAS REQUIRED FOR NEW SYSTEM. COORDINATE WITH BUILDING MANAGEMENT.17.PROVIDE PRODUCTS OF ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILARSERVICE FOR THREE YEARS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITHMANUFACTURER'S INSTRUCTIONS.18.DO NOT CUT STRUCTURAL ELEMENTS WITHOUT PRIOR WRITTEN APPROVAL.19.CONCEAL PIPING AND DUCTWORK TO THE GREATEST EXTENT POSSIBLE.20.INSTRUCT OWNER IN PROPER OPERATION OF SYSTEMS.21.DRAWINGS DO NOT SHOW ALL OFFSETS WHICH MAY BE REQUIRED. MAKE OFFSETS WITH FITTINGS USING THELEAST ANGLE OF OFFSET POSSIBLE. DUCTWORK & PIPING SHALL BE ROUTED TO AVOID ALL STRUCTURALSUPPORTS, AND COORDINATED WITH WORK OF OTHER TRADES.22.MATERIALS, METHODS, AND INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE LATEST EDITION OFTHE FOLLOWING CODES AS ADOPTED BY THE AUTHORITY HAVING JURISDICTION. (FEDERAL WAY)2015 INTERNATIONAL BUILDING CODE (IBC)2015 INTERNATIONAL MECHANICAL CODE (IMC)2015 UNIFORM PLUMBING CODE (UPC)2015 INTERNATIONAL FIRE CODE (IFC)2015 WASHINGTON STATE ENERGY CODE (WSEC) WITH LOCAL AMENDMENTSSHEETMETAL NOTES1.PERFORM ALL SHEETMETAL WORK IN ACCORDANCE WITH CURRENT SMACNA STANDARDS.2.DUCT SEALING SHALL MEET REQUIREMENTS LISTED IN CHAPTER 6 OF IMC AND WASHINGTON STATE ENERGYCODE WITH LOCAL AMENDMENTS. IN ADDITION, PROVIDE SEAL CLASS A FOR ALL DUCTWORK.3.CONSTRUCT DUCTS WITH G-90 OR BETTER GALVANIZED STEEL (ASTM 527) LFQ.4.CONSTRUCT RECTANGULAR DUCTWORK TO MEET ALL FUNCTIONAL CRITERIA DEFINED IN CHAPTER 11, OF THESMACNA HVAC DUCT CONSTRUCTION STANDARDS. PROVIDE DIAGONAL CREASING OR BEADING ON ALL PANELSWIDER THAN 18-INCHES, AND PANELS LESS THAN 18 GAGE. CONSTRUCT ROUND AND FLAT OVAL DUCTWORK INACCORDANCE WITH CHAPTER 3 OF SMACNA HDCS.5.DUCTMATE, METU, OR W.D.C.I. DUCT CONNECTION SYSTEMS ARE ACCEPTABLE. DUCTS CONSTRUCTED USINGTHESE SYSTEMS WILL REFER TO THE MANUFACTURER'S GUIDELINES FOR SHEET GAGE, INTERMEDIATEREINFORCEMENT SIZE AND SPACING, AND JOINT REINFORCEMENTS.6.PROVIDE COLLARS WHEREVER AN EXPOSED DUCT PASSES THROUGH A WALL, SLAB, OR CEILING:1-INCH WIDE,18-GAGE ANGLE WITH MITERED CORNERS & SEAL WITH FIBERGLASS AND MASTIC.7.SPIN-IN FITTINGS SHALL BE CONICAL TYPE WITH VOLUME DAMPER, AND QUADRANT; FLEX MASTER ELGEN OREQUIVALENT.8.ELBOWS IN RECTANGULAR OR SQUARE DUCTWORK SHALL HAVE AN INSIDE RADIUS EQUAL TO DIMENSION OFELBOW IN THE PLANE OF THE TURN.9.ELBOWS IN ROUND DUCTWORK SHALL HAVE THE INSIDE RADIUS EQUAL TO DIMENSION OF ELBOW IN THE PLANEOF THE TURN. USE SEGMENTED, STANDING SEAM, PLEATED, OR STAMPED ELBOWS. ADJUSTABLE ELBOWS AREALLOWED IF RADIUS CONFORMS TO ABOVE.10.SQUARE CORNER INSERTS (TURNING VANES) SHALL BE SMACNA FIG. 4.3 DOUBLE THICKNESS, RUNNER TYPE 2WITH 2-1/8-INCH SPACING.11.VOLUME DAMPERS ARE NOT SHOWN GENERALLY. INCLUDE A DAMPER IN THE DUCT TO EACH SUPPLY, EXHAUST,OR RETURN OPENING; ALSO IN EACH BRANCH DUCT WHERE THREE OR MORE OPENINGS ARE ASSOCIATED WITHTHE BRANCH. LOCATE DAMPERS AT A POINT WHERE THE DUCT IS ACCESSIBLE; AS FAR FROM THE OUTLET ASPOSSIBLE. DO NOT PROVIDE VOLUME DAMPER ON SUPPLY DUCTWORK UPSTREAM OF TERMINAL UNITS.DAMPERS SHALL BE RUSKIN MD25 OR MDRS25.12.THOROUGHLY CLEAN ALL DEBRIS FROM THE INSIDE OF ALL DUCTWORK AND PLENUMS.13.MECHANICAL DRAWINGS SHOW APPROXIMATE LOCATIONS FOR GRILLES AND DIFFUSERS. REFER TOARCHITECTURAL REFLECTED CEILING PLANS AND ELEVATIONS FOR EXACT LOCATIONS. AFTER SHOPDRAWINGS ARE COMPLETED VERIFY EXACT LOCATION OF GRILLES AND DIFFUSERS IN THE FIELD. ENSURETHAT DIFFUSER AND GRILLE FRAMES MATCH CEILING TYPES AND FINISH PRIOR TO ORDERING.14.CONNECT FLEXIBLE DUCTS TO METAL DUCTS WITH A SLIP JOINT MADE USING FIRE RESISTANT MASTIC ANDCLAMP, IDEAL "SNAP-LOCK" OR VENTLOCK "SURETIGHT NO. 670" AT EACH END. SUPPORT IN ACCORDANCE WITHSMACNA HVAC DUCT CONSTRUCTION STANDARDS. DO NOT INSTALL WITH ABRUPT BENDS OR OFFSETS.MAXIMUM LENGTH 5-FEET. LOW PRESSURE INSULATED FLEXIBLE DUCT SHALL BE THERMAFLEX MK-E. HIGHPRESSURE INSULATED FLEXIBLE DUCT SHALL BE THERAMFLEX MK-C.REMODEL CONSTRUCTION NOTES1.DEMOLITION: WORK REQUIRED IS NOTED ON PLANS. VERIFY WITH ON SITE CONDITION AND OWNER. SALVAGEEQUIPMENT FOR OWNER'S USE AS NOTED.2.COORDINATE INTERRUPTIONS OF SERVICES PASSING THROUGH WORK AREA TO MINIMIZE DISRUPTION INADJACENT SPACES. COORDINATE WITH BUILDING OWNER.3.INSTALL NEW WORK GENERALLY AS SHOWN. ADEQUATE SPACE HAS BEEN VERIFIED TO THE DEGREEPOSSIBLE, BUT MAY REQUIRE MINOR RELOCATION OF SMALL CONDUIT AND CEILING WIRE. COORDINATEEXTENT OF RELOCATION WITH GENERAL CONSTRUCTION WORK.4.COORDINATE WORK WITH GENERAL CONSTRUCTION TO MINIMIZE DUST & DUST MIGRATION.PIPING NOTES1.SANITARY, WASTE, AND VENT PIPING (PLASTIC NOT ALLOWED) SHALL BE NO-HUB CAST IRON OR DWV COPPER.2.HOT AND COLD WATER PIPING SHALL BE HARD DRAWN COPPER TUBING: TYPE L, ASSEMBLED WITH WROTCOPPER FITTINGS AND LEAD-AND ANTIMONY-FREE SOLDER.3.INSULATE ALL HOT AND COLD WATER PIPING WITH GLASS FIBER INSULATION WITH ALL SERVICE JACKET. USEHEAT BONDING TAPE TO CLOSE INSULATION; STAPLES AND PRESSURE TAPE ARE PROHIBITED.4.PROVIDE ALL REQUIRED ACCESSORIES INCLUDING SHUT-OFFS AND CLEAN-OUTS. PROVIDE COMPONENTSWHICH PREVENT BACK-SIPHONAGE OR CROSS-CONNECTIONS. PROVIDE ISOLATION DEVICES TO REDUCESOUND TRANSMISSION.5.PROVIDE STOPS FOR EACH WATER CONNECTION TO EACH FIXTURE OR ITEM OF EQUIPMENT.6.DISINFECT WATER DISTRIBUTION SYSTEM. FLUSH AND TEST ALL SYSTEMS FOR PROPER OPERATION. ADJUSTSYSTEM TO PREVENT WATER HAMMER.7.REFER TO PIPING DIAGRAMS AND DETAILS FOR REQUIRED FITTINGS, VALVES, ETC. FLOOR PLANS ANDSECTIONS INDICATE EQUIPMENT LOCATIONS AND GENERAL PIPE ROUTING ONLY.8.REFER TO CIVIL DRAWINGS FOR UTILITY WORK 5'-0" BEYOND THE BUILDING LINE.ENERGY CODE MECHANICAL NOTES1.HEAT PUMPS HAVING SUPPLEMENTARY ELECTRIC RESISTANCE HEAT SHALL HAVE CONTROLS THAT, EXCEPTDURING DEFROST, PREVENT SUPPLEMENTARY HEAT OPERATION WHEN THE HEAT PUMP CAN MEET THEHEATING LOAD.2.WHERE USED TO CONTROL BOTH HEATING AND COOLING, ZONE THERMOSTATIC CONTROLS SHALL PROVIDE ATEMPERATURE RANGE OR DEADBAND OF AT LEAST 5°F WITHIN WHICH THE SUPPLY OF HEATING AND COOLINGENERGY TO THE ZONE IS CAPABLE OF BEING SHUT OFF OR REDUCED TO A MINIMUM.3.EACH HVAC SYSTEM SHALL HAVE CONTROLS THAT VARY THE START-UP TIME OF THE SYSTEM TO JUST MEETTHE TEMPERATURE SET POINT AT TIME OF OCCUPANCY.4.EACH ZONE SHALL BE PROVIDED WITH THERMOSTATIC SETBACK CONTROLS THAT ARE CONTROLLED BY EITHERAN AUTOMATIC TIME CLOCK OR PROGRAMMABLE CONTROL SYSTEM.5.BOTH OUTDOOR AIR SUPPLY AND EXHAUST SHALL BE EQUIPPED WITH NOT LESS THAN CLASS I MOTORIZEDDAMPERS.6.WHERE A HUMIDITY CONTROL DEVICE EXISTS IT SHALL BE SET TO MAINTAIN A DEADBAND OF AT LEAST 10%RELATIVE HUMIDITY WHERE NO ACTIVE HUMIDIFICATION OR DEHUMIDIFICATION TAKES PLACE.7.DEMAND CONTROLLED VENTILATION (DCV) SHALL BE INCLUDED FOR SPACES LARGER THAN 500 FT2 FORSIMPLE SYSTEMS AND SPACES LARGER THAN 150 FT2 FOR MULTIPLE ZONE SYSTEMS.8.ALL LONGITUDINAL AND TRANSVERSE JOINTS, SEAMS AND CONNECTIONS OF LOW-PRESSURE SUPPLY ANDRETURN DUCTS SHALL BE SECURELY FASTENED AND SEALED WITH WELDS, GASKETS, MASTICS (ADHESIVES),MASTIC-PLUS-EMBEDDED-FABRIC SYSTEMS OR TAPES INSTALLED IN ACCORDANCE WITH THEMANUFACTURER’S INSTALLATION INSTRUCTIONS.EXCEPTION(S):A.CONTINUOUSLY WELDED AND LOCKING-TYPE LONGITUDINAL JOINTS AND SEAMS ON DUCTS OPERATINGAT STATIC PRESSURES LESS THAN 2 INCHES W.G. PRESSURE CLASSIFICATION.9.PROVIDE AN OPERATING AND MAINTENANCE MANUAL TO THE BUILDING OWNER.11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 SYMBOLDESCRIPTIONSYMBOLS LEGEND - AIR HANDLINGDETAIL REFERENCESECTION REFERENCEELEVATION REFERENCE1XXX.XXXXX.XXXXX.XXSYMBOLDESCRIPTIONSYMBOLS LEGEND - GENERALSECTION IDENTIFICATION NUMBERSHEET WHERE SECTION IS DRAWNELEVATION IDENTIFICATION NUMBERSHEET WHERE ELEVATION IS DRAWNDETAIL IDENTIFICATION NUMBERSHEET WHERE DETAIL IS DRAWNA10X10000APADRRECTANGULAR TO ROUND TRANSITIONROUND BRANCH TO ROUND DUCT CONNECTIONROUND BRANCH TO RECTANGULAR DUCT CONNECTIONRECTANGULAR BRANCH TO RECTANGULAR DUCTCONNECTION WITH 45° TAPERROUND OR RECTANGULAR BRANCH TO ROUND OR RECTANGULAR DUCTCONNECTIONRECTANGULAR OR ROUND, 90° ELBOW,R/W OR R/D = 1.5POSITIVE PRESSURE DUCT - TURNING TOWARDPOSITIVE PRESSURE DUCT - TURNING AWAYNEGATIVE PRESSURE DUCT - TURNING TOWARDNEGATIVE PRESSURE DUCT - TURNING AWAYROUND DUCT - TURNING TOWARDROUND DUCT - TURNING AWAYFLAT-OVAL DUCT - TURNING TOWARDFLAT-OVAL DUCT - TURNING AWAYFLEXIBLE CONNECTIONACCESS DOOR (AD) OR ACCESS PANEL (AP)VOLUME DAMPERMOTOR OPERATED DAMPERBACKDRAFT DAMPERFLEXIBLE DUCTEQUIPMENT WITH EQUIPMENT IDENTIFICATIONTHERMOSTATCEILING SUPPLY DIFFUSERROUND, 90° ELBOW, R/W OR R/D = 1.5RECTANGULAR, 90° ELBOW, R/W OR R/D = 1.5SQUARE CORNER ELBOW WITH TURNING VANES45° BRANCH CONNECTIONTRANSITION OR REDUCER - NOTED FOT (FLAT ON TOP) OR FOB (FLAT ONBOTTOM) IF REQUIREDINCLINE RISE (R) OR DROP (D) IN DIRECTION OF ARROWCEILING RETURN DIFFUSERAIRFLOW, SUPPLYAIRFLOW, RETURNTDIFFUSER IDENTIFIERCONNECTION SIZEAIR FLOW (CFM)DIFFUSER TYPE MARKSYMBOLDESCRIPTIONSYMBOLS LEGEND - AIR HANDLINGSYMBOLDESCRIPTIONSYMBOLS LEGEND - AIR HANDLINGSYMBOLDESCRIPTIONSYMBOLS LEGEND - PIPINGSYMBOLDESCRIPTIONSYMBOLS LEGEND - PIPINGP/TPSAF/TSPIPING OR DUCTED AIRFLOWNON-DUCTED AIRFLOWELECTRICAL CONNECTIONFLOW CONTINUATION ARROWCOMPLEX INTERLOCK (ELEC., PNEUMATIC, ETC.)CONNECTION TO CENTRAL MONITORING AND CONTROL SYSTEM (CMCS)PUMPCENTRIFUGAL FANELECTRIC MOTOR/STARTER ASSEMBLYELECTRIC MOTOR OPERATOR (VALVES AND DAMPERS)FUNNEL DRAINFLOOR DRAINSYMBOLDESCRIPTIONSYMBOLS LEGEND - PIPING & AIRFLOW DIAGRAMSMMFDCFIREWET PIPE ALARM VALVEFIRE DEPARTMENT CONNECTIONPRESSURE REGULATING VALVE WITH SUPERVISORY SWITCHFSYMBOLDESCRIPTIONSYMBOLS LEGEND - FIRE PROTECTIONFLOW DIRECTIONWET SPRINKLER HEADSYMBOLSYMBOLS LEGEND - MEDICAL GASESWAGDMABZVBSYMBOLSYMBOLS LEGEND - LABORATORY++++++DRY SPRINKLER HEADFIRE DAMPERFDSDFSDSMOKE DAMPERFIRE SMOKE DAMPERFDSDFSDMMBDDBDDDRAWING CONSTRUCTION ("FLAG") NOTEMATCHLINEREVISION CLOUD (ENCIRCLES DRAWING CHANGES MADE SINCE THEPREVIOUS RELEASE)REVISION REFERENCENORTH REFERENCEEQUIPMENT IDENTIFIERPOINT OF CONNECTIONDESCRIPTIONDESCRIPTIONX-XXX-XXO2MAMVMAN2MAWAGWAGCO2N2OETOLALVFMMAVCHRHPSHWSHWRCHS120°HW140°HWIDORLRLAAVSPRSTPEXISTING TO BE REMOVED (HATCH)HEAVY LINEWEIGHT INDICATES NEW WORKLIGHT LINEWEIGHT INDICATES EXISTING INFORMATIONSOIL OR WASTEVENTRAIN LEADEROVERFLOW RAIN LEADERINDIRECT DRAINCOLD WATERHOT WATERHOT WATER CIRCULATING140° POTABLE HOT WATER120° POTABLE HOT WATERFIRESPRINKLERSTANDPIPEHIGH PRESSURE STEAMHEATING WATER SUPPLYHEATING WATER RETURNCHILLED WATER SUPPLYCHILLED WATER RETURNREDUCER, CONCENTRICWYE STRAINER WITH CAPPED HOSE END BLOWDOWN VALVEANGLE VALVEAUTOMATIC CONTROL VALVE - TWO WAY (PNEUMATIC OPERATOR SHOWN)AUTOMATIC CONTROL VALVE - THREE WAY (ELECTRIC OPERATOR SHOWN)BUTTERFLY VALVEFLEXIBLE CONNECTION IN PIPINGMANUAL AIR VENT (MAV), AUTOMATIC AIR VENT (AAV)PRESSURE GAUGETHERMOMETERTHERMOMETER WELLSIGHT GLASSHOSE BIBSTEAM TRAP ASSEMBLYF/T = FLOAT AND THERMOSTATICF = FLOATT = THERMOSTATICB = BUCKETIB = INVERTED BUCKETI = IMPULSEO = ORIFICEPIPE ANCHORPIPE ALIGNMENT GUIDECONTROL VALVE STATIONPIPE SUPPORTPRESSURE/TEMPERATURE TEST PORTCAPPLUGWYE STRAINERUNIONGATE VALVEGLOBE VALVEBALL VALVEBALANCING OR PLUG VALVENEEDLE VALVEPRESSURE REDUCING VALVEBALANCING/MEASURING VALVERELIEF VALVECHECK VALVEPIPE TURNING DOWN / AWAYPIPE TURNING UP / TOWARDSPIPE DOWN TEEPIPE DOWN TEE / AWAYPIPE UP TEE / TOWARDSLABORATORY VACUUMLABORATORY AIRNON POTABLE HOT WATER RECIRCULATENON POTABLE HOT WATERNON POTABLE COLD WATERHOSE REEL (RETRACTABLE)MEDICAL AIR PRESSURE SENSORMEDICAL GAS ALARM BOXZONE VALVE BOXMEDICAL GAS VALVE (SERVICE VALVE)ETHYLENE OXIDECARBON DIOXIDENITROGENNITROUS OXIDE (NITROUS)WASTE ANESTHETIC GAS DEVICEMEDICAL AIR OUTLETWASTE ANESTHETIC GASMEDICAL VACUUMMEDICAL COMPRESSED AIROXYGEN1NLEGENDM0.134512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003LG11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 MECHANICALSCHEDULESM2.034512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003DIFFUSER-GRILLE SCHEDULEEQUIP. NOLOCATIONSERVICEBASIS OF DESIGNMANUFACTURERBASIS OF DESIGNSERIESDESCRIPTIONMAXIMUM SOUND PRESSURE(dBA)REMARKSSG-1CEILINGSUPPLY DIFFUSERTITUSMCD4-WAY ADJUSTABLE, MODULAR CORE DIFFUSER1,2,3RG-1CEILINGRETURN GRILLETITUS50FEGGCRATE RETURN GRILLE1,3,5EG-1CEILINGEXHAUST GRILLETITUS350FLSINGLE DEFLECTION GRILLE1,6REMARKS:1. SEE MECHANICAL FLOOR PLANS FOR DUCT SIZE AND CFM.2. STEEL, WHITE, ROUND NECK, SEE MECHANICAL FLOOR PLANS FOR NECK SIZE.3. BORDER TO MATCH CEILING TYPE.4. STEEL, WHITE, 3/4" BLADE SPACING.5. STEEL, WHITE, CORE ONLY IN ACT, 1/2"X1/2"X1/2" GRID.6. ALUMINUM, WHITE, FOR GWB CEILING, 3/4" BLADE SPACING, 35 DEG. FIXED DEFLECTION.EXHAUST FAN SCHEDULEEQUIP NO.LOCATIONSERVICEBASIS OF DESIGNMANUFACTURERBASIS OF DESIGN SERIESTYPEVOLUMESTATIC PRESSUREDRIVE TYPEFAN RPMMOTORSOUND POWER BY OCTAVE BANDdBAVFDYES/NOOPERATING WEIGHT(LBS)REMARKSCFMINCHES W.G.HPRPMV/PH/HZ62.51252505001000200040008000EF-01GREENHECKAE-14-438-A5PROPELLER11500.79DIRECT17500.51750115/1/60848784767370666269YES721,2,3, 4, 5REMARKS:1. PROVIDE MANUFACTURER'S ROOF CURB TO MAINTAIN 14" CLEARANCE ABOVE FINSIHED ROOF.2. INSTALL AS PER MANUFACTURER'S RECOMMENDATIONS.3. PROVIDE WITH MANUFACTURER'S NEMA-1 SWITCH (TOGGLE).4. PROVIDE WITH VFD.5. PROVIDE MOTORIZED DAMPER IN ACCORDANCE WITH WSEC.SPLIT SYSTEM CONDENSING UNIT SCHEDULEEQUIP. NOLOCATIONSERVICEBASIS OF DESIGN MANUFACTURERBASIS OF DESIGN SERIESCOOLING CAPACITYELECTRICAL DATAMAXIMUM SOUND PRESSURE(dBA)OPERATING WEIGHT (LBS)REMARKSTOTAL COOLING LOAD(MBH)OA DESIGN TEMP(DEG F)EERCONDENSER FANCOMPRESSOR(LRA)MCAMOCPV/PH/HZMOTOR (HP)CONTROLCU-1ROOFELECTRICAL / IS&T CLOSETMITSUBISHI ELECTRICPUY369510.8132531208/1/60215CU-2ROOFMED. DIST. ROOMMITSUBISHI ELECTRICNTXSST1295138.2915208/1/6081CU-3ROOFSUPERVISOR & PROVIDER OFFICESMITSUBISHI ELECTRICNTXMPH249513----3140208/1/60190REMARKS:1. PROVIDE ROOF SUPPORT 6" ABOVE FINISHED ROOF AND 4" LARGER THAN FOOTPRINT OF EQUIPMENT ON ALL SIDES.)FAN COIL SCHEDULEEQUIP. NOLOCATIONSERVICEBASIS OF DESIGNMANUFACTURERBASIS OF DESIGN SERIESTYPESUPPLY AIRFLOW(CFM)MIN OUTSIDE AIRFLOW(CFM)EXT SP(IN WG)COOLING CAPACITYHEATING CAPACITYELECTRICAL DATAMAXIMUM SOUNDPRESSURE (dBA)OPERATING WEIGHT(LBS)REMARKSCOOLING LOADOA DESIGN TEMP(DEG F)TOTAL LOAD(MBH)OA DESIGN TEMP(DEG F)MCAMOCPV/PH/HZTOTAL LOAD(MBH)SENSIBLE LOAD (MBH)FC-1ELECTRICAL/ IS&T CLOSETElectrical/ IS&T ClosetMITSUBISHINTXWSTWALL MOUNTED3500N/A36N/A9514.420130208/1/6045461FC-2MED. DIST. ROOMMITSUBISHINTXCKSCEILING MOUNTED3350N/A12N/A951220115208/1/6034501FC-3PROVIDER OFFICEMITSUBISHINTXCKSCEILING MOUNTED3350N/A12N/A951220115208/1/6034501FC-4SUPERVISOR'S OFFICEMITSUBISHINTXCKSCEILING MOUNTED3350N/A12N/A951220115208/1/6034501REMARKS: OUTSIDE IS PROVIDED TO THE SUITE THROUGH THE EXISTING ROOF TOP UNITS.EXISTING PACKAGED ROOFTOP AC UNIT SCHEDULEEQUIP. NOLOCATIONBASIS OF DESIGN MANUFACTURERBASIS OF DESIGN SERIESNOMINAL CAPACITY(TONS)SUPPLY AIRFLOW(CFM)MIN OUTSIDE AIR(CFM)ECONOMIZERELECTRICALOPERATING WEIGHT(LBS)REMARKSMCAV/PH/HZRTU-4ROOFTRANEYSC04841640695YES24356591RTU-5ROOFTRANEYSC04841510280YES24356591RTU-6ROOFTRANEYSC04841415265YES24356591RTU-7ROOFTRANEYSC04841540590YES24356591REMARKS:1.REBALANCE RTU'S TO THE SCHEDULED AIRFLOW. PROVIDE NEW MERV 8 PRE-FILTERS.LGDUCT SYSTEMS INSULATION SCHEDULE - CLIMATE ZONE 4LOCATION OF DUCTDUCT SYSTEM TYPEDUCT CONFIGURATIONINSULATION TYPEMINIMUM R-VALUE, INSULATIONTHICKNESSREMARKSDUCT NOT WITHIN CONDITIONEDSPACESUPPLY, RETURN, EXHAUST, MIXED,OUTSIDE, AND TRANSFER AIR DUCTSRECTANGULAR - EXPOSEDRIGID BOARDR-7, 1 LAYER, 2 INCH THICKRECTANGULAR - CONCEALEDDUCT WRAPR-7, 1 LAYER, 3 INCH THICKROUND AND OVALDUCT WRAPR-7, 1 LAYER, 3 INCH THICKDUCT WITHIN CONDITIONEDSPACESUPPLY, RETURN, EXHAUST, MIXED,OUTSIDE, AND TRANSFER AIR DUCTSRECTANGULAR - EXPOSEDRIGID BOARDR-7, 1 LAYER, 2 INCH THICKRECTANGULAR - CONCEALEDDUCT WRAPR-7, 1 LAYER, 3 INCH THICKROUND AND OVALDUCT WRAPR-7, 1 LAYER, 3 INCH THICKREMARKS:1. INSULATE OUTSIDE, EXHAUST, AND RELIEF AIR DUCTS FROM BUILDING ENVELOPE TO BACKDRAFT MOTORIZED DAMPER WITH R-VALUE EQUAL TO BUILDING ENVELOPE THICKNESS.2. REQUIREMENTS APPLY TO THE DUCT TYPE LISTED, WHETHER HEATED OR MECHANICALLY COOLED DUCTS REQUIRING INSULATION SHALL HAVE A VAPOR RETARDER, WITH A PERM RATING NOT GREATER THAN 0.5 AND ALL JOINTS SEALED.3. R-3; 1.0 INCH TO 3.0 LB/FT3 DUCT LINER, MINERAL OR GLASS FIBER BLANKET OF EQUIVALENT TO PROVIDE AND INSTALLED TOTAL THERMAL RESISTANCE OF AT LEAST R-33.4. R-5.3; 2.0 INCH 0.75 LB/FT3 MINERAL OR FIBER GLASS BLANKET, 1.5 INCH, 1.5 TO 3.0 LB/FT3 DUCT LINER, MINERAL OR GLASS FIBER BLANKET, 2.0 INCH 3.0 TO 7.0 LB/FT3 MINERAL OR GLASS FIBER BOARD OR EQUIVALENT TO PROVIDE AN INSTALLED TOTALTHERMAL REISTANCE OF AT LEAST R-5.3.5. R-7; 3.0 INCH 0.75 LB/FT3 MINERAL OR FIBER GLASS BLANKET, 2.0 INCH, 1.5 TO 3.0 LB/FT3 DUCT LINER, MINERAL OR GLASS FIBER BLANKET, 2.0 INCH 3.0 TO 7.0 LB/FT3 MINERAL OR GLASS FIBER BOARD OR EQUIVALENT TO PROVIDE AN INSTALLED TOTAL THERMALREISTANCE OF AT LEAST R-7.11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 ABCDE4321TTTTSHEET NOTES1.ALL EQUIPMENT, PIPING,DUCTWORK, CONTROLS ANDOR WIRING SHOWN IS AREPRESENTATION OF THEACTUAL SYSTEMS AND IS NOTTO BE CONSIDERED ANAS-BUILT. ALL DIMENSIONS,LOCATIONS AND QUANTITIESSHALL BE FIELD VERIFIEDPRIOR TO COMMENCEMENT OFDEMOLITION OR NEWCONSTRUCTION.2.UPON REMOVAL OF EXISTINGEQUIPMENT, PIPING,DUCTWORK, ETC., THECONTRACTOR SHALL PATCHANY EXISTING ROOF, WALL,FLOOR, AND OR CEILINGASSEMBLIES 8" AND SMALLERTHAT ARE NOT SLATED FORRE-USE.3.CONTRACTOR SHALL BERESPONSIBLE FOR SITEVERIFICATION.MECHANICALDEMOLITION PLANMD3.134512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003SCALE:NMECHANICAL DEMOLITION PLAN 1/4"=1'-0"DEMOLISH ALL EXISTING DUCTWORK TOPOINT OF RISERS TO ROOF. DEMOLISHEXISTING GRILLES AND DIFFUSERS. SEESHEET M3.1 FOR EXTENT OF NEW WORK.2'8'SCALE: 1/4" = 1'-0"1'4'0'LG11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 ABCDE4321Xref PT4C000077-58363Xref PT4C000076-58362Xref PT4C000075-58361Xref PT4C000067-58360Xref PT4C000077-58363Xref PT4C000076-58362Xref PT4C000075-58361Xref PT4C000067-58360 Xref PT 4C0000 77- 58363Xref PT 4C0000 76- 58362Xref PT 4C0000 75- 58361Xref PT 4C0000 67- 58360 Xref PT4C 00007 7-58 363Xref PT4C 00007 6-58 362Xref PT4C 00007 5-58 361Xref PT4C 00006 7-58 360 MECHANICALDEMOLITIONROOF PLANMD3.334512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003SCALE:NMECHANICAL DEMOLITION ROOF PLAN 1/4"=1'-0"EXISTING AC UNITSTO REMAIN (TYP.)AC-7AC-6AC-5AC-4DEMOLISH ROOF JACK2'8'SCALE: 1/4" = 1'-0"1'4'0'LG11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 ABCDE4321AC-6 ZONEAC-4 ZONEAC-5 ZONEElectrical/IS&TCloset101-22126 SFCleanSupply/Equip. Room101-23180 SFExamRoom #10101-32119 SFExamRoom #8101-3195 SFBiohazard/SoiledHolding101-11110 SFRegistration101-03176 SFWaiting101-02400 SFADAPublicToilet101-0454 SFMA WorkStations101-16371 SFWCAlcove101-01A18 SFProviderOffice101-15119 SFLab101-07285 SFEntryVestibule101-0186 SFExamRoom #11101-33100 SFExamRoom #6101-3095 SFExamRoom #1101-2595 SFExamRoom #3101-2495 SFADAPatientToilet101-0869 SFBariatricExamRoom #2101-20114 SFMed.Dist.Room101-1873 SFConsultRoom #1101-26101 FInfantScale101-29ASupervisor'sOffice101-13102 SFProviderOffice101-17129 SFExamRoom #9101-3495 SFExamRoom #7101-3595 SFExamRoom #5101-3695 SFStaffLounge101-09219 SFLabWaiting101-06A30 SFVitalsArea #1101-05A26 SFBariatricExamRoom #4101-21114 SFVitalsArea #2101-14A17 SFDrawStation #2101-07BLabCheck-in101-02A31 SFConsultRoom #2101-37108 SFDrawStation #1101-07AADAPatientToilet101-2756 SFADAPatientToilet101-2856 SFPrint101-29BPrint101-19AHall101-29Hall101-19Hall101-05Hall101-14Hall101-06ADAStaffToilet101-1048 SFEVSCloset101-1212 SFPrint101-29CFC-2 ZONEFC-1 ZONEAC-7 ZONEFC-4 ZONEFC-3 ZONE34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003HVAC ZONINGPLANM3.1SCALE:NHVAC ZONING PLAN 1/4"=1'-0"2'8'SCALE: 1/4" = 1'-0"1'4'0'LG11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 ABCDE4321TTTTTTElectrical/IS&TCloset101-22126 SFCleanSupply/Equip. Room101-23180 SFExamRoom #10101-32119 SFExamRoom #8101-3195 SFBiohazard/SoiledHolding101-11110 SFRegistration101-03176 SFWaiting101-02400 SFADAPublicToilet101-0454 SFMA WorkStations101-16371 SFProviderOffice101-15119 SFLab101-07285 SFEntryVestibule101-0186 SFExamRoom #11101-33100 SFExamRoom #6101-3095 SFExamRoom #1101-2595 SFExamRoom #3101-2495 SFADAPatientToilet101-0869 SFBariatricExamRoom #2101-20114 SFMed.Dist.Room101-1873 SFConsultRoom #1101-26101 FInfantScale101-29ASupervisor'sOffice101-13102 SFProviderOffice101-17129 SFExamRoom #9101-3495 SFExamRoom #7101-3595 SFExamRoom #5101-3695 SFStaffLounge101-09219 SFLabWaiting101-06A30 SFVitalsArea #1101-05A26 SFBariatricExamRoom #4101-21114 SFVitalsArea #2101-14A17 SFDrawStation #2101-07BConsultRoom #2101-37108 SFDrawStation #1101-07AADAPatientToilet101-2756 SFADAPatientToilet101-2856 SFPrint101-29BPrint101-19AHall101-29Hall101-19Hall101-05Hall101-14Hall101-06ADAStaffToilet101-1048 SFEVSCloset101-1212 SFPrint101-29CT14"Ø SA8"Ø SA14"Ø SA 16"X14" SA16"X12" RA8"Ø EA12"Ø EA8"Ø EA12"Ø EA10"Ø RA12"Ø RA12"Ø SA6"Ø EA14"X14" UPTO EF-1SG-18"Ø190SG-18"Ø185RG-110"Ø375SG-18"Ø140RG-18"Ø165SG-18"Ø100EG-18"Ø125SG-112"Ø405EG-112"Ø450EG-16"Ø50RG-18"Ø105SG-18"Ø130SG-18"Ø105SG-18"Ø105SG-110"Ø225RG-110"Ø330RG-16"Ø105SG-110"Ø225SG-110"Ø225SG-110"Ø215RG-110"Ø215SG-110"Ø230SG-110"Ø295RG-112"Ø475SG-110"Ø225SG-110"Ø225SG-110"Ø225RG-112"Ø450RG-112"Ø450SG-110"Ø330SG-16"Ø70SG-18"Ø10514"Ø SA16"X14" RA 18"X14" SA 6"Ø SA10"Ø SA10"Ø SA10"Ø SA12"Ø SA10"Ø RA12"Ø RA12"Ø RA12"Ø EA10"Ø EA8"Ø EA10"Ø SA10"Ø SA10"Ø SA10"Ø SA10"Ø RA10"Ø SA12"Ø SASG-18"Ø165SG-18"Ø165RG-112"Ø575EG-18"Ø165SG-18"Ø165SG-18"Ø165SG-18"Ø105RG-18"Ø105RG-16"Ø75RG-18"Ø105RG-18"Ø105RG-18"Ø105SG-18"Ø105SG-18"Ø105RG-18"Ø105SG-18"Ø105RG-18"Ø105RG-16"Ø70SG-18"Ø105EG-18"Ø130SG-16"Ø70SG-18"Ø105SG-18"Ø105RG-18"Ø105SG-18"Ø105SG-18"Ø105SG-16"Ø75RG-18"Ø105SG-18"Ø105RG-18"Ø105SG-18"Ø105SG-18"Ø105(2 TYP.)(2 TYP.)RG-18"Ø1058"Ø SA8"Ø SA16"X14" SA14"Ø RA16"X16" RA 8"Ø RA8"Ø RA8"Ø RA8"Ø RA8"Ø RA8"Ø RA8"Ø RA8"Ø RA8"Ø RA10"Ø RA6"Ø RA8"Ø RA8"Ø RA8"Ø RA8"Ø RA10"Ø RA10"Ø SA8"Ø SA8"Ø SA8"Ø RA8"Ø SA8"Ø SA6"Ø RA16"X16" SA12"Ø RA14"Ø SA8"Ø SA12"Ø SA8"Ø RA8"Ø SA16"X14" SA 8"Ø SA10"Ø SA10"Ø SA6"Ø SA12"Ø SA14"Ø RA18"X14" SA 16"X14" SA 8"Ø SA8"Ø SA16"X14" SA8"Ø SA8"Ø SA8"Ø SA10"Ø SASHEET NOTES1.ELEVATIONS OF THERMOSTATSAND SENSORS SHALL BE PERTHE ARCHITECTURAL INTERIORELEVATION DRAWINGS.THERMOSTATS SHALL NOT BELOCATED ON EXTERIOR WALLSUNLESS DIRECTED OTHERWISE.REFER TO MECHANICALDRAWINGS FOR THERMOSTATAND SENSOR LOCATIONS.FLAG NOTESEXISTING 24"X14" RETURN DUCT UPTO AC-7.EXISTING 16"x14" SUPPLY DUCT UPTO AC-7.EXISTING RETURN DUCT UP TO AC-6.EXISTING SUPPLY DUCT UP TO AC-6.EXISTING RETURN DUCT UP TO AC-5.EXISTING SUPPLY DUCT UP TO AC-5.EXISTING RETURN DUCT UP TO AC-4.EXISTING SUPPLY DUCT UP TO AC-4.1234512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003HVAC PLANM3.2SCALE:NHVAC PLAN 1/4"=1'-0"FC-1AC-6AC-7FC-4AC-5FC-2AC-412 345678 3456782'8'SCALE: 1/4" = 1'-0"1'4'0'FC-35/8" RS & 3/8" RLUP TO CU-13/8" RS & 1/4" RL UP TO CU-33/8" RS & 1/4" RL UP TO CU-23/8" RS & 1/4" RL UP TO CU-3FC-2FC-3FC-4LG11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 ABCDE4321Xref PT4C000077-58363Xref PT4C000076-58362Xref PT4C000075-58361Xref PT4C000067-58360Xref PT4C000077-58363Xref PT4C000076-58362Xref PT4C000075-58361Xref PT4C000067-58360 Xref PT4C00 0077 -583 63Xref PT4C00 0076 -583 62Xref PT4C00 0075 -583 61Xref PT4C00 0067 -583 60 Xre f PT4C000 077 -5836 3 Xre f PT4C000 076 -5836 2 Xre f PT4C000 075 -5836 1 Xre f PT4C000 067 -5836 0Xref PT4C000077-58363Xref PT4C000076-58362Xref PT4C000075-58361Xref PT4C000067-58360Xref PT4C000077-58363Xref PT4C000076-58362Xref PT4C000075-58361Xref PT4C000067-58360 Xref PT4C00 0077 -583 63Xref PT4C00 0076 -583 62Xref PT4C00 0075 -583 61Xref PT4C00 0067 -583 60 Xre f PT4C000 077 -5836 3 Xre f PT4C000 076 -5836 2 Xre f PT4C000 075 -5836 1 Xre f PT4C000 067 -5836 0 MECHANICAL ROOFPLANM3.334512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003SCALE:NMECHANICAL ROOF PLAN 1/4"=1'-0"(E)AC-4CU-1EF-185#75#(E)AC-5(E)AC-6(E)AC-7670#670#670#670#190#CU-310'-0" OSA CLEARANCE. ALL EXHAUST FANSAND PLUMBING VENTS TO REMAIN OUTSIDEOF THIS CIRCLE (TYP.)SHEET NOTES1.CONTRACTORS SHALLCOORDINATE FINAL LOCATIONOF ALL ROOF MOUNTEDEQUIPMENT WITHARCHITECTURAL ANDSTRUCTURAL DRAWINGS.5/8" RS & 3/8" RL DOWN TO FC-13/8" RS & 1/4" RL DOWN TO FC-43/8" RS & 1/4" RL DOWN TO FC-23/8" RS & 1/4" RL DOWN TO FC-32'8'SCALE: 1/4" = 1'-0"1'4'0'89#CU-2LG11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 MECHANICALDETAILSM7.134512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003SPIN-IN FITTING WITHVOLUME DAMPERSUPPLY DUCTCLAMP (TYP.)SCALE:NTSCEILING DIFFUSER DETAIL1DIFFUSER NECK, SEE PLANSFOR SIZELAY-IN T-BAR CEILING SHOWN,VERIFY TYPE OF CEILING. SEESCHEDULESECURE ELBOW TO DIFFUSER WITH AMINIMUM OF 4 SHEETMETAL SCREWSSHEETMETAL ELBOW, CENTERLINE RADIUS 1.5 X THE DIAMETEROF THE DUCT. NOTE: WHERE CENTERLINE RADIUS (1.5 X THEDIAMETER OF THE DUCT) CAN NOT BE MAINTAINED SHORTRADIUS SHORT RADIUS RIGID METAL ELBOW MAY BE USED.STRAP HANGER, 1" WIDE. BOLT AROUND DUCT ANDEXTEND A SINGLE STRAP UP TO STRUCTURE ADJUSTSUPPORT TO RELIEVE STRAIN FROM DIFFUSERINSULATED FLEXIBLE DUCT MAX. 5'-0"CEILINGLINE OF SIGHT INTERNAL LINING /INSULATIONSHEETMETAL PLENUMLAY- IN T- BAR CEILING SHOWN,VERIFY TYPE OF CEILINGSCALE:NTSRETURN AIR GRILLE DETAIL2STRAP OR ROD SUPPORT TOSTRUCTURE. ADJUST TORELIEVE ANY STRESS ON GRILLERETURN / EXHAUST GRILLE. SEE FLOOR PLANS ANDSCHEDULES FOR STYLE, SIZE AND FLOW RATEPLENUM SIZE SAME AS GRILLE (INLET & OUTLET).HANGER RODSW / OR W / OUT TYPE 48 SPRINGISOLATOR AS REQUIRED PERSPECIFICATIONSW / OR W / OUT PROTECTIVESADDLE OR SHIELD AS REQUIREDANGLE IRON ORUNISTRUT TYPE SUPPORTINSULATE PIPE AS REQUIREDBY SPECIFICATIONSNON-INSULATED PIPEHYDRONIC PIPINGINSULATION AND VAPOR BARRIERAS REQUIRED BY SPECIFICATIONSATTACH TO STRUCTURETYPE 1 CLEVIS HANGERINSULATE ASREQUIRED BY CODEATTACH TO STRUCTURENOT TO ROOF DECK (TYP)W / OR W / OUT PROTECTIVESADDLE OR SHIELD AS REQUIREDW / OR W / OUT TYPE 48 SPRINGISOLATOR AS REQUIRED PERSPECIFICATIONSNOTES:1.SIZE RODS, SPRING CUSHION, ANDHORIZONTAL MEMBER APPROVED TOSATISFY LOAD REQUIREMENT W / SAFETYFACTOR OF 5.2.DO NOT EXCEED ALLOWABLE LOAD LIMITS.ROOFSHEET METAL SHOEFOR PIPE >= 2-/2"ØMANUFACTUREDPIPE SUPPORT1" MIN. THICKNESSSCALE:NTSPIPING SUPPORT DETAIL3WALL SLEEVEREFRIGERANT LINEFLARED CONNECTIONINSULATED FLEXIBLE DRAINHOSE. INSERT SECURELYINTO CONDENSATE DRAINPIPE.POWER AND CONTROLWIRING (LINE VOLTAGE)CONDENSATE DRAIN PIPE.ROUTE CONDENSATE TONEAREST DRAIN.INSULATED REFRIGERANTPIPING TO OUTDOOR UNITFAN COIL UNITSCALE:NTSINDOOR SPLIT-SYSTEM WALL MOUNT4NOTES:1.CONSTRUCTION HOUSING AND TOP OF 22 GA SS. ALL JOINTS AND SEAMS SHALL BEWELDED OR SOLDERED WATER TIGHT. CROSSBREAK OR SLOPE TOP FOR DRAINAGE.2.VERIFY DIMENSIONS REQUIRED TO CONFORM WITH ACTUAL PIPE AND/OR INSULATIONSIZES AND QUANTITIES.3.VERIFY ROOF OPENING SIZE WITH ARCHITECTURAL AND/OR STRUCTURAL.SCALE:NTSROOF PENETRATION DETAIL - PIPING5REFER TO ARCHITECTURALFOR ROOF DECK, CURB,INSULATION, VAPOR BARRIER,ETC. MATERIALS ANDINSTALLATIONSCREWS ON EACH OF 3 SIDES (MIN).LOCATE SCREWS 6" FROM END AND 12"O.C.6"1/2" MAX.SLOPE PIPES AWAYFROM HOODSTAINLESSSTEEL SCREWSPROVIDE LOOSEFIT JOINTNOTES:1.MAINTAIN ACCESS CLEARANCES FOR SERVICE OF FILTERS, AND BLOWER. ALLOW MINIMUM 42" TO ALLACCESS PANELS.2.INSTALL PER MANUFACTURER'S WRITTEN INSTRUCTIONS.3.MECHANICAL CONTRACTOR'S SEISMIC ENGINEER TO PROVIDE DETAIL OF ISOLATORS AND SWAYBRACING.SUPPLYDUCT - SIZEAS SHOWNON PLANDUCT HANGER STRAP(TYP), CONNECT TOSTRUCTUREFLEXIBLECONNECTION (TYP)RETURN/OUTSIDEAIR DUCT - SIZEAS SHOWN ONPLANSHVACEQUIPMENTTHREADED ROD; SIZE PERSPECIFICATIONS. ATTACH TOSTRUCTURE (TYPICAL)SPRING VIBRATION ISOLATOR(TYPICAL) LOCATE NEAR CEILING.SEE ISOLATION SPECIFICATIONSSEE SPECIFICATIONS FORSEISMIC BRACINGSCALE:NTSABOVE CEILING EQUIPMENT DETAIL6PENETRATION AND CURB DETAILS,REFER TO ARCHITECTURAL ROOFSHEET A5.16SCALE:NTSROOF MOUNTED CONDENSING UNIT7SCALE:NTSROOF EXHAUST FAN W/ CURB DETAIL8MIN 18" CURB HEIGHT ABOVEROOFBACKDRAFT DAMPER /MOTORIZED WHERE NOTEDIN SPEC.PREFABRICATED AND INSULATED CURB PER DIV 23FLASHING AND COUNTER FLASHING BY OTHERS.EXHAUST FAN. SEEEF SCHEDULE FOR SIZEAND TYPESCREW DUCT TO CURBSEAL ROOF PENETRATION W/FLEXIBLE CAULKINGSHEET METAL DUCTATTACH TO HOODANCHOR CABLES W/EYELETSATTACH TO CURB2" ELASTOMERIC FOAM INSULATION FULL WIDTH AND LENGTH OF CURB.ACCOUSTICAL CAULK ALL AROUND 12" MINIMUM3"x3"x18 GAUGE ANGLE FRAME ALL AROUNDHANGER (TYPICAL)12"MINIMUMMETAL DUCTWALLSCALE:NTSDUCT PENETRATION THRU NON-RATED WALL9LGCONDENSING UNITNEOPRENE PAD AT UNITMOUNTSINSULATED REFRIGERANTPIPING WITH SLEEVESHEET METAL ENCLOSUREEQUIPMENT CURB. INSTALLEQUIPMENT AND CURB LEVEL.ROOF FLASHINGSECURE TO CURB PER MANUFACTURER'S INSTALLATIONINSTRUCTIONS. APPLY SEALANT AT FASTENERS.18 GAUGE GALVANZIED SHEET METALCAP. OVERLAP CURB MIN 2".CANT STRIPROOF MATERIALROOF INSULATIONROOF DECK11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 MECHANICALSEQUENCE OFOPERATIONSM8.134512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003SEQUENCE OF OPERATION - SPIT HEAT PUMP UNITSPLIT SYSTEM HEAT PUMP UNIT, FC-1, FC-2, FC-3 & FC-4 AND CU-1, CU-2, & CU-3THE IS&T ROOM IS BOTH HEATED AND COOLED BY A WALL MOUNTED INDOOR SPLIT SYSTEM HEAT PUMP FAN COIL. A ROOF MOUNTED OUTDOOR CONDENSING UNIT, CU-1, ISINTERLOCKED WITH THE INDOOR UNIT, FC-1. THE MEDICINE ROOM, PROVIDER OFFICE, & SUPERVISOR OFFICE, & ARE HEATED AND COOLED BY A CEILING CASSETTE INDOOR SPLITSYSTEM HEAT PUMP FAN COIL. A ROOF MOUNTED OUTDOOR CONDENSING UNIT, CU-2, IS INTERLOCKED WITH THE INDOOR UNIT, FC-2. A ROOF MOUNTED OUTDOOR CONDENSING UNIT,CU-3 IS INTERLOCKED WITH THE INDOOR UNITS FC-3 & FC-4. HEAT PUMPS SHALL OPERATE WHEN EITHER OF THE SPACES ARE IN NEED OF HEATING OR COOLING. THE UNITS SHALLRUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES:1.OCCUPIED MODE -THE UNIT SHALL MAINTAIN75 DEG F COOLING SET POINT (ADJUSTABLE)70 DEG F HEATING SET POINT (ADJUSTABLE)2.UNOCCUPIED MODE - THE UNIT SHALL MAINTAIN85 DEG F COOLING SET POINT (ADJUSTABLE)55 DEG F HEATING SET POINT (ADJUSTABLE)SET POINT ADJUST:THE OCCUPANTS SHALL BE ABLE TO ADJUST THE ROOM TEMPERATURE HEATING AND COOLING SET POINTS AND SHALL BE ABLE TO OVERRIDE AUTOMATIC OPERATION THROUGH THEROOM SENSORS.UNOCCUPIED OVERRIDE:A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE SCHEDULE AND PLACE THE UNIT INTO AN OCCUPIED MODE FOR AN ADJUSTABLE PERIOD FO TIME.AT THE EXPIRATION OF THIS, CONTROL OF THE UNIT SHALL AUTOMATICALLY RETURN TO THE SCHEDULE.THE SYSTEM SHALL BE CONNECTED TO THE BUILDING DELTA DDC CONTROL SYSTEM. MONITOR THE FOLLOWING FAN COIL POINTS:1.FC-1, FC-2, FC-3, & FC-4 OPERATION2.ROOM TEMPERATURE SET-POINTS3.ROOM TEMPERATURES4.DISCHARGE AIR TEMPERATURE5.FAN STATUSMONITOR THE FOLLOWING OUTDOOR CONDENSING UNIT POINTS:1.CU-1, CU-2, & CU-3 OPERATION2.FAN STATUS3.FREEZE STATFAN:THE FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN, UNLESS SHUTDOWN ON SAFETIES. THE FAN SPEEDS SHALL BE INDEXED AS FOLLOWS:1.LOW SPEED SHALL RUN ANYTIME THE ROOM TEMPERATURES ARE WITHIN SET POINTS.2.MEDIUM SPEED SHALL RUN ANYTIME THE ROOM TEMPERATURES ARE OUTSIDE OF SET POINTS.3.HIGH SPEED SHALL RUN ANYTIME THE ROOM TEMPERATURES ARE OUTSIDE OF SET POINTS BY A USER DEFINABLE AMOUNT (ADJ.).THE HEATING SHALL BE ENABLED WHENEVER:1.THE HEAT PUMP IS IN HEATING MODE AND THE ROOM TEMPERATURES ARE BELOW HEATING SET POINT AND THE FAN IS ON.HEATING AND COOLING - COMPRESSOR STAGE:1.THE CONTROLLER SHALL MEASURE THE ROOM TEMPERATURES AND CYCLE THE COMPRESSOR TO MAINTAIN ITS SET POINT. TO PREVENT SHORT CYCLING, THE STAGESHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME. THE COMPRESSOR SHALL RUN SUBJECT TO ITS OWN INTERNAL SAFETIES AND CONTROLS.2.THE HEATING SHALL BE ENABLED WHENEVER THE OUTSIDE AIR TEMPERATURE IS LESS THAN 65°F (ADJ.) AND THE FAN IS ON AND THE REVERSING VALVE IS IN HEAT MODE.3.THE COOLING SHALL BE ENABLED WHENEVER THE OUTSIDE AIR TEMPERATURE IS GREATER THAN 60°F (ADJ.) AND THE FAN IS ON AND THE REVERSING VALVE IS IN COOL MODE4.ON MODE CHANGE, THE COMPRESSOR SHALL BE DISABLED AND REMAIN OFF UNTIL AFTER THE REVERSING VALVE HAS CHANGED POSITION.DISCHARGE AIR TEMPERATURE:THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE:THE FOLLOWING SHALL SEND AN ALARM SIGNAL TO THE BUILDING DELTA DDC CONTROL SYSTEM:1.FC-1, FC-2, FC-3, & FC-4 FAIL STATUS2.CU-1, CU-2, & CU-3 FAIL STATUS3.ROOM TEMPERATURES ABOVE SET POINT BY A USER DEFINABLE AMOUNT4.ROOM TEMPERATURES BELOW SET POINT BY A USER DEFINABLE AMOUNT5.COMPRESSOR RUNTIME EXCEEDED: THE COMPRESSOR RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.).6.HIGH DISCHARGE AIR TEMPERATURE, 120°F (ADJ.)7.LOW DISCHARGE AIR TEMPERATURE, 40°F (ADJ.)THE FOLLOWING SHALL CAUSE THE HEAT PUMP UNIT AND AIR HANDLING UNIT TO SHUT-DOWN:1.OPERATOR COMMAND2.SMOKE DETECTOR3.FIRE ALARM4.FREEZE STAT STATUSMSCALE:NTSSPLIT SYSTEM HP - DDC - (SINGLE COMPRESSOR) P&ID1MMMMSCALE:NTSEXISTING PACKAGED DX UNIT - DDC - (SINGLE COMPRESSOR) P&ID2RH11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 GENERAL NOTES,ABBREVIATIONS, &SHEET INDEXP0.034512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003PLUMBING SHEET INDEXP0.0GENERAL NOTES, ABBREVIATIONS, & SHEET INDEXP0.1LEGENDP2.0PLUMBING SCHEDULESPD3.1PLUMBING DEMOLITION PLANP3.1PLUMBING UNDERGROUND PLANP3.2PLUMBING PLANP3.3PLUMBING ROOF PLANP7.1PLUMBING DETAILSABBREVIATIONSAAIR, AMPACUAIR CONDITIONING UNITAFFABOVE FINISHED FLOORAHUAIR HANDLING UNITALALUMINUM, ACOUSTICAL LININGARRGTARRANGEMENTATMATMOSPHEREBCBLOWER COILBDDBACKDRAFT DAMPERBFFBELOW FINISHED FLOORBFPBACKFLOW PREVENTERBHPBRAKE HORSEPOWERBLDGBUILDINGBOBBOTTOM OF BEAMBODBOTTOM OF DUCTBOSBOTTOM OF STEELBTUHBRITISH THERMAL UNITS PER HOURCAPCAPACITYCCCOOLING COILCDCEILING DIFFUSERCFMCUBIC FEET PER MINUTECHRCHILLED WATER RETURNCHSCHILLED WATER SUPPLYCICAST IRONCLGCEILING, COOLINGCNTFGL CENTRIFUGALCOCLEANOUTCONCCONCRETECONDCONDENSATECONTCONTINUE, CONTROLCOMPCOMPRESSORCOPCOEFFICIENT OF PERFORMANCECPCIRCULATING PUMPCRUCONDENSATE RETURN UNITCUCONDENSING UNITCU FTCUBIC FEETCVCONSTANT VOLUMECVTRCONVERTERCWCOLD WATERCWRCONDENSER WATER RETURNCWSCONDENSER WATER SUPPLYdBDECIBELSDBDRY BULBDCVADOUBLE CHECK VALVE ASSEMBLYDEGDEGREEDFDRINKING FOUNTAINDIDE-IONIZEDDIADIAMETERDMPRDAMPERDNDOWNDSDOWNSPOUTEEXISTINGEAEXHAUST AIREATENTERING AIR TEMPERATUREEERENERGY EFFICIENCY RATINGEFEXHAUST FANEFFEFFICIENCYEGEXHAUST GRILLEELELEVATIONEQUIPEQUIPMENTESPEXTERNAL STATIC PRESSUREEWTENTERING WATER TEMPERATUREEXHEXHAUSTEWCELECTRIC WATER COOLEREXISTEXISTINGEXPEXPANSIONEXTEXTERIOR, EXTERNALFFAHRENHEIT, FIRE LINEFDFIRE DAMPER, FLOOR DRAINFDCFIRE DEPARTMENT CONNECTIONFLAFULL LOAD AMPSFLRFLOORFLTRFILTERFMFLOW METERFOBFLAT ON BOTTOMFOFLAT OVALFOTFLAT ON TOPFPMFEET PER MINUTEFPSFEET PER SECONDFSDFIRE SMOKE DAMPERFTFEET, FAN TERMINALFVFACE VELOCITYGAGAGEGALGALLONSGALVGALVANIZEDGPMGALLONS PER MINUTEHHUMIDIFIER, HEIGHTHBHOSE BIBBHCHEATING COILHDHEADHEXHEAT EXCHANGEHOAHAND-OFF-AUTOMATICHPHORSEPOWER, HEAT PUMPHPSHIGH PRESSURE STEAMHTGHEATINGHWHOT WATERHWCHOT WATER CIRCULATINGHWPHOT WATER PUMPHWRHEATING WATER RETURNHWSHEATING WATER SUPPLYHZHERTZIDINSIDE DIAMETER, INDIRECT DRAINIEINVERT ELEVATIONIHINTAKE HOODININCHINITINITIALINTINTERIORIPLVINTEGRATED PART LOAD VALUEKWKILOWATTKWHKILOWATT HOURSLLENGTHLATLEAVING AIR TEMPERATURELBPOUND, LINEAR BARLBSPOUNDSLDLINEAR DIFFUSERLWTLEAVING WATER TEMPERATUREMAXMAXIMUMMBHTHOUSAND BTU PER HOURMCAMINIMUM CIRCUIT AMPACITYMDMANUAL DAMPERMECHMECHANICALMFRMANUFACTURERMINMINIMUMMOCPMAXIMUM OVER CURRENT PROTECTIONMODMOTOR OPERATED DAMPERMTRMOTORNCNORMALLY CLOSEDNEGNEGATIVENICNOT IN CONTRACTNONUMBER, NORMALLY OPENNTSNOT TO SCALEOAOUTDOOR AIROCON CENTERODOUTSIDE DIAMETEROPNGOPENINGORDOVERFLOW ROOF DRAINORLOVERFLOW RAIN LEADERPPUMP, PLUMBINGPDPRESSURE DROPPHPHASEPOCPOINT OF CONNECTIONPOSPOSITIVEPRPUMPED RETURNP/TPRESSURE/TEMPERATUREPVCPOLYVINYL CHLORIDEQTYQUANTITYRARETURN AIRRDROOF DRAINREFREFERENCEREQDREQUIREDRFRETURN FANRGRETURN GRILLERHRELIEF HOOD, RELATIVE HUMIDITYRLRAIN LEADERRPBFPREDUCED PRESSURE BACKFLOW PREVENTERRPMREVOLUTIONS PER MINUTESSOILSASUPPLY AIRSDSTORM DRAIN, SMOKE DAMPERSENSSENSIBLESEERSEASONAL ENERGY EFFICIENCY RATINGSFSUPPLY FAN, SQUARE FEETSGSUPPLY GRILLESLSOUNDLININGSPSTATIC PRESSURESPRSPRINKLERSSSTAINLESS STEEL, SANITARY SEWERSTPSTANDPIPETTHERMOSTATTEMPTEMPERATURETGTRANSFER GRILLETODTOP OF DUCTTOTTOTALTPTRAP PRIMER, TOTAL PRESSURETSPTOTAL STATIC PRESSURETUTERMINAL UNITTYPTYPICALUHUNIT HEATERUONUNLESS OTHERWISE NOTEDVVENT, VOLTVAVALVEVAVVARIABLE AIR VOLUMEVELVELOCITYVFDVARIABLE FREQUENCY DRIVEVTRVENT THROUGH ROOFWWASTE, WATER, WATT, WIDTHWBWET BULBWGWATER GAGEWHWATER HEATER, WALL HYDRANTWTRWATERGENERAL NOTES1.THE SCOPE OF THE MECHANICAL WORK CONSISTS OF WORK SHOWN ON THE PLANS AND AS DESCRIBED IN THESPECIFICATIONS. IN CASE OF CONFLICT, THE SPECIFICATIONS SHALL GOVERN. PROVIDE A COMPLETE &FUNCTIONAL SYSTEM.2.PERFORM ALL WORK IN ACCORDANCE WITH LOCAL CODES AND ORDINANCES. OBTAIN AND PAY FOR ALLREQUIRED PERMITS AND PAY FOR ALL FEES REQUIRED BY AUTHORITIES HAVING JURISDICTION. PAY ALLROYALTIES OR FEES REQUIRED IN CONNECTION WITH THE USE OF PATENTED DEVICES AND SYSTEMS.3.REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR GENERAL CONSTRUCTION INCLUDING LOUVERS,CONCRETE EQUIPMENT PADS, FLASHING DETAILS, ETC. REFER TO ARCHITECTURAL DRAWINGS FOR ROOMELEVATIONS, LOCATE MECHANICAL DEVICES SUCH AS TEMPERATURE SENSORS, HUMIDISTATS, PANELS, ETC.SO THAT THEY DO NOT CONFLICT WITH GENERAL CONSTRUCTION (WAINSCOT, DOOR HARDWARE, ETC.) NORWITH ELECTRICAL SYSTEM (LIGHT SWITCHES, SPEAKERS, OUTLETS, ETC.).4.COORDINATE WITH OTHER TRADES:A.REFER TO ELECTRICAL DRAWINGS AND CONFIRM ELECTRICAL CHARACTERISTICS SHOWN FORMECHANICAL EQUIPMENT (VOLTAGE, PHASE, HZ, ETC). MATCHES THAT OF THE MECHANICAL EQUIPMENTPROVIDED.B.PROVIDE ADEQUATE CLEARANCE OF MECHANICAL WORK FROM ELECTRICAL EQUIPMENT. MAINTAINMINIMUM ACCESS OF 6-INCHES ABOVE CABLE TRAYS AND 18-INCHES TO THE SIDE OF CABLE TRAYS.CLEARANCE ABOVE CABLE TRAY SHOULD BE 1/2 THE WIDTH AND NOT LESS THAN 6-INCHES WHENRUNNING PARALLEL WITH CABLE TRAY. AND NOT LESS THAN 6-INCHES WHEN RUNNING PERPENDICULARTO THE CABLE TRAY.5.ARRANGE EQUIPMENT SO THAT ACCESS CLEARANCES INDICATED BY DRAWINGS, REQUIRED BY CODES, ORRECOMMENDED BY MANUFACTURER ARE PROVIDED.6.INSTALL MATERIALS AND SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND ACCEPTEDSUBMITTALS. INSTALL MATERIAL IN PROPER RELATION TO ADJACENT CONSTRUCTION AND WITH UNIFORMAPPEARANCE FOR EXPOSED WORK.7.THOROUGHLY EXAMINE ALL AREAS WHERE EQUIPMENT, DUCTWORK, AND PIPING WILL BE INSTALLED ANDREPORT ANY CONDITION THAT PREVENTS THE PROPER INSTALLATION OF THE MECHANICAL WORK.8.COMPLY WITH WASHINGTON STATE ENERGY CODE SECTION C408.1.3 DOCUMENTATION REQUIREMENTSINCLUDING ALL LOCAL JURISDICTION AMENDMENTS. INCLUDE THE DEVELOPMENT OF CONSTRUCTION ANDAS-BUILT DRAWINGS, PROJECT MANUALS, AND SYSTEM BALANCING REPORTS.9.PURSUANT TO SECTION C408.1.3 OF THE WASHINGTON STATE ENERGY CODE, THE HVAC CONTROL SYSTEMSHALL BE TESTED TO ENSURE THAT THE CONTROL DEVICES, EQUIPMENT AND SYSTEMS ARE CALIBRATED,ADJUSTED, AND OPERATE IN ACCORDANCE WITH THE APPROVED PLANS AND SPECIFICATIONS. SEQUENCES OFOPERATION SHALL BE FUNCTIONALLY TESTED TO ENSURE THEY OPERATE IN ACCORDANCE WITH THEAPPROVED PLANS AND SPECIFICATIONS.10.THE COMMISSIONING SPECIFICATION, INCLUDING ALL FUNCTIONAL TEST PROCEDURES, SHALL BE PROVIDEDAND ENFORCED BY THE CONTRACTOR.11.PROVIDE SEISMIC RESTRAINT IN ACCORDANCE WITH IBC AND ASCE STANDARD 7. SUBMIT CALCULATIONS BYLICENSED STRUCTURAL ENGINEER. PRODUCTS MAY CONFORM TO SMACNA SEISMIC RESTRAINT GUIDELINES.12.PROVIDE A SINGLE SUBMITTAL OF ALL MECHANICAL EQUIPMENT AS SPECIFIED. AS A MINIMUM, SUBMITPRODUCT DATA FOR ALL EQUIPMENT AND FIXTURES LISTED IN ACCOMPANYING SCHEDULES FOR APPROVAL.13.USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITHMANUFACTURER'S INSTRUCTIONS.14.ARRANGEMENT OF SYSTEMS INDICATED ON THE DRAWINGS IS DIAGRAMMATIC, AND INDICATES THE MINIMUMREQUIREMENTS FOR PLUMBING AND MECHANICAL WORK. ADJUST TERMINAL UNIT LOCATIONS, BASED ON FIELDMEASUREMENTS, TO AVOID INSTALLATION ABOVE DESKS. SITE CONDITIONS SHALL DETERMINE THE ACTUALARRANGEMENT OF THE WORK. TAKE FIELD MEASUREMENTS BEFORE PREPARING SHOP DRAWINGS, OBTAINAPPROVAL OF SHOP DRAWINGS BEFORE BEGINNING FABRICATION. BE RESPONSIBLE FOR ACCURACY OFDIMENSIONS AND LAYOUT. OVERHEAD PIPING AND DUCTWORK SHALL BE ARRANGED TO OBTAIN MAXIMUMHEAD ROOM.15.CLEAN AND PROTECT WORK FROM DAMAGE. RESTORE DAMAGED FINISHES. COVER ENDS OF PIPING ANDDUCTWORK NOT ACTIVELY BEING WORKED ON.16.MODIFY AND EXTEND EXISTING SERVICE TO ACCOMMODATE NEW WORK. RELOCATE EXISTING COMPONENTSAS REQUIRED FOR NEW SYSTEM. COORDINATE WITH BUILDING MANAGEMENT.17.PROVIDE PRODUCTS OF ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILARSERVICE FOR THREE YEARS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITHMANUFACTURER'S INSTRUCTIONS.18.DO NOT CUT STRUCTURAL ELEMENTS WITHOUT PRIOR WRITTEN APPROVAL.19.CONCEAL PIPING AND DUCTWORK TO THE GREATEST EXTENT POSSIBLE.20.INSTRUCT OWNER IN PROPER OPERATION OF SYSTEMS.21.DRAWINGS DO NOT SHOW ALL OFFSETS WHICH MAY BE REQUIRED. MAKE OFFSETS WITH FITTINGS USING THELEAST ANGLE OF OFFSET POSSIBLE. DUCTWORK & PIPING SHALL BE ROUTED TO AVOID ALL STRUCTURALSUPPORTS, AND COORDINATED WITH WORK OF OTHER TRADES.22.MATERIALS, METHODS, AND INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE LATEST EDITION OFTHE FOLLOWING CODES AS ADOPTED BY THE AUTHORITY HAVING JURISDICTION. (FEDERAL WAY)2015 INTERNATIONAL BUILDING CODE (IBC)2015 INTERNATIONAL MECHANICAL CODE (IMC)2015 UNIFORM PLUMBING CODE (UPC)2015 INTERNATIONAL FIRE CODE (IFC)2015 WASHINGTON STATE ENERGY CODE (WSEC) WITH LOCAL AMENDMENTSREMODEL CONSTRUCTION NOTES1.DEMOLITION: WORK REQUIRED IS NOTED ON PLANS. VERIFY WITH ON SITE CONDITION AND OWNER. SALVAGEEQUIPMENT FOR OWNER'S USE AS NOTED.2.COORDINATE INTERRUPTIONS OF SERVICES PASSING THROUGH WORK AREA TO MINIMIZE DISRUPTION INADJACENT SPACES. COORDINATE WITH BUILDING OWNER.3.INSTALL NEW WORK GENERALLY AS SHOWN. ADEQUATE SPACE HAS BEEN VERIFIED TO THE DEGREEPOSSIBLE, BUT MAY REQUIRE MINOR RELOCATION OF SMALL CONDUIT AND CEILING WIRE. COORDINATEEXTENT OF RELOCATION WITH GENERAL CONSTRUCTION WORK.4.COORDINATE WORK WITH GENERAL CONSTRUCTION TO MINIMIZE DUST & DUST MIGRATION.PIPING NOTES1.SANITARY, WASTE, AND VENT PIPING (PLASTIC NOT ALLOWED) SHALL BE NO-HUB CAST IRON OR DWV COPPER.2.HOT AND COLD WATER PIPING SHALL BE HARD DRAWN COPPER TUBING: TYPE L, ASSEMBLED WITH WROTCOPPER FITTINGS AND LEAD-AND ANTIMONY-FREE SOLDER.3.INSULATE ALL HOT AND COLD WATER PIPING WITH GLASS FIBER INSULATION WITH ALL SERVICE JACKET. USEHEAT BONDING TAPE TO CLOSE INSULATION; STAPLES AND PRESSURE TAPE ARE PROHIBITED.4.PROVIDE ALL REQUIRED ACCESSORIES INCLUDING SHUT-OFFS AND CLEAN-OUTS. PROVIDE COMPONENTSWHICH PREVENT BACK-SIPHONAGE OR CROSS-CONNECTIONS. PROVIDE ISOLATION DEVICES TO REDUCESOUND TRANSMISSION.5.PROVIDE STOPS FOR EACH WATER CONNECTION TO EACH FIXTURE OR ITEM OF EQUIPMENT.6.DISINFECT WATER DISTRIBUTION SYSTEM. FLUSH AND TEST ALL SYSTEMS FOR PROPER OPERATION. ADJUSTSYSTEM TO PREVENT WATER HAMMER.7.REFER TO PIPING DIAGRAMS AND DETAILS FOR REQUIRED FITTINGS, VALVES, ETC. FLOOR PLANS ANDSECTIONS INDICATE EQUIPMENT LOCATIONS AND GENERAL PIPE ROUTING ONLY.8.REFER TO CIVIL DRAWINGS FOR UTILITY WORK 5'-0" BEYOND THE BUILDING LINE.LG11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 DETAIL REFERENCESECTION REFERENCEELEVATION REFERENCE1XXX.XXXXX.XXXXX.XXSYMBOLDESCRIPTIONSYMBOLS LEGEND - GENERALSECTION IDENTIFICATION NUMBERSHEET WHERE SECTION IS DRAWNELEVATION IDENTIFICATION NUMBERSHEET WHERE ELEVATION IS DRAWNDETAIL IDENTIFICATION NUMBERSHEET WHERE DETAIL IS DRAWNRECTANGULAR TO ROUND TRANSITIONROUND BRANCH TO ROUND DUCT CONNECTIONROUND BRANCH TO RECTANGULAR DUCT CONNECTIONRECTANGULAR BRANCH TO RECTANGULAR DUCTCONNECTION WITH 45° TAPERROUND OR RECTANGULAR BRANCH TO ROUND OR RECTANGULAR DUCTCONNECTIONRECTANGULAR OR ROUND, 90° ELBOW,R/W OR R/D = 1.5ROUND, 90° ELBOW, R/W OR R/D = 1.5RECTANGULAR, 90° ELBOW, R/W OR R/D = 1.5SQUARE CORNER ELBOW WITH TURNING VANES45° BRANCH CONNECTIONTRANSITION OR REDUCER - NOTED FOT (FLAT ON TOP) OR FOB (FLAT ONBOTTOM) IF REQUIREDSYMBOLDESCRIPTIONSYMBOLS LEGEND - AIR HANDLINGSYMBOLDESCRIPTIONSYMBOLS LEGEND - PIPINGSYMBOLDESCRIPTIONSYMBOLS LEGEND - PIPINGP/TPSAF/TSSYMBOLSYMBOLS LEGEND - MEDICAL GASESWAGDMABZVBSYMBOLSYMBOLS LEGEND - LABORATORY++++++DRAWING CONSTRUCTION ("FLAG") NOTEMATCHLINEREVISION CLOUD (ENCIRCLES DRAWING CHANGES MADE SINCE THEPREVIOUS RELEASE)REVISION REFERENCENORTH REFERENCEEQUIPMENT IDENTIFIERPOINT OF CONNECTIONDESCRIPTIONDESCRIPTIONX-XXO2MAMVMAN2MAWAGWAGCO2N2OETOLALVFMMAVCHRHPSHWSHWRCHS120°HW140°HWIDORLRLAAVSPRSTPEXISTING TO BE REMOVED (HATCH)HEAVY LINEWEIGHT INDICATES NEW WORKLIGHT LINEWEIGHT INDICATES EXISTING INFORMATIONSOIL OR WASTEVENTRAIN LEADEROVERFLOW RAIN LEADERINDIRECT DRAINCOLD WATERHOT WATERHOT WATER CIRCULATING140° POTABLE HOT WATER120° POTABLE HOT WATERFIRESPRINKLERSTANDPIPEHIGH PRESSURE STEAMHEATING WATER SUPPLYHEATING WATER RETURNCHILLED WATER SUPPLYCHILLED WATER RETURNREDUCER, CONCENTRICWYE STRAINER WITH CAPPED HOSE END BLOWDOWN VALVEANGLE VALVEAUTOMATIC CONTROL VALVE - TWO WAY (PNEUMATIC OPERATOR SHOWN)AUTOMATIC CONTROL VALVE - THREE WAY (ELECTRIC OPERATOR SHOWN)BUTTERFLY VALVEFLEXIBLE CONNECTION IN PIPINGMANUAL AIR VENT (MAV), AUTOMATIC AIR VENT (AAV)PRESSURE GAUGETHERMOMETERTHERMOMETER WELLSIGHT GLASSHOSE BIBSTEAM TRAP ASSEMBLYF/T = FLOAT AND THERMOSTATICF = FLOATT = THERMOSTATICB = BUCKETIB = INVERTED BUCKETI = IMPULSEO = ORIFICEPIPE ANCHORPIPE ALIGNMENT GUIDECONTROL VALVE STATIONPIPE SUPPORTPRESSURE/TEMPERATURE TEST PORTCAPPLUGWYE STRAINERUNIONGATE VALVEGLOBE VALVEBALL VALVEBALANCING OR PLUG VALVENEEDLE VALVEPRESSURE REDUCING VALVEBALANCING/MEASURING VALVERELIEF VALVECHECK VALVEPIPE TURNING DOWN / AWAYPIPE TURNING UP / TOWARDSPIPE DOWN TEEPIPE DOWN TEE / AWAYPIPE UP TEE / TOWARDSLABORATORY VACUUMLABORATORY AIRNON POTABLE HOT WATER RECIRCULATENON POTABLE HOT WATERNON POTABLE COLD WATERHOSE REEL (RETRACTABLE)MEDICAL AIR PRESSURE SENSORMEDICAL GAS ALARM BOXZONE VALVE BOXMEDICAL GAS VALVE (SERVICE VALVE)ETHYLENE OXIDECARBON DIOXIDENITROGENNITROUS OXIDE (NITROUS)WASTE ANESTHETIC GAS DEVICEMEDICAL AIR OUTLETWASTE ANESTHETIC GASMEDICAL VACUUMMEDICAL COMPRESSED AIROXYGEN1NPIPING OR DUCTED AIRFLOWNON-DUCTED AIRFLOWELECTRICAL CONNECTIONFLOW CONTINUATION ARROWCOMPLEX INTERLOCK (ELEC., PNEUMATIC, ETC.)CONNECTION TO CENTRAL MONITORING AND CONTROL SYSTEM (CMCS)PUMPCENTRIFUGAL FANELECTRIC MOTOR/STARTER ASSEMBLYELECTRIC MOTOR OPERATOR (VALVES AND DAMPERS)FUNNEL DRAINFLOOR DRAINSYMBOLDESCRIPTIONSYMBOLS LEGEND - PIPING & AIRFLOW DIAGRAMSMMFLOW DIRECTIONFLOOR SINK (SQUARE AND ROUND)LEGENDP0.134512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003LG11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 PLUMBINGSCHEDULESP2.034512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003ELECTRIC WATER HEATER SCHEDULEEQUIP. NOLOCATIONSERVICEBASIS OF DESIGNMANUFACTURERBASIS OF DESIGN SERIESTANK DESCRIPTIONVOLUME (GAL)INPUT (KW)NUMBER OF ELEMENTSSIMULTANEOUS/NON-SIMULTANEUOSTEMP RISE (DEG F)RECOVERY RATE(GPH)LWT (DEG F)THERMAL EFFICIENCYELECTRICALDIMENSIONS DIAXHEIGHT(IN)SHIPPING WEIGHT (LBS)OPERATING WEIGHT (LBS)REMARKSMAX kWV/PH/HZWH-1UTILITY 101-09AMMA CLINICA.O. SMITHENT-50ELECTRIC50929021120926240/1/6021X611255251REMARKS:1. PRESSURE RELIEF VALVE SET AT 175 PSI.NOTE: DIAMETER LARGER THAN 30" WILL NOT FIT THROUGH A REGULAR SIZED INTERIOR DOOR.LGPUMP SCHEDULEEQUIP. NOLOCATIONSERVICEBASIS OF DESIGN MANUFACTURERBASIS OF DESIGN MODEL NUMBERTYPEMINIMUM FLOW(GPM)HEAD(FT)CONNECTION SIZE (IN)ELECTRICALWEIGHT(LBS)REMARKSSPEED(RPM)MOTOR (HP)FLA / LRAV/PH/HZDCP-1WATER HEATER ROOMDHWBELL AND GOSSETECOCIRCIN-LINE CIRC1.510.01/2"VARIES60 WN/A115/1/6010.01NOTES:1. PROVIDE WITH STAINLESS STEEL BODY, SUITABLE FOR DOMESTICE WATER APPLICATIONS.EXPANSION TANK SCHEDULEEQUIP. NOLOCATIONSERVICEBASIS OF DESIGN MANUFACTURERBASIS OF DESIGN MODEL NUMBERTANK DESCRIPTIONTANK TYPEVOLUME GALLONSACCEPTANCE VOLUME GALLONSPRESSURE RATING PSIDIA INHEIGHT INSYSTEM CONNECTION (NPTM)WEIGHT LBSREMARKSET-1ELECTRIC WATER HEATERDOMESTIC HOT WATERAMTROLST-5C-DDDIAPHRAGMASME20.91508143/4"10-REMARKS:PLUMBING FIXTURE SCHEDULEMARKDESCRIPTIONROUGH-IN CONNECTION INREMARKSWVCWHWTWFD-1FLOOR DRAIN31-1/2------JAY R SMITH FIGURE 2005, SIZE 02, A STRANGER (ROUND), NICKEL BRONZE FACE, NO-HUB CONNECTION.L-1LAVATORY, WALL MOUNTED21-1/41/21/2--KOHLER K-2030 GREENWICH WALL HUNG LAVATORY. CHICAGO FAUCET 4" OC 895-317FCABCP GN1FC GOOSENECK.MS-1MOP SINK321/21/2--KOHLER K-6710 "WHITBY" CORNER FLOOR MOUNTED SERVICE SINK. CHICAGO FAUCET 897-CP.S-1EXAM SINK21-1/21/21/2--CORIAN MODEL 804 15-3/4"X15-3/4" SOLID SURFACE LAVATORY. CHICAGO FAUCETS 4" 895-317E73-RGD2AB GN2FC GOOSENECK, NON-AERATING LAMINAR OUTLET.S-2LAB/ SOILED/ MED. DIST. SINK21-1/21/21/2--CORIAN MODEL 859P 13-3/8"X17-3/8" SOLID SURFACE SINK. CHICAGO FAUCETS 8" OC 786-CP W/ E32 MALE LAMINAR OULET.S-3LAB SINK21-1/21/21/2--CORIAN MODEL 871 15-5/8"X20-7/8" SOLID SURFACE SINK. CHICAGO FAUCETS 8" OC 786-CP W/ E32 MALE LAMINAR OULET.S-4STAFF LOUNGE SINK21-1/21/21/2--CORAIN MODEL 871 20-7/8" X15-5/8" SOLID SURFACE SINK. CHICAGO FAUCETS 8" OC 786-CP WITH E32 MALE LAMINAR OUTLET.S-5SOILED SINK21-1/21/21/2--CORIAN MODEL 850 DOUBLE BOWL 18"X31" UNDERMOUNTED SOLID SURFACE SINK. CHICAGO FAUCETS 8" OC 786-CP WITH E32 MALE LAMINAR OUTLET.WC-1WATER CLOSET, TANK TYPE - ADA421/2----KOHLER K-25077 "KINGSTON" FLOOR MOUNTED ELONGATED 1.28 GPM TWO-PIECE TANK TYPW TOILET WITH K-4650-A LUSTRA SEAT.--WATER HAMMER ARRESTOR----------ZURN WILKINS MODEL #1260XL, LEAD FREE WATER HAMMER ARRESTOR, CERTIFIED TO NSF/ANSI STANDARD 372, DEVICE SHALL BE PRE-CHARGED AND SEALED AT THE FACTORY. INSTALL PER PDIRECOMMENDATION.REMARKS:1. COORDINATE MOUNTING HEIGHTS AND HANDING WITH ARCHITECTURAL DRAWINGS AND FIELD CONDITIONS.2. MANUFACTURER LISTED IS BASIS OF DESIGN. PROVIDE LISTED OR EQUAL APPROVED BY OWNER.11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 ABCDE4321SHEET NOTES1.ALL FIXTURES AND PIPINGSHOWN IS A REPRESENTATIONOF THE ACTUAL SYSTEMS AND ISNOT TO BE CONSIDERED ANAS-BUILT. ALL DIMENSIONS ANDLOCATIONS SHOULD BE FIELDVERIFIED PRIOR TOCOMMENCEMENT OFDEMOLITION OR NEWCONSTRUCTION.2.UPON REMOVAL OF EXISTINGFIXTURES, PIPING, ETC., THECONTRACTOR SHALL PATCHANY EXISTING WALL OR FLOORASSEMBLIES. REFER TOARCHITECTURAL DEMOLITIONDRAWINGS FOR ADDITIONALINFORMATION ANDCOORDINATION ITEMS.FLAG NOTESREMOVE PLUMBING FIXTUREIN ITS ENTIRETY. CAPSANITARY FLUSH AT WALL ORFINISHED FLOOR. CAPVENTING AT CEILING ANDDOMESTIC PIPING SERVICESAT WALL.PROVIDE CAP AT EXISTING 3"TAKEOFF AS SHOWN.REMAINING BELOW GRADEPIPING SHALL BE ABANDONEDIN PLACE.1PLUMBINGDEMOLITION PLANPD3.134512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003SCALE:NPLUMBING DEMOLITION PLAN 1/4"=1'-0"1(E) 4" PVC. I.E. = -3' 2"(E) 4" PVC. I.E = -2' 5"(E) 3" PVC. I.E. = -2' 0"(E) 4" PVC. I.E. = -3' 9"(E) 4" PVC. I.E. = -4' 0"APPROXIMATE EXTENT OF SAWCUTTING REQUIRED FOR ROUTING OFNEW PIPING. SEE SHEET P3.2 FORNEW SANITARY PIPING.EXISTING 4" WASTE. FIELD VERIFY EXACTLOCATION VIA IMAGING AND OR CAMERA.INVERT ELEVATION UNKNOWN AT THIS TIME.2'8'SCALE: 1/4" = 1'-0"1'4'0'1112211LG11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 ABCDE4321SHEET NOTES1.CONTRACTOR SHALLCOORDINATE ALL TRENCHINGSO THAT ANY NEW OREXISTING FOOTINGS, GRADEBEAMS AND OR COLUMNS AREMINIMALLY IMPACTED. RISERSAND RISER LOCATIONS SHALLBE COORDINATED WITHSTRUCTURAL. SHOULDROUTING BE REQUIRED AT ORNEAR FOOTING, PROVIDESLEEVE IN ACCORDANCE WITHSTRUCTURAL DRAWINGS ANDDETAILS.2.THE CONTRACTOR SHALLREFER TO ARCHITECTURALAND STRUCTURAL DRAWINGSFOR LOCATIONS OF SHEARWALLS. COORDINATE ROUTINGACCORDINGLY. PROVIDESLEEVES AND ORPENETRATIONS INACCORDANCE WITHSTRUCTURAL DRAWINGS ANDDETAILS.3.INVERT ELEVATIONS PROVIDEDFOR COORDINATION ANDREFERENCE. COORDINATEWITH SITE WORK CONTRACTORFOR EXACT INVERT ELEVATION.34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003PLUMBINGUNDERGROUNDPLANP3.1SCALE:NPLUMBING UNDERGROUND PLAN 1/4"=1'-0"(E) 4" PVC @ -3' 2"(E) 4" PVC @ -2' 5"(E) 4" PVC @ -3' 9"(E) 4" PVC @ -4' 0"4" W2" W UP TO S-12" W UP TO S-12" W UP TO S-12" W UP TO S-12" W UP TO S-12" W UP TO L-12" W UP TO S-12" W UP TO S-12" W UP TO S-12" W UP TO S-12" W UP TO L-12" W UP TO S-42" W UP TO S-52" W UP TO S-22" W UP TO S-32" W UP TO L-12" W UP TO L-12" W UP TO S-22" W UP TO S-12" W UP TO S-23" W UP TO MS-14" W4" W UP TO WC-14" W UP TO WC-14" W UP TO WC-14" W UP TO WCO4" W3" W2" W4" W4" W4" W4" W UP TO WC-14" W3" W UP TO FD-12'8'SCALE: 1/4" = 1'-0"1'4'0'CAPP.O.C.P.O.C.P.O.C.P.O.C.P.O.C.P.O.C.LG11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 ABCDE4321Electrical/IS&TCloset101-22126 SFCleanSupply/Equip. Room101-23180 SFExamRoom #10101-32119 SFExamRoom #8101-3195 SFBiohazard/SoiledHolding101-11110 SFRegistration101-03176 SFWaiting101-02400 SFADAPublicToilet101-0454 SFMA WorkStations101-16371 SFWCAlcove101-01A18 SFProviderOffice101-15119 SFLab101-07285 SFEntryVestibule101-0186 SFExamRoom #11101-33100 SFExamRoom #6101-3095 SFExamRoom #1101-2595 SFExamRoom #3101-2495 SFADAPatientToilet101-0869 SFBariatricExamRoom #2101-20114 SFMed.Dist.Room101-1873 SFConsultRoom #1101-26101 FInfantScale101-29ASupervisor'sOffice101-13102 SFProviderOffice101-17129 SFExamRoom #9101-3495 SFExamRoom #7101-3595 SFExamRoom #5101-3695 SFStaffLounge101-09219 SFLabWaiting101-06A30 SFVitalsArea #1101-05A26 SFBariatricExamRoom #4101-21114 SFVitalsArea #2101-14A17 SFDrawStation #2101-07BLabCheck-in101-02A31 SFConsultRoom #2101-37108 SFDrawStation #1101-07AADAPatientToilet101-2756 SFADAPatientToilet101-2856 SFPrint101-29BPrint101-19AHall101-29Hall101-19Hall101-05Hall101-14Hall101-06ADAStaffToilet101-1048 SFEVSCloset101-1212 SFPrint101-29C3" VTR2" V2" V2" V2" V1-1/4" CD1-14" CD5/8" CD DOWN TO MS-1SEE DETAIL 4/M7.1 FOR CONNECTION1-1/2" V2" VTR1-1/2" V2" V2" V1-14" CD DOWN TO S-1SEE DETAIL 10/M7.1 FOR CONNECTION1-14" CD DOWN TO S-2SEE DETAIL 10/M7.1FOR CONNECTION2" V2" W2" VTR1-1/2" V2" V1" CW2" CW1" CW1" CW1" CW1" HWR1-1/2" HW1-1/4" HW1-1/4" HW1-1/4" HW1-1/4" HW2" V1-1/4" CW3/4" CW1/2" V1" CW3/4" HW3/4" CW1/2" V1-1/4" HW1" HW1" CW1" HW3/4" CW3/4" HW1" HW1-1/4" HW1-1/4" CW1-1/4" HW1-1/4" CW1-1/4" CW1" CW1" CW3/4" HW1-1/4" CW1" HW1" CW3/4" CW1-1/2" V3/4"" HW3/4" CW1-1/2" V3/4"" HW3/4" CW1-1/2" V3/4"" HW1-1/4" HWSHEET NOTES1.PIPING IS SHOWNDIAGRAMMATICALLY.INSTALL PIPING INACCORDANCE WITH BESTPLUMBING PRACTICES.VENT AND WATERHEADERS TO FIXTURESTO BE ROUTED IN WALLSAND CHASE WHEREAPPLICABLE.34512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003PLUMBING PLANP3.2SCALE:NPLUMBING PLAN 1/4"=1'-0"(E) 2" CW2'8'SCALE: 1/4" = 1'-0"1'4'0'S-1S-1S-1S-1S-1S-1S-1S-1S-3WC-1L-1S-5S-2S-1WC-1WC-1L-1L-1S-2S-1MS-1S-1WC-1L-1S-2S-4L-1WC-1WH-1S-1S-1DCP-1SEE CIVIL FORCONTINUATIONFD-1ET-1SEE DETAIL 1/M7.1FOR WATER HEATER CONFIGURATIONLG11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 ABCDE4321Xref PT4C000077-58363Xref PT4C000076-58362Xref PT4C000075-58361Xref PT4C000067-58360Xref PT4C000077-58363Xref PT4C000076-58362Xref PT4C000075-58361Xref PT4C000067-58360 Xref PT4C00 0077 -583 63Xref PT4C00 0076 -583 62Xref PT4C00 0075 -583 61Xref PT4C00 0067 -583 60 Xre f PT4C000 077 -5836 3 Xre f PT4C000 076 -5836 2 Xre f PT4C000 075 -5836 1 Xre f PT4C000 067 -5836 0Xref PT4C000077-58363Xref PT4C000076-58362Xref PT4C000075-58361Xref PT4C000067-58360Xref PT4C000077-58363Xref PT4C000076-58362Xref PT4C000075-58361Xref PT4C000067-58360 Xref PT4C00 0077 -583 63Xref PT4C00 0076 -583 62Xref PT4C00 0075 -583 61Xref PT4C00 0067 -583 60 Xre f PT4C000 077 -5836 3 Xre f PT4C000 076 -5836 2 Xre f PT4C000 075 -5836 1 Xre f PT4C000 067 -5836 0 PLUMBING ROOFPLANP3.334512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003SHEET NOTES1.CONTRACTORS SHALLCOORDINATE WITH FINALLOCATION OF ALL ROOFMOUNTED EQUIPMENT WITHARCHITECTURAL ANDSTRUCTURAL DRAWINGS.SCALE:NROOF PLAN 1/4"=1'-0"670#670#670#670#10'-0" OSA CLEARANCE. ALL EXHAUST FANSAND PLUMBING VENTS TO REMAIN OUTSIDEOF THIS CIRCLE (TYP.)2" VTR3" VTR2" VTR2'8'SCALE: 1/4" = 1'-0"1'4'0'CU-185#75#190#89#LG11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 PLUMBING DETAILSP7.134512 S 16th Ave, Suite AOWNER:COPYRIGHT TO:DATE:DRAWN BY:InSight Healthcare ArchitectureMARKDATEDESCRIPTIONPROJECT NAME:SHEET TITLE:SHEET #:PROJECT NO.31230MMA ClinicFederal WayFederal Way, WA 98003PERMIT SET11/10/202010 NOVEMBER 2020600 Stewart St., Ste 1400Seattle, Washington 98101Tel206.267.1700Fax206.267.1701SAZAN #658-20003SCALE:NTSELECTRIC WATER HEATER DIAGRAM1EXPANSION TANKAQUASTAT TIMERFLEXIBLECONNECTION (TYP)ELECTRICWATERHEATER4" CONCRETE PAD WITH 1"CHAMFERED EDGES (IF LEGS NOTFURNISHED WITH WATER HEATER)HOSE END DRAIN VALVEEXTEND TO FLOOR DRAINTEMP/PRESSURE RELIEF VALVEDIELECTRIC UNION (TYP)THERMOMETERPRESSUREGAUGEINCOMPRESSIBLEINSULATION PAD1" WIDE, 16 GA STEEL STRAPANCHOR BOLT TO STRUCTUREPIPE TO NEAREST FLOOR DRAINAND TERMINATE WITH AN AIR GAPCHECK VALVE (TYP)ISOLATION VALVECWWASTE HW120°FMIXING VALVE140°FBREAK OUT FLOOR AROUNDEXISTING PIPEPATCH FLOOR PER ARCHDWGSEXISTING FLOOREXISTING PIPE TO REMAINCAP OR PLUG EXISTING PIPEDEPENDING ON PIPEMATERIAL, SEE NOTE 2REMOVE EXISTING PIPE RISERNOTES:1.WHERE CONNECTION IS TO A FLOOR DRAIN, FUNNEL FLOOR DRAIN, OR RECEPTORDRAIN, REMOVE DRAIN BODY PRIOR TO CAPPING.2.CAPPING/PLUGGING INSTRUCTIONS PER MATERIAL:a.CAST IRON NO HUB PIPE: PROVIDE CAP AND NEW COUPLING.b.CAST IRON HUB AND SPIGOT PIPE: PROVIDE PLUG AND GASKET IN EXISTING HUBAND CAULK OR GASKET ALL AROUND.c.COPPER TUBING PIPE: SOLDER CAP TO PIPE.d.GALVANIZED AND BLACK STEEL PIPE: THREAD PIPE AND PROVIDE CAP.SCALE:NTSCAPPED PIPE (DEMOLITION) DETAIL2STRAINERPIPE SIZE AS NOTED ON PLANSDURING CONCRETE POUR(STEP #1)AFTER CONCRETE HARDENS(STEP #2)NOTES:1. COMPLETE INSTALLATION OF FLOOR DRAIN ANDSETTING OF FINAL ELEVATION WILL NOT BEALLOWED DURING INITIAL CONCRETE POUR.2. DO NOT ALLOW GROUT TO PENETRATE WEEP HOLES AND FILL UP TRAP.INSTALL STRAINER, STRAINER HEAD,AND FLASHING COLLAR (SET FINALELEVATION)FINISHED GROUT (BY G.C.)CONCRETE BY G.C.FLOOR DRAIN BODYCUT 1-1/2" RIGIDINSULATION TO FIT.ATTACH WITH DUCT TAPEDUCT TAPEREMOVE STRAINER, STRAINERHEAD, AND FLASHING COLLAR.STORE FOR LATER INSTALLATIONSLOPED FLOORTRAP PRIMERCONNECTIONCAULKFLASHINGCONCRETE BY G.C.SCALE:NTSFLOOR DRAIN INSTALLATION DETAIL8SIZE AS SHOWN ON PLANS,MATERIAL AS NOTED INSPECIFICATIONSNICKEL BRONZE TOPFINISHED FLOORCAST IRON RISERFOR INDOORAPPLICATIONSCONCRETE, CERAMICTILE, TERRAZZO - USESTANDARD SCORIATEDCLEANOUT COVER;CARPET - USE CARPETFLANGE; VINYL - USECLEANOUT INSERTCOVER.FOR EXTERIORAPPLICATIONS, PROVIDEAN 18"x18"x5-1/2"CONCRETE PAD AND ANICKEL BRONZE TOP.1.NOTES:2.18" CLEAR ALL AROUNDSCALE:NTSINTERIOR CLEANOUT DETAIL5TENANT WATER METER - ELECTRONIC TURBINE TYPE(TYP ONE PER TENANT). PROVIDE 5 PIPE DIAMETERSOF STRAIGHT PIPE UPSTREAM & 3 PIPE DIAMETERS OFSTRAIGHT PIPE DOWNSTREAM (WHERE INDICATED).BYPASS VALVE - LOCKINGTRANSMITTING REGISTERCOORDINATE LOCATION WITHELECTRICAL AND CONTROLSCONTRACTORWATER SERVICE - SEECIVIL FOR WATER METERCAPPED BALL VALVE(TYP. SEE PLAN)IDTO TENANT FIXTURESTO COMMONFIXTURESTO DRAINSCALE:NTSWATER METER DIAGRAM7ISOLATIONVALVE (TYP)INDIRECT DRAININDICATING ISOLATION VALVE (TYP)RPBPWASTECWCWCWSCALE:NTSINSTALLATIONLAVATORY ( PUBLIC) SERVICES6HOT WATER STOPCOLDLAVATORYHOT FAUCETESCUTCHEON (TYPICAL)FLEXIBLE RISER (TYPICAL)TEEBALL VALVECOLD WATER STOPLAVATORY TEMPERING VALVE, FOR INSTALLATION AT ALL PUBLICFIXTURES WHERE HW EXCEEDS 120°F.SCALE:NTSSERVICE SINKCONDENSATE DRAIN DISCHARGE TO42 PIPE DIAMETERS1"CHROME-PLATEDBRASS ESCUTCHEON3/4" MINIMUM COPPER CONDENSATE PIPING IN WALLSERVICE SINKNOTE:EXPOSED PORTION OF PIPING SHALL BE COPPER.CUT PIPE ENDAT 45° ANGLEOPEN VENTALL PIPING SAME SIZE ASDRAIN PAN CONNECTION(MINIMUM 1")DRAIN PAN1.0 x UNIT RATED TOTALSTATIC PRESSURE(MINIMUM 2")1.5 x UNIT RATED TOTALSTATIC PRESSURE(MINIMUM 3")SCALE:NTSCONDENSATE DRAIN TRAP3GALV CLAMPCONDENSATE DRAINFROM ABOVE(1-1/2" MAX SIZE)EXISTING FIXTUREGASKETPROVIDE TEE ANDTAIL PIECE TO MATCHEXISTING TRAPEXISTING P-TRAP1583215790155401543015050150601514015260154121585615855REFERENCES:SOURCE:NOTES:SECTION:15415 - CONDENSATE DRAIN PIPING SYSTEMVENT THRU ROOFAHUAHUAIR GAP FITTING ANDDEEP P-TRAP REQDW/CONNECTION TOVENTP-TRAP REQD W/SEPARATE DRAINTO EXISTING TRAPDEEP SEAL P-TRAP, TYLER PIPE CO.AIR GAP FITTING W/WADE W-2490-TTHREADED CAST IRON WADE W-2490SAAISUSPENDED CEILINGCONDENSATEDRAIN PANDRAIN PAN DETAIL - 15050-C1, C2DRAIN TO SINKDRAIN TO SEWERSEPERATELY TOOVERFLOW PIPEDCONSPICUOUS LOCATIONSCALE:NTSCONDENSATE DRAIN TO SINK AND VENT10SCALE:NTSVENT THROUGH ROOF 9VENT PIPING; SIZEAS NOTED ON PLANSFINISHED ROOF15-0"MIN. FROM ANYFRESH AIR INTAKEVANDAL-PROOFVENT CAPFLASHINGFLASHING 10' ALL SIDES12"MIN.LG11/09/2020RECEIVEDCITY OF FEDERAL WAY COMMUNITY DEVELOPMENTNov 20 2020 PP XXXX XXX J PB SB NL M XXXXXX OS PC OS PC HOME RUN TO SOURCE OF SUPPLY PANEL DESIGNATION BRANCH CIRCUIT NUMBERS A-1,3,5 LIGHT FIXTURE IDENTIFIER - REFER TO LIGHTING FIXTURE SCHEDULE SHADING INDICATES LUMINAIRE CIRCUIT OR WITH BATTERY BACKUP BALLAST "NL" INDICATES FIXTURE STAYS ON 24/7 2x4 LUMINAIRE 2x2 LUMINAIRE WALL MOUNTED LUMINAIRE STRIP LUMINAIRE DOWNLIGHT WALL MOUNTED LUMINAIRE ILLUMINATED EXIT SIGN - SINGLE FACE ARROW INDICATES DIRECTION OF EGRESS, UNIVERSAL MOUNT ILLUMINATED EXIT SIGN - DOUBLE FACE ARROW INDICATES DIRECTION OF EGRESS, UNIVERSAL MOUNT BATTERY-POWERED EMERGENCY WALLPACK COMBINATION BATTERY POWERED EMERGENCY WALLPACK AND ILLUMINATED EXIT SIGN LIGHTING CONTROL SYSTEM POWER PACK SWITCH BYPASS DEVICE CEILING MOUNTED OCCUPANCY SENSOR WITH POWER PACK -PASSIVE INFRARED TYPE UNLESS NOTED: PHOTOELECTRIC CONTROL CEILING MOUNTED OCCUPANCY SENSOR WALL MOUNTED PHOTOELECTRIC CONTROL WALL MOUNTED MOTOR-RATED SWITCH - SIZE OL PER MOTOR REQUIREMENTS AMPERES SHORT CIRCUIT AVAILABLE (SYMMETRICAL) PANELBOARD EQUIPMENT CABINET - TYPE AS NOTED 208Y/120V, 3Ø, 4W PANELBOARD MINIMUM 3/4" CONDUIT CONCEALED IN CEILING SPACE OR IN WALL MINIMUM 3/4" WITH #12 AWG CONDUCTORS WITH DEDICATED NEUTRAL EACH CIRCUIT, UNLESS OTHERWISE NOTED ON PLAN. PROVIDE EQUIPMENT GROUNDING CONDUCTORS SIZED PER NFPA 70. FLEXIBLE METAL CONDUIT CONDUIT - CONCEALED IN OR UNDER FLOOR CONDUIT OR CABLE VERTICAL DOWN CONDUIT OR CABLE VERTICAL UP CONDUIT STUB - TERMINATE WITH BUSHING OR CAP IF UNDERGROUND BREAK LINE CONDUCTORS - NOT CONNECTED JUNCTION BOX PULLBOX - SIZE AS INDICATED OR AS REQUIRED BY CODE DETAIL REFERENCE SECTION REFERENCE ELEVATION REFERENCE 1 X XX.XX X XX.XX X XX.XX SECTION IDENTIFICATION NUMBER SHEET WHERE SECTION IS DRAWN ELEVATION IDENTIFICATION NUMBER SHEET WHERE ELEVATION IS DRAWN DETAIL IDENTIFICATION NUMBER SHEET WHERE DETAIL IS DRAWN DRAWING CONSTRUCTION ("FLAG") NOTE MATCHLINE REVISION CLOUD (ENCIRCLES DRAWING CHANGES MADE SINCE THE PREVIOUS RELEASE) REVISION REFERENCE NORTH REFERENCE EQUIPMENT IDENTIFIERX-XX EXISTING TO BE REMOVED (HATCH) HEAVY LINEWEIGHT INDICATES NEW WORK LIGHT LINEWEIGHT INDICATES EXISTING INFORMATION 1 N XX TT T T SINGLE-POLE WALL SWITCH MOUNT SWITCHES AT 48" AFF. TO CL, UON. WALL SWITCH - SUBSCRIPT 2 = 2-POLE LV = LOW-VOLTAGE 3 = 3-WAY OS = OCCUPANCY SENSOR TYPE 4 = 4-WAY OP = OCCUPANCY/PHOTOELECTRIC TYPE K = KEYED WP = WEATHERPROOF D = LINE VOLTAGE DIMMER LOWER CASE LETTER INDICATES SWITCHING GROUP MOUNT SWITCHES AT +48" AFF. TO CL, UON. ANY COMBINATION OF SWITCH TYPES CAN BE USED (IE. 3K = 3-WAY KEYED SWITCH) NEMA 5-20R, +18" AFF UON TAMPER RESISTANT, NEMA 5-20R, +18" AFF UON NEMA 5-20R W/ GROUND FAULT CIRCUIT INTERRUPTER, +18" AFF UON SPLIT WIRED, NEMA 5-20R, +18" AFF UON CONTROLLED, NEMA 5-20R, +18" AFF UON NEMA 5-20R MOUNTED ABOVE COUNTER. COORDINATE WITH CASEWORK SHOP DRAWINGS AND ARCHITECTURAL DRAWINGS. NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER, ABOVE COUNTER. COORDINATE WITH CASEWORK SHOP DRAWINGS AND ARCHITECTURAL DRAWINGS. TAMPER RESISTANT, NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER, ABOVE COUNTER. COORDINATE WITH CASEWORK SHOP DRAWINGS AND ARCHITECTURAL DRAWINGS. SPECIAL PURPOSE RECEPTACLE TYPE AS SHOWN ON PLANS CEILING-MOUNTED, NEMA 5-20R PUSH BUTTON NEMA 5-20R WITH USB CHARGER - (2) TYPE A USB PORTS T TAMPER RESISTANT, NEMA 5-20R WITH USB CHARGER - (2) TYPE A USB PORTS ABBREVIATIONS GENERAL NOTES: 1. SYMBOLS LEGENDS ARE PROVIDED FOR REFERENCE PURPOSES ONLY. THE SYMBOLS REPRESENT THE TYPE OF DEVICES THAT MAY BE REQUIRED IN THE WORK; QUANTITIES AND LOCATIONS ARE AS SHOWN ON THE PLAN SHEETS. 2. PROVIDE 3/4" CONDUIT & #12 CONDUCTORS UNLESS NOTED OTHERWISE. PROVIDE ONE NEUTRAL CONDUCTOR FOR EACH UNGROUNDED CONDUCTOR OF SINGLE PHASE LINE-NEUTRAL BRANCH CIRCUITS. DO NOT SHARE NEUTRAL CONDUCTORS. 3. EACH FEEDER AND BRANCH CIRCUIT CONDUIT SHALL HAVE AN EQUIPMENT GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH NFPA 70, ARTICLE 250. 4. ALL ELECTRICAL EQUIPMENT IN PORTIONS OF THE BUILDING NOT BEING REMODELED SHALL BE LEFT IN WORKING CONDITION. RESTORE ANY CIRCUITS INTERRUPTED. 5. ALL NEW LIGHT FIXTURES AND FIXTURES IN AREAS ADJACENT DEMOLITION & CONSTRUCTION AREAS ARE TO BE THOROUGHLY CLEANED IMMEDIATELY PRIOR TO NOTICE OF SUBSTANTIAL COMPLETION. 6. THE FOLLOWING IS PART OF THIS PROJECT AND ALL COSTS PERTAINING THERETO SHALL BE INCLUDED IN THE BASE BID: A. NEW ELECTRICAL EQUIPMENT AND APPARATUS SHALL BE COORDINATED AND CONNECTED INTO THE EXISTING SYSTEM AS REQUIRED. B. POWER WIRING AND CABLE INSTALLATIONS SHALL BE CONCEALED ABOVE ACCESSIBLE CEILINGS AND IN WALLS. EXPOSED WIRING SHALL BE INSTALLED IN APPROVED SURFACE METAL RACEWAY WHERE INDICATED. C. WHERE EXISTING CONDUITS ARE INDICATED FOR REUSE, FIELD VERIFY INTEGRITY OF REUSED RACEWAYS PRIOR TO INSTALLATION OF CONDUCTORS. PROVIDE NEW RACEWAYS WHERE EXISTING ARE UNUSABLE. D. LOCATIONS OF ALL EXISTING WALL MOUNTED DEVICES SUCH AS SWITCHES, RECEPTACLE, AND OUTLETS ARE SHOWN DIAGRAMMATICALLY. VISIT THE SITE TO CONFIRM EXACT DEVICE LOCATIONS AND COORDINATE INSTALLATIONS WITH FIXED CASEWORK, DOORS AND RELITES. E. PROVIDE PENETRATIONS THROUGH WALLS, FLOORS, AND CEILINGS AS REQUIRED. PROVIDE SUITABLE FIRE RATED MATERIALS AND SEAL ALL CEILING, FLOOR, AND WALL PENETRATIONS TO MATCH FIRE RATING OF SURFACES PENETRATED. DEMOLITION NOTES: A. THE EXISTING CONDITIONS SHOWN WERE TAKEN FROM AVAILABLE RECORD INFORMATION. FIELD VERIFY ALL CONDITIONS THAT MAY AFFECT CONSTRUCTION. IF ANY DISCREPANCIES ARE DISCOVERED, NOTIFY THE ENGINEER IN WRITING AND REQUEST DIRECTION PRIOR TO COMMENCING WORK. B. EXISTING LIGHT FIXTURES SHALL BE CAREFULLY REMOVED (DO NOT DAMAGE) AND RETURNED TO THE OWNER. C. ANY AND ALL EQUIPMENT HAVING ELECTRICAL CONNECTIONS THAT REQUIRE DISCONNECTING AND/OR RE-CONNECTING AS A RESULT OF CONSTRUCTION SHALL BE INCLUDED AS A PART OF THIS CONTRACT. D. THE EXISTING ELECTRICAL DEVICES, CONDUIT, AND/OR EQUIPMENT THAT FOR ANY REASON OBSTRUCTS CONSTRUCTION SHALL BE RELOCATED UNLESS OTHERWISE NOTED. LOCATION IS TO BE AS CLOSE AS POSSIBLE TO THE ORIGINAL LOCATION. E. ALL CIRCUITS, CONDUIT AND WIRE THAT ARE NOT TO REMAIN IN SERVICE SHALL BE REMOVED BACK TO THE FIRST ACCESSIBLE JUNCTION BOX WHERE IT SHALL BE TIED OFF AND LABELED AS SPARE WITH CIRCUIT NUMBER INDICATED. F. REMOVE ALL ABANDONED WIRE AND CABLING. @ AT A/C AIR CONDITIONING(ER) A (AMP) AMPERE AC ABOVE COUNTER, ALTERNATING CURRENT ADJ ADJUSTABLE ADJT ADJACENT AFF ABOVE FINISHED FLOOR AIC AMPERE INTERRUPTING CAPACITY ALT ALTERNATE ANN ANNUNCIATOR ARCH ARCHITECT; ARCHITECTURAL AUTO AUTOMATIC AUX AUXILIARY AWG AMERICAN WIRE GAUGE BKR BREAKER BLDG BUILDING C CONDUIT CAP CAPACITY CATV CABLE TELEVISION CB CIRCUIT BREAKER CKT CIRCUIT CLG CEILING CLR CLEAR COL COLUMN COM COMMUNICATION CPS CYCLES PER SECOND CT CURRENT TRANSFORMER CTL CONTROL CU COPPER DC DIRECT CURRENT DISC SW DISCONNECT SWITCH DISC DISCONNECT DN DOWN DWG DRAWING E EXISTING EDH ELECTRIC DUCT HEATER EF EXHAUST FAN EGC EQUIPMENT GROUNDING CONDUCTOR EL ELEVATION ELEC ELECTRICAL ELEV ELEVATOR EM EMERGENCY ENCL ENCLOSURE ENTR ENTRANCE EQUIP/EQP EQUIPMENT EWC ELECTRIC WATER COOLER EWH ELECTRIC WATER HEATER EXH EXHAUST EXT EXTERIOR EXIST EXISTING F FAHRENHEIT/FUSE FA FIRE ALARM FARA FIRE ALARM REMOTE ANNUNCIATOR FACP FIRE ALARM CONTROL PANEL FC FOOTCANDLE FCU FAN COIL UNIT FD FIRE DAMPER FDR FEEDER FIXT FIXTURE FLA FULL LOAD AMPS FSD FIRE/SMOKE DAMPER GFI GROUND FAULT CIRCUIT INTERRUPTER GFR GROUND FAULT RELAY H HIGH HOR HORIZONTAL HP HORSEPOWER HR HOUR HT HEIGHT HW HOT WATER HZ HERTZ IBC INTERNATIONAL BUILDING CODE IC INTERCOM IES ILLUMINATING ENGINEERING SOCIETY IEEE INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS IG ISOLATED GROUND IMC INTERMEDIATE METAL CONDUIT JB JUNCTION BOX KCMIL THOUSAND CIRCULAR MILLS KVA KILOVOLT AMPERES KVAR KILOVOLT AMPERES REACTIVE KW KILOWATT KWH KILOWATT HOUR LBS POUNDS LF LINEAR FEET (FEET) LS LIFE SAFETY LT LIGHT LTG LIGHTING LV LOW VOLTAGE MAG MAGNETIC MAN MANUAL MAT MATERIAL MAX MAXIMUM MCA MINIMUM CIRCUIT AMPACITY MCB MAIN CIRCUIT BREAKER MECH MECHANICAL MIN MINIMUM MISC MISCELLANEOUS MLO MAIN LUG ONLY MOCP MAXIMUM OVERCURRENT PROTECTION MTD MOUNTED MTG MOUNTING MTR MOTOR N NEUTRAL N/A NOT APPLICABLE NAC NOTIFICATION APPLIANCE CIRCUIT NC NORMALLY CLOSED NEC NATIONAL ELECTRICAL CODE NEMA NATIONAL ELECTRIC MANUFACTURERS ASSOCIATION NESC NATIONAL ELECTRICAL SAFETY CODE NEUT NEUTRAL NFPA NATIONAL FIRE PROTECTION ASSOCIATIONS NIC NOT IN CONTRACT NO NORMALLY OPEN NTS NOT TO SCALE OC ON CENTER OFCI OWNER FURNISHED CONTRACTOR INSTALLED OL OVERLOAD P PRIMARY PA PUBLIC ADDRESS PB PULL BOX PE PHOTO ELECTRIC PF POWER FACTOR PH PHASE PNL PANEL POC POINT OF CONNECTION PWR POWER QTY QUANTITY R RACEWAY RAD RADIUS RECPT/REC RECEPTACLE REF REFRIGERATOR RLA RATED LOAD AMPS RPM REVOLUTIONS PER MINUTE S SOUTH SEC SECURITY SCCR SHORT CIRCUIT CURRENT RATING SD SMOKE DETECTOR SECT SECTION SF SUPPLY FAN SHT SHEET SPD SURGE PROTECTIVE DEVICE SPEC SPECIFICATION SPL SPECIAL SQ SQUARE STOR STORAGE SW SWITCH SWBD SWITCHBOARD SYM SYMMETRICAL SYS SYSTEM T THERMOSTAT TB TERMINAL BOX TC TIME CLOCK TEL TELEPHONE TV TELEVISION TYP TYPICAL UFC UNIFORM FIRE CODE UG UNDERGROUND UH UNIT HEATER UL UNDERWRITERS LABORATORIES UON UNLESS OTHERWISE NOTED V VOLT VAV VARIABLE AIR VOLUME VEL VELOCITY VM VOLTMETER VOL VOLUME W WATT, WEST W/ WITH W/O WITHOUT WH WATER HEATER WHM WATT HOUR METER WP WEATHERPROOF X REACTANCE XFMR TRANSFORMER XMTR TRANSMITTER Z IMPEDANCE & AND I.E.: THAT IS LIGHTING NOTES: 1. LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS ZONED ON THE LIGHTING PLANS. SWITCHING AND DIMMING ZONES ARE INDICATED ADJACENT TO EACH FIXTURE. 2. MANUAL CONTROLS SHALL ALLOW OCCUPANTS TO UNIFORMLY REDUCE ILLUMINATION LEVELS AT LEAST 50%. 3. EACH AREA THAT IS REQUIRED TO HAVE A MANUAL CONTROL SHALL ALSO HAVE AUTOMATIC TIME SWITCH CONTROL. PROVIDE TIMED OVERRIDE SWITCHES THAT WILL SERVE A MAXIMUM AREA OF 2500 S.F. IN LOCATIONS SHOWN ON PLANS. EXCEPTIONS: A. EMERGENCY EGRESS LIGHTING CONTROLLED BY OCCUPANCY SENSORS. B. LIGHTING IN SPACES CONTROLLED BY OCCUPANCY SENSORS. C. INFORMATION TECHNOLOGY (IDF) ROOMS 4. THE MAXIMUM LIGHTING POWER THAT MAY BE CONTROLLED FROM A SINGLE SWITCH OR AUTOMATIC CONTROL SHALL NOT EXCEED THAT WHICH IS PROVIDED BY A 20 AMPERE CIRCUIT LOADED TO NOT MORE THAN 80 PERCENT. 5. PROVIDE FUNCTIONAL TESTING OF AUTOMATIC LIGHTING CONTROLS. SUBMIT WRITTEN PROCEDURES FOR FUNCTIONAL TESTING OF ALL AUTOMATIC CONTROLS WITH DESCRIPTION OF THE EXPECTED SYSTEM RESPONSE. SYMBOLS LEGEND DISCONNECT SWITCH 3-POLE UNLESS NOTED OTHERWISE FUSED DISCONNECT SWITCH 3-POLE UNLESS NOTED OTHERWISE - OVERCURRENT PROTECTION AS REQUIRED BY EQUIPMENT MANUFACTURER OR AS NOTED S F FACP F FIRE ALARM SYSTEM CONTROL PANEL FACP - FIRE ALARM CONTROL PANEL FAA OR FARA - FIRE ALARM ANNUNCIATOR FIRE ALARM PULL STATION FIRE ALARM STROBE ONLY - WALL FIRE ALARM HORN STROBE FIRE ALARM HORN ONLY FIRE ALARM BELL SMOKE DETECTOR FIRE ALARM DUCT SMOKE DETECTOR WITH SAMPLING TUBE XX F XX FIRE ALARM STROBE ONLY - CEILING XX FIRE ALARM SPEAKER STROBE XX FIRE ALARM SPEAKER ONLYS S TV TV OUTLET XX 19" COMMUNICATIONS RACK - WALL MOUNTED 19" COMMUNICATIONS RACK - FLOOR MOUNTED COMMUNICATIONS - OUTLET, +18" UON (# = REPRESENTS THE NUMBER OF COMMUNICATION PORTS. (IE 1,2,3)) (W = SINGLE COMMUNICATIONS PORT WALL MOUNTED AT +54" AFF.) (P = PAYPHONE, WALL MOUNTED AT +48" AFF) WP P A C CR WP ALARM BELL PANIC/DURESS BUTTON CCTV CAMERA - PAN/TILT/ZOOM TYPE. WP INDICATES WEATHERPROOF CCTV CAMERA - FIXED TYPE. WP INDICATES WEATHERPROOF DOOR/WINDOW CONTACT CARD READER. WP INDICATES WEATHERPROOF, ROUGH-IN TO INCLUDE 3/4"R TO J-BOX IN CEILING ABOVE DH DOOR HOLDER CCTV CAMERA - FIXED TYPE. 369 VIEW SECURITY ALARM PANELA 360° HEAT DETECTORH ES ELECTRIC DOOR STRIKE CONNECTION, ROUGH-IN TO INCLUDE 3/4R FROM DOOR FRAME TO J-BOX ABOVE CEILING REX REQUEST TO EXIT CONNECTION, ROUGH-IN SAME AS, OR SHARED WITH, ELECTRIC DOOR STRIKE. DS DAYLIGHT HARVESTING SENSOR 34512 S 16th Ave, Suite A 31230 Federal Way, WA 98003 10 NOVEMBER 2020 600 Stewart St., Ste 1400 Seattle, Washington 98101 Tel 206.267.1700 Fax 206.267.1701 SAZAN # 658-20003 HZD ELECTRICAL SHEET INDEX E0.0 GENERAL NOTES, ABBREVIATIONS, LEGEND AND SHEET INDEX E1.1 ELECTRICAL SCHEDULES E1.2 NREC E2.1 LIGHTING PLAN E3.1 FLOOR PLAN - POWER E3.2 ROOF PLAN - POWER E4.1 ANCILLARY PLAN E5.1 ONE-LINE DIAGRAM AND PANEL SCHEDULES 11/10/2020 RECEIVED CITY OF FEDERAL WAY COMMUNITY DEVELOPMENT Nov 20 2020 34512 S 16th Ave, Suite A 31230 Federal Way, WA 98003 10 NOVEMBER 2020 600 Stewart St., Ste 1400 Seattle, Washington 98101 Tel 206.267.1700 Fax 206.267.1701 SAZAN # 658-20003 HZD 11/10/2020 RECEIVED CITY OF FEDERAL WAY COMMUNITY DEVELOPMENT Nov 20 2020 FIGURE C408.1.4.2 COMMISSIONING COMPLIANCE CHECKLIST Project Information Project Name: Project Address: Certified Commissioning Professional: Certifying Body: Commissioning Plan was used during construction and included items below Commissioning Plan (Section C408.1.2) A narrative description of activities and the personnel intended to accomplish each one Measurable criteria for performance Functions to be tested: Mechanical Systems were included in the commissioning process (Section C408.2) Building mechanical systems have been tested to demonstrate the installation and operation of components, systems and system-to-system interfacing relationships in accordance with approved plans and specifications There are unresolved deficiencies with the mechanical systems. These are described in the Preliminary Commissioning Report submitted to the Owner. The following items are not in compliance with energy code:Commissioned Systems (Sections C408.2, C408.3, C408.4 and C408.6) Service Water Heating Systems were included in the commissioning process (Section C408.3) Service water heating systems have been tested to demonstrate that control devices, components, equipment, and systems are calibrated, adjusted and operate in accordance with approved plans and specifications There are unresolved deficiencies with the service water heating systems. These are described in the Preliminary Commissioning Report submitted to the Owner. The following items are not in compliance with energy code: Electrical Power or Lighting Systems were included in the commissioning process (Section C408.4) Electrical power and automatic lighting controls have been tested to demonstrate the installation and operation of components, systems, and system-to-system interfacing relationships in accordance with approved plans and specifications There are unresolved deficiencies with the electrical power and/or automatic lighting controls. These are described in the Preliminary Commissioning Report submitted to the Owner. The following items are not in compliance with energy code: Additional systems included in the commissioning process (Section C408.5) If additional items were included, list them here: There are unresolved deficiencies with systems required by C406 or C407. These are described in the Preliminary Commissioning Report submitted to the Owner. The following items are not in compliance with energy code: Metering System Functional Testing has been completed (Section C408.6) Energy source meters, energy end-use meters, the energy metering data acquisition system and required display are calibrated adjusted and operate to minimally meet code requirements. There are unresolved deficiencies with the metering system. These are described in the Preliminary Commissioning Report submitted to the Owner. The following items are not in compliance with energy code: FIGURE C408.1.4.2 COMMISSIONING COMPLIANCE CHECKLIST (Continued) Manuals, record documents and training have been completed or are scheduled System documentation has been provided to the owner or scheduled date: _____________________Supporting Documents (Section C103.6) Record documents have been submitted to owner or scheduled date: _________________________ Training has been completed or scheduled date: __________________________________________ Preliminary Commissioning Report submitted to Owner and includes items below:Preliminary Commissioning Report (Section C408.1.4.1) Itemization of deficiencies found during testing that are part of the energy code and that have not been Deferred tests that cannot be performed at the time of report preparation with anticipated date of Status of the project’s record documents, manuals, and systems operation training with respect to corrected at the time of report preparation. completion. requirements in Section 103.6. I hereby certify that all requirements for Commissioning have been completed in accordance with the Washington State Energy Code, including all items above.Certification ---------------------------------------------------------------------------------------------------------------------------------------------- Building Owner or Owner’s Representative Date 34512 S 16th Ave, Suite A 31230 Federal Way, WA 98003 10 NOVEMBER 2020 600 Stewart St., Ste 1400 Seattle, Washington 98101 Tel 206.267.1700 Fax 206.267.1701 SAZAN # 658-20003 HZD 11/10/2020 RECEIVED CITY OF FEDERAL WAY COMMUNITY DEVELOPMENT Nov 20 2020 34512 S 16th Ave, Suite A 31230 Federal Way, WA 98003 10 NOVEMBER 2020 600 Stewart St., Ste 1400 Seattle, Washington 98101 Tel 206.267.1700 Fax 206.267.1701 SAZAN # 658-20003 HZD 11/10/2020 RECEIVED CITY OF FEDERAL WAY COMMUNITY DEVELOPMENT Nov 20 2020 A B C D E 4 3 2 1 NL Electrical/ IS&T Closet 101-22 126 SF Clean Supply/ Equip. Room 101-23 180 SF Exam Room #10 101-32 119 SF Exam Room #8 101-31 95 SF Biohazard/ Soiled Holding 101-11 110 SF Registration 101-03 176 SF Waiting 101-02 400 SF ADA Public Toilet 101-04 54 SF MA Work Stations 101-16 371 SF WC Alcove 18 SF Provider Office 101-15 119 SF Lab 101-07 285 SF Entry Vestibule 101-01 86 SF Exam Room #11 101-33 100 SF Exam Room #6 101-30 95 SF Exam Room #1 101-25 95 SF Exam Room #3 101-24 95 SFADA Patient Toilet 101-08 69 SF Bariatric Exam Room #2 101-20 114 SF Med. Dist. Room 101-18 73 SF Consult Room #1 101-26 101 F Infant Scale Supervisor's Office 101-13 102 SF Provider Office 101-17 129 SF Exam Room #9 101-34 95 SF Exam Room #7 101-35 95 SF Exam Room #5 101-36 95 SF Staff Lounge 101-09 219 SF Lab Waiting 30 SF Vitals Area #1 26 SF Bariatric Exam Room #4 101-21 114 SF Vitals Area #2 17 SF Draw Station #2 101-07B Lab Check-in 31 SF Consult Room #2 101-37 108 SF Draw Station #1 101-07A ADA Patient Toilet 101-27 56 SF ADA Patient Toilet 101-28 56 SF Print Print Hall 101-29 Hall 101-19 Hall 101-05 Hall 101-14 Hall 101-06 ADA Staff Toilet 101-10 48 SF EVS Closet 101-12 12 SF Print LV LVOS LV OS OSOSOS LVALVLVLVDDDDDLV DLVDLVDDDDDDA2-28,R4 A2-28,R4 A2-28,R4 A2-26,R3 A2-26,S1 A2-26,R3 A2-26,R6 A2-26,S1 A2-26,S1 A2-26,R3 A2-26,R3 A2-26,R3 A2-28,R1 A2-28,R1 A2-28,R1 A2-28,R2 A2-28,R2 A2-28,R2 A2-28,R2 A2-28,R2 A2-28,R6 A2-28,R6 A2-28,R6 A2-28,R6E A2-28,R6 A2-28,R6E A2-28,R6 A2-28,R6 A2-28,R6 A2-28,R6 A2-28,R2 A2-28,R2ELVa A2-28,R4 A2-28,R4 A2-28,R4 A2-28,R4 A2-28,R4 A2-28,R4 A2-28,R4 A2-28,R4 A2-28,R4 A2-28,R4 A2-24,R4A2-24,R4 A2-24,R1A2-24,R1 A2-24,R1 A2-24,R1 A2-24,R1 A2-24,R1 A2-24,R1A2-24,R1 A2-26,R2E A2-26,R2 A2-26,R2E A2-26,R2 A2-26,R2E A2-26,R2 A2-26,R2EA2-26,R2A2-26,R2EA2-26,R2A2-26,R2A2-26,R2E A2-26,R2 A2-26,R2 A2-26,R2 A2-26,R2E A2-24,R4 A2-24,R4 A2-26,R6 A2-26,R6 A2-24,R1 A2-24,R1 A2-24,R1 A2-24,R1 A2-24,R1 A2-24,R1 A2-24,R1 A2-24,R1 A2-24,R1 A2-24,R1 A2-26,R2E A2-26,R2 A2-26,R2E A2-26,R2 A2-28,R1 A2-28,R1 A2-24,R1 A2-24,R1 A2-24,R1 A2-24,R1 A2-26,R6 A2-28,R6 A2-28,R6 A2-28,R6 A2-28,R6 A2-28,R6 A2-26,R2E A2-26,R2 A2-28,R5 A2-28,R5 A2-28,R5 A2-26,R6 OS LVA2-26,W1 A2-26,W1 A2-26,W1 A2-26,W1 A2-26,W1 A2-24,R6 A2-26,R6 A2-26,R6 A2-26,R6 MOUNT ABOVE DOOR HEADER A2-26,R6 A2-26,X1 A2-28,X1 A2-26,X1 A2-26,X1 A2-26,X1 A2-26,X1 A2-26,S1 A2-26,S1 TYP1 D LCP PRIMARY ZONE OS OS PRIMARY DAYLIGHT ZONE 1 PRIMARY DAYLIGHT ZONE 2 LVOS OS OS PRIMARY ZONE DAYLIGHT OS OS OS OS OS LVDDLVLV a a a a a EXISTING WALL LIGHT (TYPICAL) 3 2 2 34512 S 16th Ave, Suite A 31230 Federal Way, WA 98003 10 NOVEMBER 2020 600 Stewart St., Ste 1400 Seattle, Washington 98101 Tel 206.267.1700 Fax 206.267.1701 SAZAN # 658-20003 SCALE:NLIGHTING PLAN 1/4"=1'-0" HZD SHEET NOTES: FLAG NOTES: 1 1. SEE LIGHTING FIXTURES SCHEDULE ON SHEET 1.1. 2. ROUTE CORRIDOR, WAITING, ENTRY VESTIBULE AND EXAM ROOM LIGHTING CIRCUIT VIA LIGHTING CONTROL PANEL. 3. SEE ENERGY CODE FORMS ON SHEET E0.02. 4. PROVIDE COMMISSIONING PER ENERGY CODE C405.13 AND C408. 5. COORDINATE LIGHTING CONTROLS SEQUENCE OF OPERATION WITH OWNER. MOUNT FIXTURES IN FRONT AND BACK OF DATA RACKS. COORDINATE LOCATIONS WITH COMMUNICATIONS CONSULTANT PRIOR TO INSTALLATION. DISCONNECT EXISTING SIGN. RETAIN EXISTING SIGN CIRCUIT FOR FUTURE USE. CONNECT LIGHT FIXTURE TO EXISTING BUILDING MOUNTED LIGHTING FIXTURES CIRCUIT. PROVIDE AN UNSWITCHED LIGHTING CIRCUIT FOR BATTERY BACKUP BALLAST. 2 3 11/10/2020 RECEIVED CITY OF FEDERAL WAY COMMUNITY DEVELOPMENT Nov 20 2020 A B C D E 4 3 2 1 TYPICAL EXAM ROOM REF BELOW/FREEZE ABOVE COPIER TV, +84 MICROWAVE COPIER SHREDDER SCALE ADA SCALE Electrical/ IS&T Closet 101-22 126 SF Clean Supply/ Equip. Room 101-23 180 SF Exam Room #10 101-32 119 SF Exam Room #8 101-31 95 SF Biohazard/ Soiled Holding 101-11 110 SF Registration 101-03 176 SF Waiting 101-02 400 SF ADA Public Toilet 101-04 54 SF MA Work Stations 101-16 371 SF WC Alcove 18 SF Provider Office 101-15 119 SF Lab 101-07 285 SF Entry Vestibule 101-01 86 SF Exam Room #11 101-33 100 SF Exam Room #6 101-30 95 SF Exam Room #1 101-25 95 SF Exam Room #3 101-24 95 SFADA Patient Toilet 101-08 69 SF Bariatric Exam Room #2 101-20 114 SF Med. Dist. Room 101-18 73 SF Consult Room #1 101-26 101 F Infant Scale Supervisor's Office 101-13 102 SF Provider Office 101-17 129 SF Exam Room #9 101-34 95 SF Exam Room #7 101-35 95 SF Exam Room #5 101-36 95 SF Staff Lounge 101-09 219 SF Lab Waiting 30 SF Vitals Area #1 26 SF Bariatric Exam Room #4 101-21 114 SF Vitals Area #2 17 SF Draw Station #2 101-07B Lab Check-in 31 SF Consult Room #2 101-37 108 SF Draw Station #1 101-07A ADA Patient Toilet 101-27 56 SF ADA Patient Toilet 101-28 56 SF Print Print Hall 101-29 Hall 101-19 Hall 101-05 Hall 101-14 Hall 101-06 ADA Staff Toilet 101-10 48 SF EVS Closet 101-12 12 SF Print MONITOR, +48" REF +60" +42" +42" MICROWAVE TV +84" +42" COPIER SCALE COPIER COPIER SHREDDER SCALE FIRE ALARM POWER SUPPLY (NAC) MOUNT ON LADDER TRAY ABOVE DATA RACK COPIER MOTORIZED DOOR CONTROLLER REF BELOW/FREEZER ABOVE 1 1 1 1 1 3 5 7 J A1-3,5,7 9,11 4 13 13 13 13 13 17 15 19 34 19 37 37 37 23 35 35 35 4 4 33 30 32 30 3232 32 3030 30 7 97999777791315 4 4 2 4 28 14 22 17 19 17 17 17 17191919 19 21 212323 23 21 21 23 23 4 25 25 2525 25 25 27 29 29 29 29 29 31 31 33353335 35 333739 41 35 2 2 2 2 22 2 4 4 4 2 2222 J A1-1,13 J A1-19,21 J A1-23,25 J A1-33,35 J A1-39,41 J A1-6,8 22 J A1-10,12 JA1-20,22 J A1-24,26 J A1-34,36 J A2-1,3 J A2-30,32 J A2-7,9 J A2-17,19 J A2-21,23 J A2-25,27 J A2-33,35,37 J A2-2,4 J A2-39,41 1 D1 D1 PNL A-1 PNL A-2 22 3 33 3 3 3 3 3 3 3 3 3 M M 29 M M J A2-29,31 J A2-11,13,15 J A1-38,40 J A1-30,32 +42" +42" J A1-16,18 J A1-2,4 J A1-29,31 J A1-22,27 22 J A1-37A1-15,17 19 4 4 1 FOR DURESS PNL WH-1 FC-1 21 19 EXAM TABLE J J J J 5 5 5 J 5 5 5 2 2 34 SECURITY ALARM PANEL 6 6 FC-3 FC-4 FC-2 FC-1 34 FOR CATV MOTORIZE DOOR CONTROLLER M M A2-36 MCMCTO MOTORIZED DOOR AT REAR ENTRY J A2-34 EMS CONTROL PNL 4 M M A1-43 DCP-1 5 J 5 J 5 J 5 3335 DIAGNOSTIC CONSOLE, +44" DEMOLITION NOTES: D1 34512 S 16th Ave, Suite A 31230 Federal Way, WA 98003 10 NOVEMBER 2020 600 Stewart St., Ste 1400 Seattle, Washington 98101 Tel 206.267.1700 Fax 206.267.1701 SAZAN #658-20003 SCALE:NPOWER PLAN 1/4"=1'-0" HZD SHEET NOTES: FLAG NOTES: 1 2 3 4 1. SEE EQUIPMENT CONNECTION SCHEDULES ON SHEET E1.1. REMOVE LOAD CENTER. REMOVE CONDUCTORS AND CONDUIT BACK TO ACCESSIBLE CEILING SPACE. POWER AND CONTROL WIRES UP TO CU-1, ON ROOF. SURFACE MOUNT PANELBOARD. SEE ONE - LINE DIAGRAM, SHT E5.1 FOR ADDITIONAL INFORMATION. SEE TYPICAL EXAM ROOM FOR ELECTRICAL WORK IN THIS AREA. WIRE DEVICES TO CIRCUITS INDICATED AT J-BOX HOMERUN. FIELD COORDINATE LOCATION WITH COMMUNICATIONS SYSTEM SUB CONSULTANT'S DWGS. PROVIDE POWER FOR ELECTRIC DOOR RELEASE. COORDINATE WITH SECURITY SYSTEM CONSULTANT. ROUTE CIRCUITS VIA CHASE. SEE ARCHITECTURAL DRAWING. MOUNT RECEPTACLE FOR UPS BATTERY IN CASEWORK. COORDINATE WITH CASEWORK SUPPLIER'S DWGS AND ARCHITECTURAL DWGS PRIOR TO ROUGH-IN. PLUG REF/FZR INTO UPS. 5 6 7 11/10/2020 RECEIVED CITY OF FEDERAL WAY COMMUNITY DEVELOPMENT Nov 20 2020 A B C D E 4 3 2 1 M M MM M MM M D1 D1M M 6 A2-8,10 A2-20 A2-12,14A2-16,18 WP J A2-6,20 WP WP 6 1 2 2 CU-1 EF-1 CU-3 CU-2 WP 3 3 3 4 4 4 A2-43, 45,47 #10+#12G 5 A2-49,51,53 #10+#12G 5 A2-55,57,59 #10+#12G 5 A1-42,44,46 #10+#12G 5 EXISTING HVAC UNIT TO REMAIN, TYP AC-5 AC-4AC-6AC-7 34512 S 16th Ave, Suite A 31230 Federal Way, WA 98003 10 NOVEMBER 2020 600 Stewart St., Ste 1400 Seattle, Washington 98101 Tel 206.267.1700 Fax 206.267.1701 SAZAN # 658-20003 SCALE: NROOF PLAN - POWER 1/4"=1'-0" HZD FLAG NOTES GENERAL NOTES DEMOLITION NOTES D1 1. SEE EQUIPMENT CONNECTION SCHEDULES ON SHEET E0.1. 2. DO NOT INSTALL CONDUIT DIRECTLY ON ROOF. PROVIDE TREATED WOOD BLOCKS. SECURE TO ROOF STRUCTURE. REMOVE CONDUCTORS AND CONDUIT BACK TO PANEL. SEAL ABANDONED OPENING WATERTIGHT. 1 PROVIDE ROOF PENETRATION FOR CONDUIT INSTALLATION. SEAL OPENING WATERTIGHT. MOUNT +12" ABOVE ROOF. PROVIDE FIELD FABRICATED SUPPORT USING UTILITY CHANNELS. MOUNT +60" ABOVE ROOF. PROVIDE FIELD FABRICATED SUPPORT USING UTILITY CHANNELS. PROVIDE CONTROL WIRES TO ASSOCIATED INDOOR UNIT. INTERCEPT RACEWAY IN CEILING SPACE AND EXTEND TO PANEL. 2 3 4 5 11/10/2020 RECEIVED CITY OF FEDERAL WAY COMMUNITY DEVELOPMENT Nov 20 2020 A B C D E 4 3 2 1 Electrical/ IS&T Closet 101-22 126 SF Clean Supply/ Equip. Room 101-23 180 SF Exam Room #10 101-32 119 SF Exam Room #8 101-31 95 SF Biohazard/ Soiled Holding 101-11 110 SF Registration 101-03 176 SF Waiting 101-02 400 SF ADA Public Toilet 101-04 54 SF MA Work Stations 101-16 371 SF WC Alcove 18 SF Provider Office 101-15 119 SF Lab 101-07 285 SF Entry Vestibule 101-01 86 SF Exam Room #11 101-33 100 SF Exam Room #6 101-30 95 SF Exam Room #1 101-25 95 SF Exam Room #3 101-24 95 SFADA Patient Toilet 101-08 69 SF Bariatric Exam Room #2 101-20 114 SF Med. Dist. Room 101-18 73 SF Consult Room #1 101-26 101 F Infant Scale Supervisor's Office 101-13 102 SF Provider Office 101-17 129 SF Exam Room #9 101-34 95 SF Exam Room #7 101-35 95 SF Exam Room #5 101-36 95 SF Staff Lounge 101-09 219 SF Lab Waiting 30 SF Vitals Area #1 26 SF Bariatric Exam Room #4 101-21 114 SF Vitals Area #2 17 SF Draw Station #2 101-07B Lab Check-in 31 SF Consult Room #2 101-37 108 SF Draw Station #1 101-07A ADA Patient Toilet 101-27 56 SF ADA Patient Toilet 101-28 56 SF Print Print Hall 101-29 Hall 101-19 Hall 101-05 Hall 101-14 Hall 101-06 ADA Staff Toilet 101-10 48 SF EVS Closet 101-12 12 SF Print 2 2 4 4 4 4 4 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 4 2 2 2 2 2 2 DH FOR HDMI CABLE 1 11 1 1 1 1 1 1 1 1 1 4 2 W +54" 2 4 4 42 2 2 2 J J 2 +48" FA NAC PNL 1" TO EXISTING FACP APPROXIMATELY 80' 2 A A 360° 360° 3/4" TYPICAL EXAM ROOM REX REX A DURESS PANEL 3 TYP 5 4 6 6 CATV 6 +84" 7 7 6 8 8 8 8 1 34512 S 16th Ave, Suite A 31230 Federal Way, WA 98003 10 NOVEMBER 2020 600 Stewart St., Ste 1400 Seattle, Washington 98101 Tel 206.267.1700 Fax 206.267.1701 SAZAN #658-20003 SCALE:NFLOOR PLAN - ANCILLARY SYSTEMS 1/4"=1'-0" FLAG NOTES 1 DEMOLITION NOTES 1. DISCONNECT AND REMOVE ALL EXISTING LOW VOLTAGE DEVICES AND WIRES AND CONDUITS BACK TO THEIR RESPECTIVE CONTROL PANELS. 2. DISCONNECT AND REMOVE ALL LOW VOLTAGE CONTROL PANELS. REMOVE POWER CONNECTIONS BACK TO PANELBOARD. HZD 2 SEE TYPICAL EXAM ROOM FOR ELECTRICAL WORK IN THIS AREA. 3/4" FIRE RETARDANT PLYWOOD BACKBOARD, FLOOR TO CEILING. PANIC BUTTON/DURESS BUTTON. PROVIDE CABLE TO DURESS PANEL IN ELECTRICAL/IS&T ROOM. PROVIDE CONNECTION TO EXISTING BUILDING FIRE ALARM CONTROL PANEL. COORDINATE DATA RACK REQUIREMENTS AND LOCATIONS WITH COMMUNICATIONS SYSTEMS CONSULTANT. COORDINATE REQUIREMENTS WITH SECURITY SYSTEMS PROVIDED. ROUTE CABLES VIA CHASE. SEE ARCHITECTURAL DRAWINGS. READER WILL BE SURFACE MOUNTED BUT RACEWAY SHALL ROUTE THROUGH FACADE AND INTO INTERIOR WALL FOR ACCESS TO CEILING. 3 4 5 6 7 8 11/10/2020 RECEIVED CITY OF FEDERAL WAY COMMUNITY DEVELOPMENT Nov 20 2020 (E)TENANT METER BANK TERMINAL BOX 1600A MLO 120/208V, 3Ø, 4W (E) 3SETS, 4-600KCMIL (E)PNL D 200A ML 120/208V (E)PNL A1 200A ML 120/208V (E)PNL A2 200A ML 120/208V PNL A1 200A ML 120/208V PNL A2 200A ML 120/208V (E)PNL 200A ML 120/208V (E)PNL 200A ML 120/208V PB PB (E) UTILITY METER 34512 S 16th Ave, Suite A 31230 Federal Way, WA 98003 10 NOVEMBER 2020 600 Stewart St., Ste 1400 Seattle, Washington 98101 Tel 206.267.1700 Fax 206.267.1701 SAZAN #658-20003 1 FLAG NOTES 1 INTERCEPT EXISTING CONDUIT AND CONDUCTORS IN ACCESSIBLE CEILING SPACE. PROVIDE SPLICE BOX AND EXTEND TO PANEL.1 2"C, 4 #3/0+#6G EXISTING ONE - LINE DIAGRAM SCALE :: NONE HZD 11/10/2020 RECEIVED CITY OF FEDERAL WAY COMMUNITY DEVELOPMENT Nov 20 2020